In this article: Section 30 - Installation of Lighting Equipment. The code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the information you need. This series of articles provides a guide to help users find their way through this critical document. The series is not intended to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook, but will hopefully provide some help in navigating the code.

Section 30, as outlined in rule 30-000 Scope, is a supplementary or amendatory section of the code and provides additional and specific requirements for the location, installation, wiring, protection, and control of all lighting equipment. Appendix B contains important additional helpful notes and the CEC Handbook contains helpful information on determining conductor sizes and protection ratings.

Rule 30-002 - Special terminology, has definitions for terms specifically used in this section for specific types of lighting:

  • Cabinet lighting systems, undercabinet lighting systems and landscape lighting systems are complete extra-low-voltage lighting assemblies that are packaged by the manufacturer and which include installation instructions.
  • Cable lighting systems are extra-low-voltage lighting systems with bare secondary conductors for one or more luminaire heads, commonly referred to as trapeze lighting.
  • Recessed luminaires, Type IC, Inherently protected, Non-IC, and Non-IC with marked spacing are luminaires intended to be wholly or partially recessed in a ceiling or surface and are either intended to be in contact with insulation, not in contact with insulation, in contact with insulation but inherently thermal protected, or not in contact with specifically marked spacing.

General

Rules 30-100 to 30-110 cover general requirements for the installation and wiring of luminaires, lampholders, incandescent filament lamps, electric discharge lamps and associated electrical equipment.

Rule 30-102 requires that branch circuits for luminaires, etc. be limited to a nominal system voltage of 347/600volts and 150 volts-to-ground in dwelling units.

Rule 30-104 requires that the rating of protection of luminaires be based on the voltage involved, whether in a dwelling unit or non-dwelling unit, and type and arrangement of the luminaire as per sub rules (a) to (d).

Rule 30-106 requires that the overcurrent device for high-intensity discharge lighting equipment shall not be included in the luminaire or ballast box unless the combination is so marked.

Rule 30-108 requires that, except for cases of line-to-line voltage, luminaires shall be polarized so that the identified conductor is attached to the identified terminal.

Rule 30-110 requires the non-current carrying metal parts of luminaires to be bonded to ground as per the rules of Section 10.

Location of lighting equipment

Rule 30-200 provides requirements for luminaires when installed near or over combustible material.

Rule 30-202 outlines the requirements for luminaires installed in show windows.

Rule 30-204 gives restrictions on the location of luminaires installed in, and prohibits the installation of some types of luminaires in clothes closets.

Installation of lighting equipment

Rules 30-300 to 30-308 provide requirements for the installation of all lighting equipment. These rules cover such areas as preventing exposure of live parts, proper supporting of luminaires, providing covers for associated outlet boxes, providing adequate wiring space for conductors and connections and preventing temperatures exceeding conductor ratings.

Rules 30-308 to 30-310 provide requirements for circuit connections and for the insulation of conductors when the luminaire is used as a raceway.

Rules 30-312 to 314 provide requirements governing the installation of luminaires with combustible shades and enclosures and protection of luminaires below a minimum height. (Note that these requirements reflect requirements in the National Building Code as referenced in Appendix G.)

Rules 30-316 to 30-322 provide requirements for luminaires installed in damp or wet locations, lighting equipment in damp locations near grounded metal, where exposed to flying objects, and for totally enclosed gasketted luminaires.

Wiring of lighting equipment

Rules 30-400 to 30-412 provide requirements for wiring of all lighting equipment. They cover wiring of luminaires, colour coding of conductors, conductor insulation, exposed wiring on suspended luminaires, wiring of ceiling outlet boxes, wiring of show window luminaires and the use of tap connection conductors.

Luminaires in buildings of residential occupancy

Rules 30-500 to 30-510 provide specific requirements and locations for lighting equipment installed in any and all residential occupancies. These rules specify the location of lighting equipment at entrances, in dwelling units, stairways, basements, storage rooms, garages and carports. (Note that these requirements reflect requirements in the National Building Code as referenced in Appendix G.)

Lampholders

Rules 30-600 to 30-608 are the requirements for the installation of lampholders. These rules cover the connection of the identified conductor to lampholders, switched lampholders used on an unidentified circuit, luminaires with pull-type switch mechanisms, lampholders in wet or damp locations, and pendant lampholders.

Electric-discharge lighting systems operating at 1000 V or less

Rules 30-702 to 30-712 provide the requirements for the non-use of oil-filled transformers, installation on DC circuits, voltages in dwelling units, installation of auxiliary equipment such as reactors, capacitors, and resistors, control of luminaires, and branch circuit capacity.

Electric-discharge lighting systems operating at more than 1000 V

Rules 30-802 to 30-822 cover prohibition of equipment with voltage of more than 1000 volts in dwelling units, installation of lighting system control, transformer ratings, prohibition of liquid –filled transformers except for non=flammable liquids, secondary connection of transformers, location of transformers, wiring methods, transformer loading, lamp supports, lamp terminals and lampholders, and marking.

Recessed luminaires

Rules 30-902 to 30-908 provide the requirements for the installation and spacing of various types of IC, non-IC and designed-for-non-combustible-surfaces luminaires recessed in cavities in ceilings or walls.

Rule 30-910 provides requirements for the wiring of recessed luminaires.

Permanent outdoor floodlighting installations

Rule 30-1000 specifies that the requirements of this part are for installation of permanent outdoor floodlighting installations mounted on poles or towers and with the understanding that, except for changing of lamps, all maintenance is done by qualified persons.

Rules 30-1002 to 30-1014 cover service equipment, underground wiring methods, wiring methods on poles, disconnecting means at poles, overcurrent protection of pole-top branch circuits, branch circuit wiring, and joints.

Rules 30-1016 and 30-1020 are requirements for the location and overcurrent protection of transformers.

Rule 30-1020 covers the switching requirements for floodlights.

Rules 30-1022 to 30-1032 cover the grounding and bonding of outdoor floodlight installations.

Rules 30-1034 and 30-1036 covers types of equipment permitted and climbing steps on poles.

Exposed wiring for permanent outdoor lighting

Rules 30-1100 to 30-1120 provide the requirements for the installation of exposed wiring for permanent outdoor lighting other than floodlighting where the circuits are run between buildings or poles. These rules cover conductor types, use of insulators, height of conductors, spacing from combustible material, spacing of conductors, lampholders, protection of lampholders, use and construction of messenger cables, and branch circuit loading and protection.

Extra-low-voltage lighting systems

Rules 30-1200 to 30-1208 are the requirements for extra-low-voltage lighting systems and provide guidelines for sources of supply and the installation of landscape, cable and cabinet and undercabinet lighting systems.

In the next instalment, we will be discussing Section 32 - Fire Alarm Systems, Fire Pumps, and Carbon Monoxide Alarms.

* The source for this series of articles is the Canadian Electrical Code, Part I, published by CSA

William (Bill) Burr is the former Chair of the Canadian Advisory Council on Electrical Safety (CACES), former Director of Electrical and Elevator Safety for the Province of BC, and former Director of Electrical and Gas Standards Development and former Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting billburr@gmail.com.

 

Changing Scene

  • Prev
  Eaton is pleased to announce the appointment of Rahul Duggal to the position of Product ...
Is it possible for the Ideal Nationals competition to be even more exciting? That question will be ...
The Solar Energy Society of Alberta and Energy Efficiency Alberta, in partnership with the ...
Nat will develop and execute on key sales strategies along with leading his team to drive strong ...
John MacDonald (better known as Satch) has decided that he will retire from Ideal Supply at the end ...
Aspiring skilled trades participants recently descended upon annual Skills Competitions held in ...
Join WiRE and partners 20/20 Catalysts Program and the Aboriginal Apprenticeship Board of Ontario ...
A new program launched by Nova Scotia with federal government support will provide rebates of up to ...
The National Electrical Contractor Association announced on June 18 that Southwire has been ...
Located 160 kilometres west of the Porcupine mine in Chapleau, Ontario, Borden is set to be ...

Electrician Forum Brought to you by Schneider Electric

As industry experts you know the products you use everyday better than anyone and should have input on what information you receive about products and what could improve them.

Therefore, we want your insight on the biggest challenges or issues you face when installing loadcentres, breakers (CAFI, GFI's…) and other surge protection devices. We ask that you do not provide product specific details but rather your general issues and concerns or any questions that have come to mind while working with these product types. Provide us with your valued expert insight into the issues you have faced so manufacturers can better inform you about the installation and use of these products. Lets generate some discussion that will help guide the Industry.

Make your comments  HERE

 

Codes and Regulations Brought to You by the CSA Group

  • Prev
In this article: Section 58 — Passenger Ropeways and Similar Equipment. Rule 58-000 ...
  Unauthorized CSA Group certification marks have been found on wiring by Triumph Cable ...
In this article: Section 52 — Diagnostic imaging installations. The CE code is a ...
In this article: Section 46 — Emergency Power Supply, Unit Equipment, Exit Signs, and ...
  In this article: Section 44 — Theatre Installations. The CE Code is a ...
CSA has published C22.2 No. 60947-7-3, the harmonized standard for low-voltage switchgear and ...
  Electric welders. The CE Code is a comprehensive document. Sometimes it can seem ...
  In this article: Section 40 — Electric cranes and hoists. The CE Code is a ...

 

Cloud

There has been a lot of talk about cloud computing and Software-as-a-Service (SaaS) models these days but both are relatively new to the lighting industry. Let’s take a look at what they are as well as their roles in commercial lighting.

What is cloud computing?

Cloud computing is the on-demand delivery of compute power, database storage, and applications via the Internet with pay-as-you-go or subscription-based pricing. Cloud computing means that instead of all the computer hardware, software, and data that you are using sitting somewhere inside your company’s network, it’s provided and managed for you as a service by another company and you access it over the Internet. 

Read More



Tools for the Trade

  • Prev
  IDEAL Industries has introduced Combination Drill Taps to its tool lineup. Combining the ...
  Stripping and crimping device, 100 - 240 V input voltage, for insulated ferrules with a ...
Professional all-in-one cutter/stripper for coaxial and twisted pair cables     ...
  Klein Tools' Coax Explorrer 2 tests coaxial cable and maps up to 4 locations   ...
  Ideal Industries' T-14 wire stripper s are ideal for all professionals working within the ...
  The ATS850 conveyor eliminates all types of electro static discharge requirements. ...
  Lorik Tool & Automation has the experience and ability to manufacture a variety of ...
  Ideal Industries' 26 piece insulated Journeyman kit is ideal for new electricians or for ...
  Klein Tools Deluxe Fish Rod Set comes in 19 pieces that when assembled can fish wire and ...
  BendWorks Software was designed to help electrical contractors adopt this new process ...

Product News

  • Prev
  Eaton has announced expanded fixtures, controls and accessories for its Halo ...
  The HALO Home Internet Access Bridge (Bridge) enables you to control your HALO Home ...
  The wireless receptacle is an integral part of the WaveLinx Wireless Connected Lighting ...
  The latest in label creation software,  Brady  Workstation has revolutionized ...
Brady’s new ToughStripe Max floor marking tape is ideal for high-traffic areas where sliding ...
  Strip, cut, twist, shear and crimp with one tool. Features four dedicated crimpers for B ...
  The ultimate in UL listed and CSA certified watertight, direct burial ...
  The IDEAL Stripmaster® Model 950™ Wire Stripper is an electrically operated, ...
   Arlington’s zinc MC cable fittings, for dry locations, are convenient and ...
  Suitable for installation in cable trays in dry, damp and wet locations or for direct ...

 

Peers & Profiles

  • Prev
  In a recent sit-down Electrical Industry Canada was able to learn a little ...
David Johns is a unique and dedicated individual both at home and in the workplace. At home he is a ...
    Sean Freeman is a vibrant, enthusiastic and selfless individual who has taken his ...
  Automation companies are drivers of innovation, and have penetrated near every industry ...
Total Electrical Solutions was founded in 2013 by Jeremy Herrington in Quispamsis, on the outskirts ...
Andrew MacLeod is a territory sales manager with Leviton Manufacturing of Canada in British ...
  Floyd Lau founded Amptek Technologies in 2002 as an end to end engineering design ...
Mike Marsh, President and CEO of SaskPower, has been a leading figure in Saskatchewan’s ...
Gordon MacDonald is a cheerful, driven individual who loves to be challenged, a trait that suits ...
  Most of us have a difficult enough time managing one job and a home life. However, some ...

Copper $US Dollar price per pound


 

Jean-Marc Myette

By Line Goyette

Meeting people in our industry often comes with surprises. This was the case with Jean-Marc Myette, Business Development Manager of ABB’s Electrification Products Division and chair of the Board of Electro-Federation Canada’s Quebec section. Not only does he know the electrical industry down to the most minute product and technological innovations, he is also a professional car racer on sabbatical, and someone very involved in his business community and personal life.

Read More

 

 

Kerrwil Publications

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2018 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil