Bill BurrBy William (Bill) Burr

The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the information you need. This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook** but will hopefully provide some help in navigating, while reading the code.

The 24th Edition of the CE-C, Part I, (C22.1-18)* is now available from CSA Group. This discussion of Section 78 — Marine Wharves, Docking Facilities, Fixed and Floating Piers, and Boathouses is based on the new edition.

Rule 80-000 notes that this is a supplementary or amendatory section of the code and applies only to the installation of impressed current cathodic protection systems. Appendix B and the CEC Handbook have additional information and descriptions of cathodic protection.

Rule 80-002 provides wiring methods for DC wiring and includes:

  • conformance to Section 12, except for below ground burial of not less than 450mm or 200mm in raceway or with mechanical protection
  • conformance to Section 18 and Section 20 in hazardous areas

Where DC wiring is installed underground below a Section 20 (Annex J20) Class I hazardous area, it may be buried to a depth not less than 450 mm or 200mm in raceway, providing the wiring is in threaded rigid conduit and sealed in accordance with rules 18-104 or 18-154, where it emerges from the ground.

Rule 80-004 requires that DC cathodic protection wiring be a minimum No. 12 AWG, except for instrumentation and reference electrode leads, and be selected in accordance with rule 12-102 (3) with regard to location and conditions of use.

Rule 80-006 specifies that splices, taps and connections made in conductors underground or exposed to the weather must be

  • made by welding, by a positive compression tool, by crimping and soldering, or by means of a copper, bronze, or brass cable connector
  • sealed against moisture by taping or other method as effective as the original insulation
  • connected to piping by thermit welding, or by a clamp of the same material as the piping or anodic to it
  • connected to a tank or other structure with a welded stud, thermit welding or other permanent means
  • sealed against moisture by the application of a material resistant to any corrosive environment

Rule 80-008 requires that the cathodic protection system rectifier be provided with a dedicated circuit in accordance with the requirements of Section 12.

Rule 80-010 outlines that each rectifier unit of a cathodic protection system have a separate disconnecting means installed

  • readily accessible
  • within sight of, and
  • within 15 m of the unit, or
  • integral to the rectifier and equipped with barriers or other suitable means to protect service personnel from live parts on the line side
  • rendered inaccessible to unauthorized persons by a lockable cover
  • labelled in a conspicuous, legible, and permanent manner identifying it as the disconnecting means for a cathodic protection system

Rule 80-012 requires that where the available operating voltage is more than 50V

  • the voltage difference between exposed points of the protected system, or
  • any point in the vicinity of the anodes, and any point 1m away on the earth's surface, not exceed 10V.

Rule 80-014 requires that the following warning signs and drawings be provided:

  • a marking warning on tanks, pipes and structures that the cathodic protection system not be disconnected unless the power source is turned off
  • a sign, in a conspicuous location adjacent to the disconnecting means of electrical apparatus connected to the cathodically protected structures, advising that the cathodic protection be turned off and a temporary cathodic protection bypass conductor, appropriately sized for maximum available current, be installed before equipment or piping is replaced or modified
  • in a non-hazardous location, a sign advising that the use of a temporary cathodic protection bypass conductor, appropriately sized for maximum available current, may be used as an alternative to turning off the cathodic protection when replacing or modifying the protected equipment
  • a drawing, placed inside or near the rectifier cabinet, showing the location, polarity and anodes of underground cathodic protection wiring
  • a notice, placed in a conspicuous location adjacent to the entranceway of a storage or process container, advising that the cathodic protection system must be turned off before entering the container

In the next instalment, we will be discussing Section 84 – Interconnection of Electric Power Production Sources.

William (Bill) Burr is the former Chair of the Canadian Advisory Council on Electrical Safety (CACES), former Director of Electrical and Elevator Safety for the Province of BC, and former Director of Electrical and Gas Standards Development and former Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting; billburr@gmail.com

* The source for this series of articles is the Canadian Electrical Code, Part I, published by CSA.

**Note the CEC Handbook is also published by CSA.

 

Changing Scene

  • Prev
Joshua Remigio, 29, of Leamington, Ontario was electrocuted last week while working on the property ...
O’Neil Electric Supply is very pleased to announce the addition of Siemens Canada EM LP as ...
Fluke is celebrating its 70th anniversary by giving away a prize package valued at US$6,000. Prizes ...
This past summer, from July 1 to September 15, AD Rewards ran the Redeem for a Dream promotion.
  Rittal Systems Canada, the world’s largest and most trusted manufacturer of ...
Learn about the latest trends in structured cabling. Offered by Fluke Networks, this seminar will ...
  After a decade of creating affordable, energy-efficient LED Lighting exclusively for the ...
Effective January 1, 2019, Ramy Yousif assumes the position of Rexel Atlantic’s General ...
Standard’s Mississauga Sales office has moved to a new location and is now fully operational. ...
Heather and Elaine Gerrie, co-presidents of Gerrie Electric, are this year’s winners of the ...

Electrician Forum Brought to you by Schneider Electric

As industry experts you know the products you use everyday better than anyone and should have input on what information you receive about products and what could improve them.

Therefore, we want your insight on the biggest challenges or issues you face when installing loadcentres, breakers (CAFI, GFI's…) and other surge protection devices. We ask that you do not provide product specific details but rather your general issues and concerns or any questions that have come to mind while working with these product types. Provide us with your valued expert insight into the issues you have faced so manufacturers can better inform you about the installation and use of these products. Lets generate some discussion that will help guide the Industry.

Make your comments  HERE

 

Codes and Regulations Brought to You by the CSA Group

  • Prev
In this article: Section 58 — Passenger Ropeways and Similar Equipment. Rule 58-000 ...
  Unauthorized CSA Group certification marks have been found on wiring by Triumph Cable ...
In this article: Section 52 — Diagnostic imaging installations. The CE code is a ...
In this article: Section 46 — Emergency Power Supply, Unit Equipment, Exit Signs, and ...
  In this article: Section 44 — Theatre Installations. The CE Code is a ...
CSA has published C22.2 No. 60947-7-3, the harmonized standard for low-voltage switchgear and ...
  Electric welders. The CE Code is a comprehensive document. Sometimes it can seem ...
  In this article: Section 40 — Electric cranes and hoists. The CE Code is a ...

 

Cloud

There has been a lot of talk about cloud computing and Software-as-a-Service (SaaS) models these days but both are relatively new to the lighting industry. Let’s take a look at what they are as well as their roles in commercial lighting.

What is cloud computing?

Cloud computing is the on-demand delivery of compute power, database storage, and applications via the Internet with pay-as-you-go or subscription-based pricing. Cloud computing means that instead of all the computer hardware, software, and data that you are using sitting somewhere inside your company’s network, it’s provided and managed for you as a service by another company and you access it over the Internet. 

Read More



Tools for the Trade

  • Prev
  IDEAL Industries has introduced Combination Drill Taps to its tool lineup. Combining the ...
  Stripping and crimping device, 100 - 240 V input voltage, for insulated ferrules with a ...
Professional all-in-one cutter/stripper for coaxial and twisted pair cables     ...
  Klein Tools' Coax Explorrer 2 tests coaxial cable and maps up to 4 locations   ...
  Ideal Industries' T-14 wire stripper s are ideal for all professionals working within the ...
  The ATS850 conveyor eliminates all types of electro static discharge requirements. ...
  Lorik Tool & Automation has the experience and ability to manufacture a variety of ...
  Ideal Industries' 26 piece insulated Journeyman kit is ideal for new electricians or for ...
  Klein Tools Deluxe Fish Rod Set comes in 19 pieces that when assembled can fish wire and ...
  BendWorks Software was designed to help electrical contractors adopt this new process ...

Product News

  • Prev
  Raising the bar in lighting performance, operational efficiency and employee safety, ...
Despite automated solutions, switchgear manufacturing still involves a great deal of manual work ...
Conceived from Karice’s award-winning creations, Olah takes aesthetic inspiration from a ...
Standard has added to its LED tape offering: the line now includes a RGB LED tape option, RGB tape ...
Encoder specialist POSITAL has announced a new generation of analog rotary encoders for position ...
With FANUC's FIELD system, manufacturers can connect ALL of their automation equipment (not just ...
Magic Lite’s new LED parking garage light delivers a bright, uniform illumination for ...
With more work being completed outside of the traditional office setting, having the right tools on ...
  Eaton has announced expanded fixtures, controls and accessories for its Halo ...
  The HALO Home Internet Access Bridge (Bridge) enables you to control your HALO Home ...

 

Peers & Profiles

  • Prev
Allison Wood and Dominique Rivet are two apprentices who had a wealth of career options available ...
  In a recent sit-down Electrical Industry Canada was able to learn a little ...
David Johns is a unique and dedicated individual both at home and in the workplace. At home he is a ...
    Sean Freeman is a vibrant, enthusiastic and selfless individual who has taken his ...
  Automation companies are drivers of innovation, and have penetrated near every industry ...
Total Electrical Solutions was founded in 2013 by Jeremy Herrington in Quispamsis, on the outskirts ...
Andrew MacLeod is a territory sales manager with Leviton Manufacturing of Canada in British ...
  Floyd Lau founded Amptek Technologies in 2002 as an end to end engineering design ...
Mike Marsh, President and CEO of SaskPower, has been a leading figure in Saskatchewan’s ...
Gordon MacDonald is a cheerful, driven individual who loves to be challenged, a trait that suits ...

Copper $US Dollar price per pound


 

Jean-Marc Myette

By Line Goyette

Meeting people in our industry often comes with surprises. This was the case with Jean-Marc Myette, Business Development Manager of ABB’s Electrification Products Division and chair of the Board of Electro-Federation Canada’s Quebec section. Not only does he know the electrical industry down to the most minute product and technological innovations, he is also a professional car racer on sabbatical, and someone very involved in his business community and personal life.

Read More

 

 

Kerrwil Publications

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2018 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil