By William (Bill) Burr

In this article: Section 40 — Electric cranes and hoists. The CE Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the information you need. This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook, but will hopefully provide some help in navigating the code.

40-000 Scope — this is a supplementary or amendatory section of the code and applies to the installation of electrical equipment and circuits for electric cranes, hoists, and monorails. The CEC Handbook provides additional notes and diagrams to better explain this section.

40-002 Supply conductor sizes — because of the short duty of crane and hoist motors, supply conductors are selected from Table 58, which specifically applies to crane and hoist installations.

40-004 Conductor protection — supply conductors for the main contactors of cranes and hoists must be in raceway, armoured cable, or mineral insulated, aluminum-sheathed or copper-sheathed cable. There is an exception to this where a conducting track of conducting rails is used as per 40-018. Where conductors supply the crane or hoist equipment directly and where a flexible connection is necessary, flexible type cord or festoon cable is permitted provided there is a take-up device provided to prevent damage and contact with the floor.

40-006 Overcurrent protection — for main contact supply conductors or directly supplied equipment, the overcurrent protection must be selected as per Rule 28-200 and Tables 29 and D16 for the motor load, plus any allowance as per Rule 14-104 where conductors have been selected with capacity for the other loads on the crane or hoist.

40-008 Disconnecting means — all ungrounded conductors of the main contact conductors must be capable of being simultaneously disconnected quickly for safety in an emergency and for maintenance. The disconnect must be within sight of the main contact conductors or the equipment. In addition, the disconnect must be accessible and be operable from the ground or floor over which the crane or hoist operates.

40-010 Main contact conductors — this rule requires that where there are bare main contact conductors, they must have an ampacity not less than the conductors supplying them and, if wire, shall be not smaller than No. 4 AWG copper, or No. 2AWG aluminum. If the conductors are more than 18 m long, then the minimum size must be No. 2 AWG copper or No. 1/0 AWG aluminum unless intermediate strain relief is provided by clamp type insulating supports. Bare conductors may be hard drawn copper, aluminum wire, or steel or other suitable metal in the form of angles, tees, T-rails, or other rigid shapes.

40-012 Spacing of main contact conductors —because bare main contact conductors depend on free air space to provide insulation between phases and to ground, this rule outlines the minimum support separation required of main contact conductor wires installed in a horizontal plane of 75mm for monorail hoists and 155 mm for other than monorail hoists. If installed in other than a horizontal plane, the separation of the main contact conductor wire supports must be 200mm. They should also be supported so that the extreme limit of displacement maintains a separation of 38mm from any surface. Where the bare main contact conductors are rigid, the supports must provide a minimum separation of 25mm between conductors, collectors, and any surface.

40-014 Supporting of main contact conductors — in addition to the spacing required in rule 40-012, the main contact conductor wires must be stretched between strain insulators at each end and supported throughout the length at 6m intervals. If building conditions preclude supporting at 6m intervals, it may be increased to a maximum of 12m intervals providing the separation between contact conductors is increased by the same proportion. In the case of rigid main contact conductors, insulated supports must be spaced at intervals of up to 80 times the vertical height of the conductor but not more than 4.5m. Refer to the CEC Handbook for diagrams illustrating support spacing and calculation notes.

40-016 Joints in rigid contact conductors — this rule outlines the importance of ensuring that any joints made in rigid main contact conductors must maintain the same ampacity of the conductors over the joint to eliminate any overheating.

40-018 Use of track as a conductor — this rule permits a single monorail, tramrail or crane runway track to be used as one of the main contact conductors or supply circuit conductors for one phase of a 3-phase circuit, providing it is derived from a single isolating transformer, does not exceed 300 v, is bonded to ground (see Rule 10-1100 to 10-1108), and any joints meet rule 40-016.

40-020 Guarding of contact conductors — requires that all contact conductors be guarded against inadvertent contact with bare current-carrying parts unless incorporated in an enclosed contact assembly. In addition, as long as a minimum clearance of 6 m between bare contact conductors and grade, floor, or any working surface (including a catwalk) is maintained, guarding of bare contact conductors may not be required.

40-022 Contact conductors not to supply other equipment — this rule prohibits the contact conductors supplying the crane, hoist or monorail feeding other equipment not essential to the operation of the crane, hoist or monorail.
40-024 Bonding — as per Rule 10-406 all exposed non-current carrying parts shall be bonded to ground. In addition, in the case of a track or rail used as a conductor, it shall be bonded in accordance with Rule 40-018. Note that metal wheels on metal rails may provide a low impedance grounding path. A flexible supply connection as per Rule 40-004(2) must contain a bonding conductor.

In the next instalment, we will be discussing Section 42 — Electric welders.

The source for this series of articles is the Canadian Electrical Code, Part I, published by CSA

William (Bill) Burr is the former Chair of the Canadian Advisory Council on Electrical Safety (CACES), former Director of Electrical and Elevator Safety for the Province of BC, and former Director of Electrical and Gas Standards Development and former Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting billburr@gmail.com.

 

 

Changing Scene

  • Prev
 Electro-Federation Canada (EFC) announced the launch of its new brand identity last ...
WANTED: Skilled Electrician. Apprentice. or Team  Must be able to perform a simple wiring ...
  Malcolm Bird, General Manager of Fusetek, and Frank Dunnigan, CEO of Techspan Industries, ...
  EiKO, a manufacturer and distributor of premium lighting products, is expanding its ...
  The new CSA C83-17 offers utilities a comprehensive list of components, with critical ...
  Schneider Electric Canada has just launched Go Green in the City 2018, its global ...
  A new report published by Philips Lighting and SmartCitiesWorld highlights drivers and ...
This ongoing study provides industry with information on the most up-to-date issues and statistics ...

 Electrician Forum Brought to You by Schneider Electric             

The Electrician Forum is a monthly column that provides valuable information to electricians and electrical contractors on current industry trends and concerns. 

Schneider ElectricSponsored by Schneider Electric

In this issue: 

Quite simply put if you feel that job site costing and quote development are a lot of work, you are right! To properly assess a job and estimate the required work time, product costs and various other expenses can take more time than is often feasible for a small company. You need to be spending your time completing projects, which can become difficult if you are spending your hours doing cost analysis. We learned this first hand in last month’s edition of the Electrician Forum when Steve Beeby of Beehive Electric discussed the balance required to own and operate an electrical contracting company.

read more...

Watch a portion of the interview conducted by Electrical Industry Canada with Steve Beeby of Beehive Electric

 

Codes and Regulations Brought to You by the CSA Group

  • Prev
In this article: Section 58 — Passenger Ropeways and Similar Equipment. Rule 58-000 ...
  Unauthorized CSA Group certification marks have been found on wiring by Triumph Cable ...
In this article: Section 52 — Diagnostic imaging installations. The CE code is a ...
In this article: Section 46 — Emergency Power Supply, Unit Equipment, Exit Signs, and ...
  In this article: Section 44 — Theatre Installations. The CE Code is a ...
CSA has published C22.2 No. 60947-7-3, the harmonized standard for low-voltage switchgear and ...
  Electric welders. The CE Code is a comprehensive document. Sometimes it can seem ...
  In this article: Section 40 — Electric cranes and hoists. The CE Code is a ...

Fluke Hammon Healy

As our population grows and consumers continue to rely on technology for both essentials and comfort, the need for power quality has become vital. Fluke is a leader in this field, offering power quality training seminars, as well as employing power quality specialists with years of industry experience.

This month’s personal profile is a double feature of two of Fluke’s senior power quality specialists, Hilton Hammond and Frank Healy.

Hilton Hammond has been with Fluke since 1995, and in 2013 moved into his current position as Power Quality Business Unit Manager. He has a deep and thorough knowledge of power quality and related electrical instrumentation. 

Frank Healy, Power Quality Product Marketing Manager at Fluke since 2006, has been in the industry for well over three decades. He globally manages Fluke’s power quality products, including measuring instruments and precision power analyzers.

Read More



Tools for the Trade

  • Prev
  IDEAL Industries has introduced Combination Drill Taps to its tool lineup. Combining the ...
  Stripping and crimping device, 100 - 240 V input voltage, for insulated ferrules with a ...
Professional all-in-one cutter/stripper for coaxial and twisted pair cables     ...
  Klein Tools' Coax Explorrer 2 tests coaxial cable and maps up to 4 locations   ...
  Ideal Industries' T-14 wire stripper s are ideal for all professionals working within the ...
  The ATS850 conveyor eliminates all types of electro static discharge requirements. ...
  Lorik Tool & Automation has the experience and ability to manufacture a variety of ...
  Ideal Industries' 26 piece insulated Journeyman kit is ideal for new electricians or for ...
  Klein Tools Deluxe Fish Rod Set comes in 19 pieces that when assembled can fish wire and ...
  BendWorks Software was designed to help electrical contractors adopt this new process ...

Latest Articles

  • Prev
In marketing terms, your company’s Net Promoter Score indicates your customers’ ...
Contractors' prices for new non-residential building construction rose 0.8% in the fourth quarter. ...
Clear and consistent marking is becoming increasingly important across all industries, and more and ...

Product News

  • Prev
  Make a design statement with Philips OneSpace luminous ceiling prefab panels and ...
  Philips has a wide variety of tools that can help with all of your lighting projects. No ...
  Ford Transit Cargo Vans Continue To Set New Standards For Taking Care Of ...
  Z11-DW – Deluxe Electrical Package. Steel. Nissan NV200 / City Express. ...
  As the first two and four-channel portable scopes safety rated CAT III 1000V / CAT IV ...
  Meet the new next generation FLIR ONE and FLIR ONE Pro thermal cameras. When connected to ...
  Square Back Shelving Unit with 5 Open Shelves. 14″d x 70″w x 58″h. ...
  Contoured Shelf Unit. Aluminum. 5 Shelves. 96"w x 62 1/2" h    
  The versatile design includes two compartments that can open to a lay-flat position for ...
  Sized to fit through standard 36" doorways. 6" Non-marking casters. Space for a ...

 

Copper $US Dollar price per pound

Kerrwil Publications

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
2016 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil