Canadian Electrical CodeJune 12, 2017

By William (Bill) Burr

In this article: Section 46 — Emergency Power Supply, Unit Equipment, Exit Signs, and Life Safety Systems. The CE Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the information you need. This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook, but will hopefully provide some help in navigating the code.


Rule 46-000 Scope states that Section 46 is a supplementary or amendatory section of the code and applies to the installation, operation and maintenance of emergency power supply and unit equipment intended to provide power to life safety systems, exit signs, and illumination of exit signs in the event of failure of the normal power supply in cooperation with the requirements of the National Building Code of Canada. Appendix B and the CSA CEC Handbook provide additional explanations and diagrams.


Rule 46-002 provides some special terminology for this section and defines emergency power supply, life safety systems and unit equipment in accordance with the terms in the National Building Code of Canada.


The section is divided into 4 parts:

• general rules, which applies to all emergency power supplies and unit equipment
• emergency power supplies
• unit equipment
• exit signs


General


Rule 46-100 specifies that an emergency power supply, including unit equipment, must have adequate capacity for all the equipment that is connected to it in case of a normal power failure.
Rule 46-102 requires that complete instructions for operation, care and monthly testing be posted, under glass, and on the premises, in conformance with the National Building Code of Canada.
Rule 46-104 states that, where batteries are used as the emergency power supply, they must be maintained in proper condition and fully charged.
Rule 46-106 specifies that emergency lights must be on a dedicated emergency circuit, with no other lamps connected to it, and need to be arranged so that the area covered is illuminated even if any one lamp fails.
Rule 46-108 outlines the wiring method for all conductors, with a few exceptions as noted below, required for life safety systems, emergency power supplies, exit signs, and between unit equipment and remote lamps. In addition to the methods outlined in this rule, the National Building Code of Canada or provincial building codes must be referenced for additional requirements for fire protection of conductors that may apply. For additional information see Appendix B and G.

These methods include:
• metal raceway of the totally enclosed type
• cable having a metal armour or sheath
• rigid non-metallic conduit
• electrical non-metallic tubing imbedded in at least 50mm of poured concrete or masonry

Exceptions to this rule include:
• conductors installed in buildings of combustible construction where rules 12-506 to 12-520 apply and may be run as NMSC or in totally enclosed non-metallic raceway
• use of flexible cord and attachment plug for unit equipment in accordance with Rule 46-304(3)
In addition, the above noted conductors must be kept separate from all other conductors and equipment, with the exception of transfer switches and exit and emergency lights with two sources of supply. Also, the supply for any other electrical equipment that is not part of the “life safety system” must not enter any busway, splitter, or other enclosure that is part of the emergency power supply as per rule 46-208.
Emergency power supply
Rule 46-200 notes that Rules 46-202 to 46-212 apply only to central standby power sourced emergency power supplies.

Rule 46-202 outlines that emergency power supplies, in conformance with the National Building Code of Canada, must consist of:
• an automatically rechargeable storage battery with sufficient capacity to maintain at least 91% of full load voltage for a minimum of 30 minutes, or
• an automatically and failure-free starting and transferring generator conforming to CSA C282 with sufficient capacity to carry the full load of the emergency power supply

Note that where storage batteries are used they should not be automobile or lead acid batteries unless they are of the totally enclosed glass-jar type, except by special permission granted under rule 2-030.
Rule 46-204 reaffirms that all power, control and communication conductors required for emergency power supply and installed outside the generator room, must, as per the requirements of the National Building Code of Canada, be protected against fire exposure to maintain continued operation.

Rule 46-206 specifies that an automatic transfer switch, solely accessible to authorized persons, that actuates upon failure of the normal power supply, must control the emergency power supply. Where an area is adequately illuminated by daylight and artificial light is only needed at night, an automatic light-actuated device may be used to control emergency illumination separately in this area.

Rule 46-208 requires that the overcurrent protection for an emergency power supply needs to be coordinated with OC devices, for feeders and circuits supplying life safety and other emergency power supply equipment, to provide selective operation in the event of a fault. These overcurrent devices must be accessible to authorized persons only.

Rule 46-210 outlines that all emergency power supplies need to be equipped with audible and visual trouble signal devices that
• warn of the normal source current failure
• indicate exit signs or life safety systems are supplied from the emergency power supply
• are wired so that they can be silenced, but continually show a red warning or trouble light
• when the system is returned to normal, continue to audibly indicate the need to restore or automatically reset the silencing switch to normal

Rule 46-212 specifies that remote lamps, located some distance from the power supply, must have a voltage drop limited to 5% of applied voltage.

Unit equipment
Rule 46-300 outlines that Rules 46-302 to 46-306 apply to unit equipment for emergency lighting only, as defined in Appendix B.
Rule 46-302 requires the bottom enclosure of unit equipment to be mounted at least 2 meters above the floor where practicable. Note that the definition of practicable includes the synonym “feasible”.

Rule 46-304 specifies the requirements that the supply connections for unit equipment include:
• permanent connection, if the voltage exceeds 250 volts or 24 amps
• flexible cord and attachment plug located 2.5 metres above the floor and within 1.5 metres of the unit equipment, where the ratings above are not exceeded
• automatic actuation upon failure of the normal lighting power supply to the area covered
Rule 46-306 provides the requirements for remote lamps to unit equipment and requires that
• the voltage drop of conductors be limited to 5% of the marked output voltage of the unit equipment
• remote lamps be included in the list of lamps provided for that unit
• the number of lamps connected to a single unit not exceed the power output rating of the unit for the duration of the emergency period
Exit signs

Rule 46-400 requires that exit signs be
• connected to a dedicated circuit, except where connected to a circuit supplying emergency lighting in the same area
• illuminated by an emergency power supply, where emergency lighting is required by the National Building Code of Canada. Note that the NBC requires that exit signs be illuminated continuously, so no switch, time clock, or other disconnecting means may be inserted in the circuit


In the next instalment, we will be discussing Section 50 — Diagnostic Imaging Installations. (Note: Sections 48 and 50 have been deleted in the 23rd Edition)
* The source for this series of articles is the Canadian Electrical Code, Part I, published by CSA
** Note the CEC Handbook is also published by CSA.

William (Bill) Burr is the former Chair of the Canadian Advisory Council on Electrical Safety (CACES), former Director of Electrical and Elevator Safety for the Province of BC, and former Director of Electrical and Gas Standards Development and former Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting billburr@gmail.com.

 

 

Changing Scene

  • Prev
  Southwire Canada has made multiple process and organizational changes to help improve ...
  With the theme “Integrated e-mobility from coast to coast”, EV's call for ...
  Schneider Electric has appointed Christophe de Maistre as Executive Vice ...
  Women looking to enter or continue their education and training in the Electrical Trades ...
  Power management company Eaton has announced that it is joining the Smart Cities ...
  Tesla Inc. is adding nearly 100 new Canadian stops to its growing network of charging ...
The National Drive Electric Week (NDEW) is a nationwide celebration to heighten awareness ...
  Contractors Guild, Ainsworth, Symtech, Plan and ACML donated their services to ...
  Lighting for healthcare presents unique challenges for accommodating the diverse ...

Emily Heitman

 

Schneider Electric has appointed Emily Heitman as Vice President of the Energy business in the U.S. and Canada. Heitman joins Schneider Electric from the ABB Power Products Division where she was the Global Vice President, Marketing & Sales, Distribution Transformers. As Vice President of Schneider Electric’s Energy business, Heitman has profit and loss responsibility for medium voltage switchgear and energy solutions, while also developing and executing commercial strategies that drive growth and market penetration in the U.S. and Canada.

 

 

Read More: Emily Heitman to lead Schneider Electric's... 

 

 

 

Electricians Provide Assistance in TD Centre's 50th Anniversary Illumination Project

Contractors Guild, Ainsworth, Symtech, Plan and ACML donated their services to temporarily reconfigure the buildings' automated lighting systems, while a crew of staff and volunteers worked to open and close blinds on over 6,000 windows across the TD Centre's five towers to create the message "Less is more or" in 100-foot-tall lights.

A media statement called it the largest public art project of its kind undertaken anywhere in the world.

Read more: Electricians Provide Assistance...

 

Codes and Regulations Brought to You by the CSA Group

  • Prev
  Unauthorized CSA Group certification marks have been found on wiring by Triumph Cable ...
In this article: Section 52 — Diagnostic imaging installations. The CE code is a ...
In this article: Section 46 — Emergency Power Supply, Unit Equipment, Exit Signs, and ...
  In this article: Section 44 — Theatre Installations. The CE Code is a ...
CSA has published C22.2 No. 60947-7-3, the harmonized standard for low-voltage switchgear and ...
  Electric welders. The CE Code is a comprehensive document. Sometimes it can seem ...
  In this article: Section 40 — Electric cranes and hoists. The CE Code is a ...

CSA

 

By William (Bill) Burr

In this article: Section 56 — Optical fibre cables. Section 56 is a supplementary or amendatory section of the code and applies to the installation of optical fibre cables in conjunction with all other electrical systems. Rule 56-002 provides a special terminology definition for an Optical Fibre Cable — a cable consisting of one or more optical fibres that transmits modulated light for the purpose of control, signalling or communications.

Rule 56-102 outlines that there are three types of optical fibre cables.



Tools for the Trade

  • Prev
  Ideal Industries' 26 piece insulated Journeyman kit is ideal for new electricians or for ...
  Klein Tools Deluxe Fish Rod Set comes in 19 pieces that when assembled can fish wire and ...
  BendWorks Software was designed to help electrical contractors adopt this new process ...
  This new lock box is ideal for group lockout situations with multiple isolation points ...
  Greenlee has taken their standard storage boxes to the next level with the limited ...
  The SureTest circuit analyzers "look behind walls" to identify wiring problems that can ...
  The Ideal Dispenser is equipped with high-quality adhesive and 3 mil thickness that ...
  The Adjustable cable stripping tool has an intuitive blade design that allows users to ...
  The SIMpull CoilPAK completes the SIMpull Circuit Management System, taking heavy, ...
  The Javelin is a new product that makes drilling holes through stud walls easier. ...

Latest Articles

  • Prev
  The global smart building market is projected to grow from an estimated $US7.42 billion ...
  I spent most of my formative years growing up in a northern British Columbia community, ...
  For many years, electricians and technicians looking for a quick current reading have ...
  The Canadian Electrical Code, Part I, is an integral part of the Canadian electrical ...
  Canadian municipalities issued $7.9 billion worth of building permits in July, ...
Demand for healthcare is outstripping capacity, but Toronto’s Humber River Hospital has a ...
  An iconic architectural feature of the Montreal skyline by day, the Jacques Cartier ...
  In May, Statistics Canada released data from the 2016 census reporting that seniors now ...

Wind Farm

 

Wind technicians have been working to keep Canada’s turbines turning for a long time now.

TransAlta’s Cowley Ridge Wind Farm was one of the first commercial facilities in the country with the original technicians back in 1993 describing their experiences of being “up so high” and that “there was nothing like it.”

Sitting on 25 meter tall lattice work towers, these machines were less than a third of the height of most tubular wind turbine towers today. However, many of the same skills learned on these first sites are still relevant today even though the technology has certainly progressed.

Read More: The Road Behind and the Road Ahead... 

 

 

 

Product News

  • Prev
  Arlington's Bare Wire Ground Clamp is made of solid brass with brass screws that is easy ...
  The Canadian Wire Connector Kit is ideal for service technicians and is easy to use and ...
  Electronic controllers for district heating and domestic hot water systems. The ...
  Nesco provides a wide range of explosion proof fittings for hazardous location sealing. ...
  Our uninterruptible power supplies for AC applications provide a pure sine curve at the ...
  Southwire's SIM pull Copper RW90 is for open wiring and use in raceways (except ...
  Bollards in the standard 42-inch format and lighted columns with a maximum format of 84 ...
  This driver detects the power and voltage needs of the attached OLED and drives the ...
  Delviro Energy's Lite Up Retail LED has a contemporary style that utilizes cutting edge ...
  Applied Strobe Technology's hazardous area warning strobe lights are ideal for visual ...

Copper $US Dollar price per pound

How One Hospital Is Improving Patient Care with Advanced Analytics Demand for healthcare is outstripping capacity, but Toronto’s Humber River Hospital has a solution: a digital Command Centre powered by GE’s Wall of Analytics. As populations grow and age, many hospitals are being stretched past their limits. Rather than apply temporary or partial fixes to address the challenges that underlie this busy, acute care hospital, Toronto’s Humber River Hospital has chosen to implement a holistic, state-of-the-art hospital command centre that will enable it to achieve radical gains in quality and efficiency.

The hospital partnered with GE Healthcare Partners to conceive, design and build the new 4,500 square-foot command centre, a cornerstone of which will be GE’s Wall of Analytics that processes real-time data from multiple source systems across the hospital.

Read more: How One Hospital is ...

 

Kerrwil Publications

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
2016 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil