The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the information you need. This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook** but will hopefully provide some help in navigating, while reading the code. The 24th Edition of the CE-C, Part I, (C22.1-18)* is now available from CSA Group.

In this article: Annex J18, which is permitted, optionally, for use in additions, modifications, renovations or operation and maintenance of existing facilities employing the division system of classification. The rules of Annex J18 are normative (mandatory) where used and amend or supplement other requirements of the Code. Additional informative (non-mandatory) information is contained in Annex JB. Due to the size of this annex, it will be discussed in multiple parts. This is Part A.

Annex J18 is divided into four parts — General, Class I, Class II and Class III locations:

    • Class I location — where flammable gases or vapours may be present in explosive quantities
    • Class II location — where combustible or electrically conductive combustible dusts are present
    •  Class III location — where easily ignitable fibres or flyings are present in sufficient quantities to produce ignitable mixtures

Rule J18-002 provides special terminology definitions for terms used in this section that are supplementary to the definitions in Section 0.

Rule J18-004 Divides Class I locations into


    • Division 1 locations where explosive gas atmospheres are present continuously, intermittently or periodically during normal operation
    • Division 2 locations where explosive gas atmospheres occur only abnormally and for a short time or locations adjacent to a Division 1 where explosive gases could be communicated

Rule J18-006 Divides Class II locations into

    • Division 1 where, under normal operating conditions or abnormal operation or failure of equipment, combustible dust may be in suspension continuously, intermittently or periodically in sufficient quantities to produce explosive or ignitable mixtures, or conduct electricity, and

    • Division 2 where, under infrequent malfunctioning of handling or processing equipment, combustible dust may


        ◦ be present in quantities sufficient to produce explosive or ignitable mixtures but only for short periods of time, or

        ◦ develop combustible dust accumulations on equipment sufficient to interfere with safe dissipation of heat or become ignitable by operational failure of equipment

Rule J18-008 divides Class III locations into

    • Division 1 locations where readily ignitable fibres or materials producing combustible flyings are handled, manufactured, or used
    • Division 2 locations where readily ignitable fibres other than those in process of manufacture are stored or handled

Rule J18-010 provides that unauthorized repairs or alterations shall not be made on live equipment and that equipment shall be maintained in its original safe condition.


The General Part of Annex J18 applies to all installations and equipment installed under this annex.


Rules J18-050 and J18-052 require that electrical equipment installed in Class I, II, or III hazardous locations shall have markings suitable for the class and division in which the equipment is installed and be marked for the class of location and the specific material that will be present:

    • for Class I, the specific gas with the atmospheric Group designation —

        ◦ Group A - acetylene

        ◦ Group B - butadiene, ethylene oxide, hydrogen, manufactured gas), or propylene oxide

        ◦ Group C - acetaldehyde, cyclopropane, diethyl ether, ethylene, hydrogen sulphide, or unsymmetrical dimethyl hydrazine (UDMH), or other gases or vapours of equivalent hazard, or


        ◦ Group D - acetone, acrylonitrile, alcohol, ammonia, benzine, benzoyl, butane, ethylene dichloride, gasoline, hexane, isoprene, lacquer solvent vapours, naphtha, natural gas, propane, propylene, styrene, vinyl acetate, vinyl chloride, xylene, or other gases or vapours of equivalent hazard

    • For Class II, the specific dust with the atmospheric group designations —

        ◦ Group E — combustible metal dust, aluminum, magnesium, and their commercial alloys, and other metals of similarly hazardous characteristics

        ◦ Group F — carbon black, coal, or coke dust, or

        ◦ Group G — flour, starch, or grain dust, and other dusts of similarly hazardous characteristics

Rule J18-054 specifies that the maximum surface temperature rating marked on equipment shall for

    • Class I locations — not exceed the minimum ignition temperature for the location

    • Class II locations — not exceed the lower of the dust cloud or dust layer ignition temperature for the location, or for organic dusts, the lower of 165 degrees centigrade or ignition temperature for the location

    • Class III locations — not exceed 165 °C for equipment that is not subject to overloading and 120 °C for equipment (such as motors or power transformers) that may be overloaded

    • equipment installed in accordance with Rule J18-150 2) or 3) - have surface temperatures at any point on the equipment that may be exposed to an explosive gas atmosphere not to exceed the minimum ignition temperature determined for the hazardous location in which the equipment is installed


    • equipment with no maximum surface temperature rating marked on Class I or Class II equipment - marked for the Class and Group, the maximum surface temperature rating shall be deemed to be 100°C

Rule J18-056 states that each room, section or area must be considered a separate location for determining the classification of the hazard.

Rule J18-058 requires that

    • walls, partitions, floors, or ceilings used to form hazard-free rooms or sections, of equipment rooms, be of substantial construction; built of or lined with non-combustible material, and such that the rooms or sections will remain free from hazards

    • locations within a building that communicate with a Class I, Division 2 location, be separated by close-fitting, self-closing, approved fire doors

    • for communication from a Class I, Division 1 location, the provisions of Rule J18-004 b) ii) apply

Rule J18-060 requires that where

    • exposed overhead conductors supply metal-covered mineral-insulated cable, surge arresters, to limit voltage to 5kV, be installed

    • single-conductor metal-covered cable used in hazardous locations, be installed to prevent sparking between cable sheaths or between cable sheaths and metal bonded to ground; clipped or strapped together in a manner that will ensure good electrical contact between metal coverings, at intervals of not more than 1.8 m, and the metal coverings be bonded to ground; or have the metal coverings continuously covered with insulating material and bonded to ground at the point of termination in the hazardous location only

Rule J18-062 permits the provisions of rules J18-100 to J18-160 to be suspended for Class I location type electrical equipment and wiring located in pressurized equipment rooms or enclosures constructed and arranged so that a protective gas pressure is effectively maintained.


Rule J18-064 requires that intrinsically safe and non-incendive electrical equipment and wiring installed in a hazardous location

    • be provided with, and installed in accordance with, the descriptive system document as described in Appendix F

    • be separated by not less than 50 mm, the metal armour or sheath of cable assemblies, a grounded metal barrier not less than 1.34 mm (No. 16 MSG) thick, or a non-metallic insulating material not less than 1.5 mm in thickness

where insulated conductors of intrinsically safe or non-incendive field wiring are installed in a raceway, compartment, enclosure, outlet, junction box, or any similar fitting, with insulated conductors of any other circuit

    • insulated conductors of different intrinsically safe or non-incendive field wiring circuits may be installed in the same raceway, compartment, outlet, junction box, or multi-conductor cable, provided that the insulated conductors of each circuit are within grounded electrically conductive shields, braids, or sheaths; or the insulated conductors of each circuit have insulation with a minimum thickness of 0.25 mm

    • raceways or cable systems for intrinsically safe and non-incendive wiring and equipment in explosive atmospheres be installed to minimize migration of flammable fluids to other locations


    • apparatus forming part of an intrinsically safe or non-incendive system be identified as such

    • intrinsically safe and non-incendive field wiring circuits be identified at terminal and junction locations


    • wiring methods for intrinsically safe and or non-incendive field wiring circuits be identified with permanently affixed labels, or colour coded light blue where no other cables or insulated conductors coloured light blue are used

Rule J18-066 specifies that electrical equipment suitable for non-hazardous locations may be installed in a Class I, Division 2 hazardous location, and electrical equipment suitable for Class I, Division 2 hazardous locations may be installed in a Class I, Division 1 hazardous location, provided that

    • no specific equipment suitable for the purpose is available


    • the equipment, during its normal operation, does not produce arcs, sparks, or hot surfaces capable of igniting an explosive gas atmosphere

    • the location is continuously monitored by a combustible gas detection system, as described in Appendix H, that

        ◦ activates an alarm when the gas concentration reaches 20% of the lower flammable limit;


        ◦ activates ventilating equipment or other means designed to prevent the concentration of gas from reaching the lower flammable limit when the gas

concentration reaches 20% of the lower flammable limit, where such ventilating equipment or other means is provided;


        ◦ automatically de-energizes the electrical equipment being protected when the gas concentration reaches 40% of the lower flammable limit, where the ventilating equipment is provided;


        ◦ automatically de-energizes the electrical equipment being protected when the gas concentration reaches 20% of the lower flammable limit, where the ventilating equipment cannot be provided; and

        ◦ automatically de-energizes the electrical equipment being protected upon failure of the gas detection instrument.

Rule J18-068 requires electrical equipment with a primary flammable fluid seal in contact with flammable fluids


    • be constructed and installed to prevent migration of flammable fluid through the wiring system, and at pressures lower than the marked maximum working pressure (MWP)

    • Where the above is met through the installation of secondary seals, the possibility of primary seal failure be obviously indicated, or marking means indicating that the enclosure may contain flammable fluid under pressure


Rule J18-070 reiterates that exposed non-current-carrying metal parts of electrical equipment, including the frames or metal exteriors of motors, fixed or portable luminaires or other utilization equipment, luminaires, cabinets, cases, and conduit, shall be bonded to ground in accordance with Section 10.


Rule J18-072 prohibits any uninsulated exposed parts of an electrical installation or of electrical equipment such as conductors, buses, terminals, or components in a hazardous location unless

    • they operate at less than 30 V (15 V in wet locations) and are additionally protected by a type of protection suitable for the location, or


    • as provided for in Rule J18-324 for electric cranes, hoists, and similar equipment in a Class III location


In the next instalment, we will be discussing Part B, Class I locations of Annex J18, of Appendix J.


* The source for this series of articles is the Canadian Electrical Code, Part I, (C22.1-18) published by CSA.
** Note the CEC Handbook is also published by CSA.

William (Bill) Burr is the former Chair of the Canadian Advisory Council on Electrical Safety (CACES), former Director of Electrical and Elevator Safety for the Province of BC, and former Director of Electrical and Gas Standards Development and former Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting billburr@gmail.com.

Changing Scene

  • Prev
Once again, Stelpro is recognized for the design excellence of its products, this time in the ...
Join CSA Group for a free webinar on Wednesday, February 20, 2019. Mitch Rushing, CSA Group ...
Effective September 1, 2019, Keith Assaff and Jody MacDonald will assume the positions of ...
AD, the member owned buying/marketing group, is merging with IDI Independent Distributors Inc. as ...
Ontario’s Ministry of Energy, Northern Development and Mines has designated NextBridge as the ...
Have you encountered electrical safety hazards or identified safety issues that, if not addressed, ...
  Legrand North America is pleased to announce the appointment of Jennifer Eastman as ...
Southwire Canada welcomes Janny Hogen Esch to the role of Manager, Customer Experience, and Sean ...
Standard and Stanpro have announced their planned merger that will take effect later this ...
The Go Green in the City challenge is now entering its 9th year and the 2019 edition is going to be ...

Electrician Forum Brought to you by Schneider Electric

As industry experts you know the products you use everyday better than anyone and should have input on what information you receive about products and what could improve them.

Therefore, we want your insight on the biggest challenges or issues you face when installing loadcentres, breakers (CAFI, GFI's…) and other surge protection devices. We ask that you do not provide product specific details but rather your general issues and concerns or any questions that have come to mind while working with these product types. Provide us with your valued expert insight into the issues you have faced so manufacturers can better inform you about the installation and use of these products. Lets generate some discussion that will help guide the Industry.

Make your comments  HERE

 

Codes and Regulations Brought to You by the CSA Group

  • Prev
The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the ...
The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the ...
In this article: Tables — Part B. This section of the Code contains 99 tables of essential ...
In this article: Section 58 — Passenger Ropeways and Similar Equipment. Rule 58-000 ...
  Unauthorized CSA Group certification marks have been found on wiring by Triumph Cable ...
In this article: Section 52 — Diagnostic imaging installations. The CE code is a ...
In this article: Section 46 — Emergency Power Supply, Unit Equipment, Exit Signs, and ...
  In this article: Section 44 — Theatre Installations. The CE Code is a ...
CSA has published C22.2 No. 60947-7-3, the harmonized standard for low-voltage switchgear and ...
  Electric welders. The CE Code is a comprehensive document. Sometimes it can seem ...

 

Cloud

There has been a lot of talk about cloud computing and Software-as-a-Service (SaaS) models these days but both are relatively new to the lighting industry. Let’s take a look at what they are as well as their roles in commercial lighting.

What is cloud computing?

Cloud computing is the on-demand delivery of compute power, database storage, and applications via the Internet with pay-as-you-go or subscription-based pricing. Cloud computing means that instead of all the computer hardware, software, and data that you are using sitting somewhere inside your company’s network, it’s provided and managed for you as a service by another company and you access it over the Internet. 

Read More

Latest Articles

  • Prev
Much has been written about the moral value and legality of paying interns versus not paying ...
As a 54-year-old low tech guy raised in small town Canada, I sometimes have issues fitting into our ...
Networked lighting control systems (NLCs) are really computer networks — they just happen to ...
As smart buildings rely on more high-power, long-reach applications, such as PONs (passive optical ...

Tools for the Trade

  • Prev
  IDEAL Industries has introduced Combination Drill Taps to its tool lineup. Combining the ...
  Stripping and crimping device, 100 - 240 V input voltage, for insulated ferrules with a ...
Professional all-in-one cutter/stripper for coaxial and twisted pair cables     ...
  Klein Tools' Coax Explorrer 2 tests coaxial cable and maps up to 4 locations   ...
  Ideal Industries' T-14 wire stripper s are ideal for all professionals working within the ...
  The ATS850 conveyor eliminates all types of electro static discharge requirements. ...
  Lorik Tool & Automation has the experience and ability to manufacture a variety of ...
  Ideal Industries' 26 piece insulated Journeyman kit is ideal for new electricians or for ...
  Klein Tools Deluxe Fish Rod Set comes in 19 pieces that when assembled can fish wire and ...
  BendWorks Software was designed to help electrical contractors adopt this new process ...

 

Lumens

This article is an excerpt from a technical brief, “Understanding LM-80, Lumen Maintenance, and LED Fixture Lifetime,” by Philips Color Kinetics.

Test results of lumen maintenance in conventional and LED light sources differ considerably. This is known as the lumen maintenance gap. These tests are performed to determine the useful life of a light source. But how do we compare lighting technologies satisfactorily if test results of a same designation do not mean the same thing? These lumen maintenance measurement distinctions are those we will examine in this article, as a clear understanding of this gap will have a significant impact on the installation, maintenance and replacement cost calculations of lighting products.

Read More

 

Product News

  • Prev
Based in Toronto, A&A Optoelectronics LTD has over ten years’ experience in providing ...
Based in Toronto, A&A Optoelectronics LTD has over ten years’ experience in providing ...
With global ratings, extensive accessory options and enhanced diagnostic capability, the NZM is the ...
The Modular Panel Board System by Square D is an innovative electrical packaging solution that can ...
The Littelfuse Coordination Panel provides a simple, time-saving solution for circuits that require ...
HPS is proud to announce the availability of a complete line transformer products compliant to ...
ABB has launched a new range of PI-Spring terminal blocks for photovoltaic installations that make ...
The 8WH2 spring-loaded terminal is extremely compact design offers a high level of convenience in ...
Rittal RiLine compact busbar systems Board SV 9635 is a showck-hazzard protection busbar board for ...
Schneider Electric's Square D PowerPact unit mount 25A offers 600 Vac/250 Vdc, 3-pole thermal ...

 

Copper $US Dollar price per pound


 

Jean-Marc Myette

By Line Goyette

Meeting people in our industry often comes with surprises. This was the case with Jean-Marc Myette, Business Development Manager of ABB’s Electrification Products Division and chair of the Board of Electro-Federation Canada’s Quebec section. Not only does he know the electrical industry down to the most minute product and technological innovations, he is also a professional car racer on sabbatical, and someone very involved in his business community and personal life.

Read More

 

 

Kerrwil Publications

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2019 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil