Bill BurrIn this article: Section 52 — Diagnostic imaging installations. The CE code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the information you need. This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook**, but will hopefully provide some help in navigating the code.

Rule 52-000 Scope states that Section 52 is a supplementary or amendatory section of the code and applies to the installation of X-ray and other diagnostic imaging equipment operating at any frequency, but does not provide any specifications for safeguards against radiation. Information on radiation safeguards is contained in the series of Health Canada Safety Codes for radiation protection. The CSA CEC Handbook provides additional explanations and tables.

Rule 52-002 provides some special terminology for this section, and defines momentary and long-term ratings of 20 seconds and 5 minutes respectively for operation of applied x-ray and computerized tomography equipment.

Rule 52-004 provides guidelines for guarding of high-voltage parts, and requires that high-voltage parts be contained within bonded to ground metal enclosures, or within separate rooms or enclosures where a circuit control switch controlling the diagnostic imaging equipment is interlocked, to be open when the door is open and unlocked, and be insulated from the enclosure. In addition, high-voltage circuit conductors must be of the shockproof type. If a milliammeter is provided, it must be either connected in the bonded-to-ground circuit conductor, or guarded, if connected in the high-voltage conductor.

Rule 52-006 permits mobile diagnostic equipment, and permanently connected diagnostic equipment on a 30 amp or less branch circuit, to be supplied with a plug and hard-usage cable or cord.

Rule 52-008 specifies that a disconnect must be placed in the supply circuit in a location accessible from the radiation control of the diagnostic equipment. The rating of the disconnect for X-ray or computerized tomography equipment is based on 100% of the power input required for the long-time rating of the equipment, or 50% of the power input required for the momentary rating of the equipment, whichever is greater. For equipment on a 120volt, 30amp circuit, the required disconnect may be a receptacle and plug of the appropriate size.

Rule 52-010 exempts transformers and capacitors, forming part of diagnostic imaging equipment, from the requirements of Section 26. This equipment must comply with the CEC Part II product standard for the equipment. Capacitors must be provided with a means for automatically discharging and grounding the plates when the supply is disconnected. This is not required if the current-carrying parts of the capacitors and conductors are located 2.5 meters or more above the floor and accessible to only authorized persons, or, if located within 2.5 meters of the floor, within

• metal enclosures that are bonded to ground, or
• enclosures of insulating material

Rule 52-012 provides for protection where step-up transformers are used for diagnostic equipment. The low-voltage circuit of the step-up transformer is required to have an overcurrent device with no exposed live parts, installed as part of or adjacent to the equipment that protects the high-voltage radiographic circuit from all fault conditions. Where the above overcurrent device is too large to protect other fluoroscopic or therapeutic circuits on the equipment, additional overcurrent protection needs to be installed to protect these circuits. In the case of portable equipment, the above requirements also apply. However, an exemption can be applied if all high-voltage parts are enclosed in a single metal enclosure, bonded to ground. Where more than one apparatus is supplied by a common high-voltage source, other switches must be installed to independently disconnect each apparatus from the high-voltage source.
Rule 52-014 reiterates that all non-current-carrying parts of apparatus, including ancillary equipment, must be bonded to ground in accordance with the requirements of Section 10.

Rule 52-016 provides the requirements for determining ampacity of supply conductors and rating of overcurrent protection for diagnostic imaging equipment. For a single piece of equipment, use the larger of

• the long-time current rating of the equipment, or
• 50% of the momentary current-rating required on a radiographic setting

Note that this information is contained on the equipment faceplate.

Where more than one piece of diagnostic equipment is supplied, the rating of the supply conductors and overcurrent device is based on

• the sum of the long time current ratings of all the equipment supplied by the circuit, or
• Tthe sum of 50% of the maximum momentary current rating for the two largest units supplied, plus 20% of the maximum momentary current rating of the other units, when the equipment is on a radiographic setting

In the next installment, we will be discussing Section 54 — Community antenna distribution and radio and television installations.

* The source for this series of articles is the Canadian Electrical Code, Part I, published by CSA
** Note the CEC Handbook is also published by CSA.

William (Bill) Burr is the former Chair of the Canadian Advisory Council on Electrical Safety (CACES), former Director of Electrical and Elevator Safety for the Province of BC, and former Director of Electrical and Gas Standards Development and former Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting billburr@gmail.com.

Changing Scene

  • Prev
The Solar Energy Society of Alberta and Energy Efficiency Alberta, in partnership with the ...
Nat will develop and execute on key sales strategies along with leading his team to drive strong ...
John MacDonald (better known as Satch) has decided that he will retire from Ideal Supply at the end ...
Aspiring skilled trades participants recently descended upon annual Skills Competitions held in ...
Join WiRE and partners 20/20 Catalysts Program and the Aboriginal Apprenticeship Board of Ontario ...
A new program launched by Nova Scotia with federal government support will provide rebates of up to ...
The National Electrical Contractor Association announced on June 18 that Southwire has been ...
Located 160 kilometres west of the Porcupine mine in Chapleau, Ontario, Borden is set to be ...
  Schneider Electric, the leader in the digital transformation of energy management and ...
The 2018 IDEAL Nationals Championship is well underway across Canada. In fact, we have reached the ...

Electrician Forum Brought to you by Schneider Electric

Schneider Electric

June 25, 2018

Sponsored by Schneider Electric

Today we are all concerned with the energy we consume within our homes. But how many truly understand the ins and outs of home energy use, and where exactly does the electrician and the development of energy management systems come into play. There is much to consider when discussing home energy use. The consumer first off needs to be informed about energy use, how it is calculated and ultimately billed if they are to make changes to their energy consumption rates. But in terms of educating consumers does the residential electrician have a role? And beyond that are manufacturers developing products designed to help electricians and consumers better understand residential energy use? Throughout this article we will deal with each of these important questions.

Read More

Codes and Regulations Brought to You by the CSA Group

  • Prev
In this article: Section 58 — Passenger Ropeways and Similar Equipment. Rule 58-000 ...
  Unauthorized CSA Group certification marks have been found on wiring by Triumph Cable ...
In this article: Section 52 — Diagnostic imaging installations. The CE code is a ...
In this article: Section 46 — Emergency Power Supply, Unit Equipment, Exit Signs, and ...
  In this article: Section 44 — Theatre Installations. The CE Code is a ...
CSA has published C22.2 No. 60947-7-3, the harmonized standard for low-voltage switchgear and ...
  Electric welders. The CE Code is a comprehensive document. Sometimes it can seem ...
  In this article: Section 40 — Electric cranes and hoists. The CE Code is a ...

 

Schneider

A new “future ready” circuit breaker from Schneider Electric is described by the company as the next generation of power distribution for the Internet of Things (IoT) era. Masterpact MTZ increases efficiency and can adapt to ever-evolving needs for safety, reliability and sustainability. The world is becoming more connected, electric, digitized, decarbonized, and decentralized, says Schneider Electric. Power distribution is facing new regulations, becoming more seamless and connected. 

Masterpact MTZ is the latest in a series of circuit breaker innovations, following Masterpact M, and then Masterpact NT/NW.

Read More



Tools for the Trade

  • Prev
  IDEAL Industries has introduced Combination Drill Taps to its tool lineup. Combining the ...
  Stripping and crimping device, 100 - 240 V input voltage, for insulated ferrules with a ...
Professional all-in-one cutter/stripper for coaxial and twisted pair cables     ...
  Klein Tools' Coax Explorrer 2 tests coaxial cable and maps up to 4 locations   ...
  Ideal Industries' T-14 wire stripper s are ideal for all professionals working within the ...
  The ATS850 conveyor eliminates all types of electro static discharge requirements. ...
  Lorik Tool & Automation has the experience and ability to manufacture a variety of ...
  Ideal Industries' 26 piece insulated Journeyman kit is ideal for new electricians or for ...
  Klein Tools Deluxe Fish Rod Set comes in 19 pieces that when assembled can fish wire and ...
  BendWorks Software was designed to help electrical contractors adopt this new process ...

Latest Articles

  • Prev
In marketing terms, your company’s Net Promoter Score indicates your customers’ ...
Contractors' prices for new non-residential building construction rose 0.8% in the fourth quarter. ...
Clear and consistent marking is becoming increasingly important across all industries, and more and ...

Peers & Profiles

  • Prev
David Johns is a unique and dedicated individual both at home and in the workplace. At home he is a ...
    Sean Freeman is a vibrant, enthusiastic and selfless individual who has taken his ...
  Automation companies are drivers of innovation, and have penetrated near every industry ...
Total Electrical Solutions was founded in 2013 by Jeremy Herrington in Quispamsis, on the outskirts ...
Andrew MacLeod is a territory sales manager with Leviton Manufacturing of Canada in British ...
  Floyd Lau founded Amptek Technologies in 2002 as an end to end engineering design ...
Mike Marsh, President and CEO of SaskPower, has been a leading figure in Saskatchewan’s ...
Gordon MacDonald is a cheerful, driven individual who loves to be challenged, a trait that suits ...
  Most of us have a difficult enough time managing one job and a home life. However, some ...
  Since 2012 Barnstormer has advanced the abilities of their brewery with the installation ...

Copper $US Dollar price per pound


Jeremy Herrington

Total Electrical Solutions was founded in 2013 by Jeremy Herrington in Quispamsis, on the outskirts of Saint John, New Brunswick. Since 2013 Jeremy has steadily grown Total Electrical Solutions in the residential, commercial and construction sectors. The growth is primarily the result of Jeremy’s customer first philosophy, plus his over 20 years of industry experience.

Jeremy grew up learning about the industry from his father who was an electrical contractor. Jeremy spent his early years helping and watching his father as a contractor and business owner. After high school Jeremy was, like many, not wholly aware of the course he wished to take and so he began an electrical apprenticeship at his father’s company.

Read More

Kerrwil Publications

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2018 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil