The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the information you need. This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook** but will hopefully provide some help in navigating, while reading the code.

The 24th Edition of the CE-C, Part I, (C22.1-18)* is now available from CSA Group. This discussion of Section 78 — Marine Wharves, Docking Facilities, Fixed and Floating Piers, and Boathouses is based on the new edition.

In this article: Tables — Part B. This section of the Code contains 99 tables of essential information that is referenced by various Rules of the Code. Tables referenced by Rules are considered normative (mandatory) elements of the Code. Note that the D tables of tabulated information in Appendix D are considered non-normative (non-mandatory) elements. The tables are in numerical order based on when that table was included in the Code. Since this is a large section it will be discussed in two parts. This is Part B covering Tables 36 to 69.

Tables 36A and 36B, referenced by Rule 4-004, provide maximum allowable ampacities for aluminum and copper conductor, respectively, neutral supported cables, based on phase conductor size, and type.

Table 37, referenced by, Rule 28-104, provides motor supply conductor minimum temperature rating based on, an ambient temperature of 30 degrees centigrade, type of motor enclosure, and class rating of the insulation.

Table 38, referenced by Rules 8-202 to 8-210 provides the demand factors for electric vehicle supply equipment, based on the number of automobile spaces or stalls per feeder, and the maximum load in watts per space or stall.

Table 39, referenced by Rule 4-004 (22), provides the minimum permitted service conductors (based on Tables 2 and 4), for 3-wire 120/240 V and 120/208 V for single dwellings and feeder conductor or cable size supplying single dwelling units of row housing, apartment, or similar buildings and terminating on equipment having a conductor termination temperature of not less than 75 °C, and based on the overcurrent device rating, calculated loads, and conductor size for copper or aluminum. Note that this table applies only to conductors sized for loads calculated in accordance with Rules 8-200(1) (a), 8-200 (2), or 8-202 (1).

Table 40, referenced by Rule 12-1006, provides the number of external threads per 25.4 mm (inch), and minimum and maximum length of thread in millimetres per trade size of rigid metal conduit.


Table 41, referenced by Rules 10-614 and 70-126, provides the minimum size of bonding jumper for service raceways per the ampacity of the largest service conductor or equivalent multiple conductors, for either copper or aluminum.

Table 42 is deleted.

Table 43, referenced by Rule 10-102, provides the minimum bare copper conductor size for concrete-encased electrodes, based on the ampacity of the largest service conductor or equivalent multiple conductors.

Table 44, referenced by Rules 8-010 and 28-704, provides full load current for three-phase AC motors by motor rating in horsepower, per rated voltage, and per induction type, squirrel-cage and wound rotor motors, or synchronous type unity power factor motors.


Table 45, referenced by Rules 28-010 and 28-704, provides the full load current for single-phase AC motors by horsepower per 115 or 230 volts.


Table 46 has been moved and is now Diagram 1.

Table 47 has been moved and is now Diagram 2.

Table 48, referenced by Rule 70-104, provides the minimum trade size of conduit for mobile homes per rating of the main overcurrent protection device and whether the system ground is excluded or included.

Table 49, has been moved and is now Diagram 3.

Table 50, referenced by Rule 26-250, for transformers provides the percentage of maximum setting or rating of the primary and secondary overcurrent protection device per the rated impedance of the transformer.

Table 51, referenced by Rules 36-300, 36-308 and Appendix B, provides the minimum size of bare copper grounding conductors for a high-voltage installation, based on the maximum available short-circuit current, the maximum fault duration, and whether the joint is brazed, made by an exothermic weld, compression or bolted joint.

Table 52, referenced by Rules 36-304, 36-306, 36-308, 36-310, and 36-312, provides tolerable touch and step voltages, based on type of ground, soil resistivity in ohms per meter, and fault duration.

Table 53, referenced by Rule 12-012, provides minimum cover requirements in millimeters for direct buried cables or insulated conductors in raceways, based on wiring method, and whether installed in vehicular or non-vehicular areas.


Table 54 has been moved and is now Diagram 4.

Table 55 has been moved and is now Diagram 5.

Table 56, referenced by Rule 2-308, provides the minimum working space around electrical equipment having exposed live parts, based on the nominal voltage to-ground.

Table 57, referenced by Rule 16-210 (6) and Table 5A, provides allowable ampacities for Class 2 copper conductors based on the size of conductor and whether it is a single conductor in free air, or not more than three copper conductors in raceway or cable, and an ambient temperature of 30 degrees centigrade. Where there are more than three conductors in raceway, use the derating factors provided by column 3.

Table 58, referenced by Rule 40-002, for short-time-rated crane and hoist motors, provides ampacities for up to four insulated copper conductors in raceway or cable for the operating temperature and duration, at an ambient temperature of 30 degrees centigrade. For five or more power conductors in raceway or cable, the ampacities shown in this table are reduced by 80%. For ambient temperatures over 30 degrees centigrade, apply the derating factors in Table 5A.

Table 59, referenced by Rule 60-704, provides the minimum size of protector grounding conductors for communications systems, based on the maximum number of protected circuits, and whether they are fused or fuseless.

Table 60, referenced by Rule 16-330, provides allowable ampacities for copper, eight-conductor, Class 2 power and data communication circuit cables, based on conductor and cable size, and number of cables in a bundle.

Table 61, referenced by Rule 68-056, provides the minimum horizontal separation from pools of buried cable, depending on the type of installation (communication or power) and, whether the cable is direct buried unjacketed with bare neutral, cables with a semi-conducting jacket, cables with a non-conducting jacket, or conductors in non-conducting ducts.
Table 62, referenced by Rules 38-013 (2) and 38-014, provides feeder demand factors for elevators, based on the number of elevators on a single feeder.


Table 63, referenced by Rule 20-034, outlines the hazardous areas for propane dispensing, container filling, and storage, based on location, extent of the hazardous location, and the Group IIA hazardous location.


Table 64, referenced by Rules 20-062 and J20-062, outlines the hazardous locations at NGV fuelling facilities, based on location, and the extent of the hazardous location zone or division.

Table 65, referenced by Rules 2-400 and 2-402, provides the enclosure selection table for non-hazardous locations, based on the degree of protection against the environmental conditions, the enclosure type, and whether its for indoor only or Indoor/outdoor use.

Table 66, referenced by Rule 4-004 (22), provides ampacities for bare or covered conductors in free air, based on 40 degrees centigrade ambient temperature, 80 degrees centigrade total conductor temperature, and 610 millimetres per second wind velocity, for both copper and aluminum conductors.

Table 67, referenced by Rule 62-200, provides the minimum clearance requirements for installed space heating systems, based on type of heating system and location, and the types of obstructions and protrusions.

Table 68, referenced by Rule 8-102, provides the maximum insulated conductor length, for 120 V single-phase circuits in dwelling units, measured from the supply side of the consumer’s service to the furthest point of utilization, on a circuit using 90-degree centigrade rated copper insulated conductors, at 30 degrees centigrade ambient temperature, based on size of conductor and overcurrent protection rating.


Table 69, referenced by Rule 20-202, outlines hazardous locations at bulk storage plants, by location, extent of the hazardous location, and the zone of the hazardous location.

In the next instalment, we will be discussing the Diagrams and the Appendices Sections of the Code.

* The source for this series of articles is the Canadian Electrical Code, Part I, (C22.1-18) published by CSA.

** Note the CEC Handbook is also published by CSA.

William (Bill) Burr is the former Chair of the Canadian Advisory Council on Electrical Safety (CACES), former Director of Electrical and Elevator Safety for the Province of BC, and former Director of Electrical and Gas Standards Development and former Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting billburr@gmail.com.

 

Changing Scene

  • Prev
The year was 2002: Jean Chrétien was Prime Minister, Avril Lavigne topped the charts, the ...
The company’s wholesale locations will be branded Robinson Supply, and the lighting and bath ...
The 500+ km transmission line from Edmonton to Fort McMurray includes two substations and involved ...
Poweska is currently BC Hydro’s Executive Vice President, Operations, with responsibility for ...
During E.B. Horsman & Son’s (EBH) Annual General Meeting on March 5, 2019, ABB Canada was ...
The Electrical Safety Association plans to implement a risk-based approach for electrical wiring by ...
Organized by the Hong Kong Trade Development Council, the Hong Kong International Lighting Fair ...
MCEE’s New Product Competition highlights the commitment to efficiency, conservation and ...
Desdowd Inc. has been chosen to serve as Thermon’s manufacturer's agent for the province of ...
Gerrie Electric Wholesale Limited’s website has a fresh new look but continues to offer the ...

Electrician Forum Brought to you by Schneider Electric

As industry experts you know the products you use everyday better than anyone and should have input on what information you receive about products and what could improve them.

Therefore, we want your insight on the biggest challenges or issues you face when installing loadcentres, breakers (CAFI, GFI's…) and other surge protection devices. We ask that you do not provide product specific details but rather your general issues and concerns or any questions that have come to mind while working with these product types. Provide us with your valued expert insight into the issues you have faced so manufacturers can better inform you about the installation and use of these products. Lets generate some discussion that will help guide the Industry.

Make your comments  HERE

 

CSAClimate change and its associated impacts will play a central role in Canada's electricity future. In fact, the Conference Board of Canada estimates that approximately $347.5 billion will need to be invested in electricity infrastructure to maintain the system reliability we have today. Making smart investments now can improve the system and help to avoid more severe climate related costs in the future.

“The critical infrastructure we rely on to power our daily lives must remain resilient to more damaging and frequent extreme weather events,” says Mary Cianchetti, President of Standards at CSA Group. “Standards play a critical role in making that happen.

Read more about climate change solutions...

 

 

 

BCEA Victoria Trade Show

The BC Electrical Association in conjunction with the Victoria distributors and manufacturers committee on Vancouver Island will be holding a tradeshow and golf tournament on May 2, 2019 at the Westin Bear Mountain Resort.

This will be a table top trade show. Distributors have agreed not to hold their own tradeshow three months on either side of this date to ensure a successful event.

 

 



Read more about the BCEA Victoria Trade Show...

 

 

Codes and Regulations Brought to You by the CSA Group

  • Prev
The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the ...
The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the ...
In this article: Tables — Part B. This section of the Code contains 99 tables of essential ...
In this article: Section 58 — Passenger Ropeways and Similar Equipment. Rule 58-000 ...
  Unauthorized CSA Group certification marks have been found on wiring by Triumph Cable ...
In this article: Section 52 — Diagnostic imaging installations. The CE code is a ...
In this article: Section 46 — Emergency Power Supply, Unit Equipment, Exit Signs, and ...
  In this article: Section 44 — Theatre Installations. The CE Code is a ...
CSA has published C22.2 No. 60947-7-3, the harmonized standard for low-voltage switchgear and ...
  Electric welders. The CE Code is a comprehensive document. Sometimes it can seem ...

 

EE LightingBy Blake Marchand

Energy Efficient Lighting is a LED lighting manufacturer with nearly 30 years of industry experience. One that was founded on principles of environmental sustainability and responsibility to future generations. Based out of Markham, Ontario, Energy Efficient Lighting are established veterans within the LED lighting industry. And with the prominence of LED lighting being a fairly recent industry trend, it is a claim that a select few can make. They offer complete lighting solutions for commercial and industrial applications. Their product lines include conventional lighting fixtures, LED retrofit kits, complete LED luminaires, LED systems, drivers and electronic ballasts.

Read more about Energy Efficient Lighting...

Latest Articles

  • Prev
Today the whole planet is talking about climate, reducing the ecological footprint, and energy ...
The Canada Green Building Council (CaGBC) has issued a new report — the first of its kind in ...
It’s no secret that 5G will bring us faster speeds, better performance and more reliable ...
Electric motors account for approximately 53% of the world’s electricity use, and at least ...
Comox Valley Electric Ltd. is a family owned company located in Courtenay, British Columbia. ...
The war for talent is fierce across all sectors of our economy, and it’s no secret that ...
Removable USB media devices such as flash drives are commonplace and convenient when it comes to ...

Tools for the Trade

  • Prev
  IDEAL Industries has introduced Combination Drill Taps to its tool lineup. Combining the ...
  Stripping and crimping device, 100 - 240 V input voltage, for insulated ferrules with a ...
Professional all-in-one cutter/stripper for coaxial and twisted pair cables     ...
  Klein Tools' Coax Explorrer 2 tests coaxial cable and maps up to 4 locations   ...
  Ideal Industries' T-14 wire stripper s are ideal for all professionals working within the ...
  The ATS850 conveyor eliminates all types of electro static discharge requirements. ...
  Lorik Tool & Automation has the experience and ability to manufacture a variety of ...
  Ideal Industries' 26 piece insulated Journeyman kit is ideal for new electricians or for ...
  Klein Tools Deluxe Fish Rod Set comes in 19 pieces that when assembled can fish wire and ...
  BendWorks Software was designed to help electrical contractors adopt this new process ...

 

IntellimeterThe i-meter MF3 is a 3-element meter, compared to the i-meter MF6 which is two element meter. The i-meter MF6 provides 1 extra 3-element meter in the same enclosure. This allows for the monitoring of Volts, Amps, KiloWatts, Power Factor, Frequency and Harmonics [V, I, kW, kVA, PF, Hz, THD (V/I)], of 2 meters in 1.

  • Innovative multifunction metering solution
  • Monitor multiple electrical Loads from the same distribution panel
  • Earn valuable LEED points
  • Track your energy consumption
  • Displays shows energy consumption; kilo-watt hours, volts, amps per phase, power factor and frequency

Read More

 

Product News

  • Prev
All Advanced ComforTech GEL harnesses feature FallTech's exclusive polymer gel endoskeleton for ...
CBS ArcSafe, a leading manufacturer of remote racking and switching solutions for low- and ...
The Utility Insulated tool kit features 13 of the essential tools the Lineman needs.   ...
When it comes to demanding jobs in the field, linemen turn to gear they can rely on to perform ...
9.5" NE Style Lineman's Pliers, 8.0" Long Nose Pliers & 8.0" Diagonal Cutters.   ...
As a Safety Manager, you’re already fully aware that workers need to correctly distinguish ...
Fluke Networks unveiled the FI-3000 FiberInspector Pro, the industry’s most ...
Klein Tools, for professionals since 1857, introduced a new AC/DC Digital Clamp Meter, ...
Insulated Cushion Grip Slotted/Phillips/Square & Long Nose Pliers 7 Piece Set.   ...
Proxxi is a wearable voltage sensor that detects energized equipment and notifies the user of ...

3-Phase Electrical Ltd.By Blake Marchand

Winnipeg-based 3-Phase Electrical prides themselves on the high calibre of work they produce and their attention to detail, always ensuring that all work is performed to the highest possible standards. Their success is attributed to understanding their customers’ needs and continuously exceeding customer expectations.


Their expertise is facilitated by a solid foundation of careful planning and diligent scheduling, both of which are key elements to delivering projects successfully.

Read more about 3-Phase Electrical Ltd....

 

 

HeatingBy Stéphane Lettre

Today the whole planet is talking about climate, reducing the ecological footprint, and energy efficiency. Various governments are making commitments to reduce greenhouse gas emissions and people are becoming more aware of the impact of choices they make on a daily basis. Another phenomenon that is accelerating in parallel is the search for lower costs among households with increasing levels of debt and companies seeking to remain competitive and profitable.



Read more about Thermostats...

 

 

 

Peers & Profiles

  • Prev
Energy Efficient Lighting is a LED lighting manufacturer with nearly 30 years of industry ...
Matt Stanson is a master electrician with over 30 years of experience. He now leads a team of ...
After eight months, 263 events, 17 broken clocks, and thousands of competitors, Ideal ...
The National Electrical Trade Council (NETCO) is an industry-funded, not-for-profit organization ...
After eight months, 263 events, 17 broken clocks, and thousands of competitors, Ideal ...
Born and raised in western India, Rupali’s passion for mathematics and science began at a ...
After eight months, 263 events, 17 broken clocks, and thousands of competitors, Ideal ...
Allison Wood and Dominique Rivet are two apprentices who had a wealth of career options available ...
  In a recent sit-down Electrical Industry Canada was able to learn a little ...
David Johns is a unique and dedicated individual both at home and in the workplace. At home he is a ...

 

EHRCIn a recent interview with the The National Post, Electricity Human Resources Canada CEO Michelle Branigan said the need for workers in Canada’s electricity industry is “extremely critical.”

The industry directly employs almost 107,000 people, but less than 1 in 20 is aged 25 or under, only 1 in 4 is a woman, and just over 1 in 10 is from a visbile minority.

These statistics are from EHRC’s Workforce in Motion, a labour market intelligence research initiative for the years 2017-2022. The research report is a planning and informing tool for a wide range of electricity sector stakeholders and provides critical information to the sector for both short and long term resource planning.

Read More

 

 

Kerrwil Publications

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2019 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil