Bill BurrBy William (Bill) Burr

The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the information you need. This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook** but will hopefully provide some help in navigating, while reading the code.

The 24th Edition of the CE-C, Part I, (C22.1-18)* is now available from CSA Group. This discussion of Section 78 — Marine Wharves, Docking Facilities, Fixed and Floating Piers, and Boathouses is based on the new edition.

In this article: Tables — Part B. This section of the Code contains 99 tables of essential information that is referenced by various Rules of the Code. Tables referenced by Rules are considered normative (mandatory) elements of the Code. Note that the D tables of tabulated information in Appendix D are considered non-normative (non-mandatory) elements. The tables are in numerical order based on when that table was included in the Code. Since this is a large section it will be discussed in two parts. This is Part B covering Tables 36 to 69.

Tables 36A and 36B, referenced by Rule 4-004, provide maximum allowable ampacities for aluminum and copper conductor, respectively, neutral supported cables, based on phase conductor size, and type.

Table 37, referenced by, Rule 28-104, provides motor supply conductor minimum temperature rating based on, an ambient temperature of 30 degrees centigrade, type of motor enclosure, and class rating of the insulation.

Table 38, referenced by Rules 8-202 to 8-210 provides the demand factors for electric vehicle supply equipment, based on the number of automobile spaces or stalls per feeder, and the maximum load in watts per space or stall.

Table 39, referenced by Rule 4-004 (22), provides the minimum permitted service conductors (based on Tables 2 and 4), for 3-wire 120/240 V and 120/208 V for single dwellings and feeder conductor or cable size supplying single dwelling units of row housing, apartment, or similar buildings and terminating on equipment having a conductor termination temperature of not less than 75 °C, and based on the overcurrent device rating, calculated loads, and conductor size for copper or aluminum. Note that this table applies only to conductors sized for loads calculated in accordance with Rules 8-200(1) (a), 8-200 (2), or 8-202 (1).

Table 40, referenced by Rule 12-1006, provides the number of external threads per 25.4 mm (inch), and minimum and maximum length of thread in millimetres per trade size of rigid metal conduit.


Table 41, referenced by Rules 10-614 and 70-126, provides the minimum size of bonding jumper for service raceways per the ampacity of the largest service conductor or equivalent multiple conductors, for either copper or aluminum.

Table 42 is deleted.

Table 43, referenced by Rule 10-102, provides the minimum bare copper conductor size for concrete-encased electrodes, based on the ampacity of the largest service conductor or equivalent multiple conductors.

Table 44, referenced by Rules 8-010 and 28-704, provides full load current for three-phase AC motors by motor rating in horsepower, per rated voltage, and per induction type, squirrel-cage and wound rotor motors, or synchronous type unity power factor motors.


Table 45, referenced by Rules 28-010 and 28-704, provides the full load current for single-phase AC motors by horsepower per 115 or 230 volts.


Table 46 has been moved and is now Diagram 1.

Table 47 has been moved and is now Diagram 2.

Table 48, referenced by Rule 70-104, provides the minimum trade size of conduit for mobile homes per rating of the main overcurrent protection device and whether the system ground is excluded or included.

Table 49, has been moved and is now Diagram 3.

Table 50, referenced by Rule 26-250, for transformers provides the percentage of maximum setting or rating of the primary and secondary overcurrent protection device per the rated impedance of the transformer.

Table 51, referenced by Rules 36-300, 36-308 and Appendix B, provides the minimum size of bare copper grounding conductors for a high-voltage installation, based on the maximum available short-circuit current, the maximum fault duration, and whether the joint is brazed, made by an exothermic weld, compression or bolted joint.

Table 52, referenced by Rules 36-304, 36-306, 36-308, 36-310, and 36-312, provides tolerable touch and step voltages, based on type of ground, soil resistivity in ohms per meter, and fault duration.

Table 53, referenced by Rule 12-012, provides minimum cover requirements in millimeters for direct buried cables or insulated conductors in raceways, based on wiring method, and whether installed in vehicular or non-vehicular areas.


Table 54 has been moved and is now Diagram 4.

Table 55 has been moved and is now Diagram 5.

Table 56, referenced by Rule 2-308, provides the minimum working space around electrical equipment having exposed live parts, based on the nominal voltage to-ground.

Table 57, referenced by Rule 16-210 (6) and Table 5A, provides allowable ampacities for Class 2 copper conductors based on the size of conductor and whether it is a single conductor in free air, or not more than three copper conductors in raceway or cable, and an ambient temperature of 30 degrees centigrade. Where there are more than three conductors in raceway, use the derating factors provided by column 3.

Table 58, referenced by Rule 40-002, for short-time-rated crane and hoist motors, provides ampacities for up to four insulated copper conductors in raceway or cable for the operating temperature and duration, at an ambient temperature of 30 degrees centigrade. For five or more power conductors in raceway or cable, the ampacities shown in this table are reduced by 80%. For ambient temperatures over 30 degrees centigrade, apply the derating factors in Table 5A.

Table 59, referenced by Rule 60-704, provides the minimum size of protector grounding conductors for communications systems, based on the maximum number of protected circuits, and whether they are fused or fuseless.

Table 60, referenced by Rule 16-330, provides allowable ampacities for copper, eight-conductor, Class 2 power and data communication circuit cables, based on conductor and cable size, and number of cables in a bundle.

Table 61, referenced by Rule 68-056, provides the minimum horizontal separation from pools of buried cable, depending on the type of installation (communication or power) and, whether the cable is direct buried unjacketed with bare neutral, cables with a semi-conducting jacket, cables with a non-conducting jacket, or conductors in non-conducting ducts.
Table 62, referenced by Rules 38-013 (2) and 38-014, provides feeder demand factors for elevators, based on the number of elevators on a single feeder.


Table 63, referenced by Rule 20-034, outlines the hazardous areas for propane dispensing, container filling, and storage, based on location, extent of the hazardous location, and the Group IIA hazardous location.


Table 64, referenced by Rules 20-062 and J20-062, outlines the hazardous locations at NGV fuelling facilities, based on location, and the extent of the hazardous location zone or division.

Table 65, referenced by Rules 2-400 and 2-402, provides the enclosure selection table for non-hazardous locations, based on the degree of protection against the environmental conditions, the enclosure type, and whether its for indoor only or Indoor/outdoor use.

Table 66, referenced by Rule 4-004 (22), provides ampacities for bare or covered conductors in free air, based on 40 degrees centigrade ambient temperature, 80 degrees centigrade total conductor temperature, and 610 millimetres per second wind velocity, for both copper and aluminum conductors.

Table 67, referenced by Rule 62-200, provides the minimum clearance requirements for installed space heating systems, based on type of heating system and location, and the types of obstructions and protrusions.

Table 68, referenced by Rule 8-102, provides the maximum insulated conductor length, for 120 V single-phase circuits in dwelling units, measured from the supply side of the consumer’s service to the furthest point of utilization, on a circuit using 90-degree centigrade rated copper insulated conductors, at 30 degrees centigrade ambient temperature, based on size of conductor and overcurrent protection rating.


Table 69, referenced by Rule 20-202, outlines hazardous locations at bulk storage plants, by location, extent of the hazardous location, and the zone of the hazardous location.

In the next instalment, we will be discussing the Diagrams and the Appendices Sections of the Code.

* The source for this series of articles is the Canadian Electrical Code, Part I, (C22.1-18) published by CSA.

** Note the CEC Handbook is also published by CSA.

William (Bill) Burr is the former Chair of the Canadian Advisory Council on Electrical Safety (CACES), former Director of Electrical and Elevator Safety for the Province of BC, and former Director of Electrical and Gas Standards Development and former Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting billburr@gmail.com.

 

AD Spotlight                                                                                                            

Changing Scene

  • Prev
EFC’s exciting new product section on Electric Vehicle Systems conducted its first face-to-face ...
Canadian battery material specialist Hydro-Québec partners with Mercedes-Benz AG as part ...
Employer response to emerging technologies’ impact on the electricity sector workforce is critical ...
The National Electrical Manufacturers Association (NEMA) has published two new standards on ...
This fall, Canada's elite electricians and apprentices will be heading to Nashville, Tennessee for ...
The Electrical industry is “Powering a Changing World” in areas such as digitization, ...
Prior to joining ABB in 2017 as Executive Vice President of the Electrification business, Deschenes ...
The Canadian Apprenticeship Forum-Forum Canadien sur l’Apprentissage (CAF-FCA) has announced ...
The Support Equity and Under-Represented Groups project will address the under-representation of ...

SIemens Light+BuildingAt this year’s Light+Building trade fair, Siemens will showcase its vision for transforming today’s passive buildings into learning and adaptive environments that intelligently interact with people. The company’s focus at this year’s show is “Building the future today”, outlining the innovations that will make this possible. These include cloud-based technologies, digital planning, occupant-centric building automation and services. New solutions for smart electrical infrastructure that seamlessly connects to the Internet of Things (IoT) are also at the core of this transformation.

Read More

 

 

 

Latest Articles

  • Prev
A broadening of the role of luminaires and a continued focus on people and energy efficiency are ...
There’s been a lot of confusion and misinformation disseminated regarding LED emergency lighting ...
We are in an Age of Disruption. Extant and emerging technologies are driving significant evolution ...
Often, code users encounter situations where they find themselves at odds with the rules contained ...
The new electrical code includes several changes to support electrical workers in the safe ...
Anyone working in the electricity sector in Canada knows the reality of how few women we have in ...
 Anyone working in the electrical industry knows the importance of labelling for both safety ...

Michelle BraniganBy Michelle Branigan

We are in an Age of Disruption. Extant and emerging technologies are driving significant evolution in the way work is done across all sectors of Canada’s economy and no industry, including electricity, will be immune.

Think of the technologies and businesses that have changed the way we live, work and connect with each other. Uber. Airbnb. Spotify. Facebook. Twitter. Duolingo. The list is long and what’s fascinating is that these are companies that did not exist 20 years ago. Yet these are common words in our lexicon today.

Read More

 

 


Greenlee Voltage DetectorsProfessionals searching for a reliable voltage detection solution have two new Greenlee options — the newly redesigned GT13 and TR13 non-contact voltage detectors. The new testers identify the presence of voltage from 50 volts to 1,000 volts AC. The redesigned GT13 and TR13 are now equipped with a more ergonomic grip and button location, along with a bright LED flashlight for use in dark work areas.


 

Read More

 

Product News

  • Prev
The LED filament lamps distinguish themselves by their sparkling white light, blending perfectly ...
Stanpro offers a wide range of Linear Fluorescent lamps for all lighting applications and needs. ...
This modern design series is a family of highly efficient and powerful LED flood lights and area ...
Our new 60W and 100W Temporary LED High Bays are the ideal substitute for traditional 250W and 400W ...
These high quality luminaires are equipped with a frosted lens that diffuses the light comfortably. ...
Arlington’s #300 non-metallic cable strap offers the easy way to attach flat NM cable to concrete ...
EiKO's Emergency Batery Kit is an LED emergency driver that allows the same LED fixture to be used ...
The LED Gimbal High Output downlight combines a sleek design with a small aperture without any ...
LPDL (Low Profile Downlight) gives you all the flexibility you need during installation, especially ...
Lumenwerx is pleased to announce the launch of a new suite of acoustic luminaires to reduce ambient ...

 

Lumenwerx AcoustixLumenwerx is pleased to announce the launch of a new suite of acoustic luminaires to reduce ambient noise – ACOUSTIX family.

Developed in conjunction with acoustics experts, the new ACOUSTIX family of luminaires combines exceptional optics and precision sound absorbing technology to create a new paradigm in acoustic lighting. The lineup’s flagship fixture, the Audia, can increase sound absorption up to 30% more than competing products.

 

 

Read More

 

 

Peers & Profiles

  • Prev
Tommy Carducci is a 14-year industry veteran working with Seneca Electrical and was one of 18 ...
Legend Power Systems is an innovative Canadian company headquartered out of Vancouver, B.C. Their ...
Founded in 1942, Franklin Empire is Canada’s largest independent electrical distributor.   ...
Nick Foster is Territory Manager, New Brunswick & P.E.I for Leviton. Foster was recently ...
Held from November 7th to 9th in Orlando, Florida and aired on ESPN 2, the Ideal National ...
Headquartered in Vancouver, Legend Power Systems is a global onsite energy management technology ...
LDS caught up with General Manager of EiKO’s Canadian division, Stephen Lee who was kind enough ...
“I had an awesome time, it was a lot of fun,” said Zach Agombar, who competed his way to 8th place ...
Held from November 7th to 9th in Orlando, Florida, and recently aired on ESPN 2, the Ideal National ...
Panel Upgrade Experts is an electrical contracting company started seven years ago by Paul ...

 

Leviton Nick FosterBy Blake Marchand

Nick Foster is Territory Manager, New Brunswick & P.E.I for Leviton. Foster was recently appointed as the Atlantic Regional Chair for Electro-Federation Canada’s (EFC) Young Professional Network (YPN).

Nick joins newly appointed National Chair, Sean Bernard of Ideal Industries, Ontario Region Chair, Joanna Kwant of Gerrie Electric, and Quebec Region Chair, Jean-Francois Gravel also with Leviton.

 

 

Read More

 

 

Kerrwil Publications Great Place to Work. Certified December 2019 - December 2020

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2020 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil