Bill BurrBy William (Bill) Burr

The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the information you need. This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook** but will hopefully provide some help in navigating, while reading the code.

The 24th Edition of the CE-C, Part I, (C22.1-18)* is now available from CSA Group. This discussion of Section 78 — Marine Wharves, Docking Facilities, Fixed and Floating Piers, and Boathouses is based on the new edition.

In this article: Tables — Part B. This section of the Code contains 99 tables of essential information that is referenced by various Rules of the Code. Tables referenced by Rules are considered normative (mandatory) elements of the Code. Note that the D tables of tabulated information in Appendix D are considered non-normative (non-mandatory) elements. The tables are in numerical order based on when that table was included in the Code. Since this is a large section it will be discussed in two parts. This is Part B covering Tables 36 to 69.

Tables 36A and 36B, referenced by Rule 4-004, provide maximum allowable ampacities for aluminum and copper conductor, respectively, neutral supported cables, based on phase conductor size, and type.

Table 37, referenced by, Rule 28-104, provides motor supply conductor minimum temperature rating based on, an ambient temperature of 30 degrees centigrade, type of motor enclosure, and class rating of the insulation.

Table 38, referenced by Rules 8-202 to 8-210 provides the demand factors for electric vehicle supply equipment, based on the number of automobile spaces or stalls per feeder, and the maximum load in watts per space or stall.

Table 39, referenced by Rule 4-004 (22), provides the minimum permitted service conductors (based on Tables 2 and 4), for 3-wire 120/240 V and 120/208 V for single dwellings and feeder conductor or cable size supplying single dwelling units of row housing, apartment, or similar buildings and terminating on equipment having a conductor termination temperature of not less than 75 °C, and based on the overcurrent device rating, calculated loads, and conductor size for copper or aluminum. Note that this table applies only to conductors sized for loads calculated in accordance with Rules 8-200(1) (a), 8-200 (2), or 8-202 (1).

Table 40, referenced by Rule 12-1006, provides the number of external threads per 25.4 mm (inch), and minimum and maximum length of thread in millimetres per trade size of rigid metal conduit.


Table 41, referenced by Rules 10-614 and 70-126, provides the minimum size of bonding jumper for service raceways per the ampacity of the largest service conductor or equivalent multiple conductors, for either copper or aluminum.

Table 42 is deleted.

Table 43, referenced by Rule 10-102, provides the minimum bare copper conductor size for concrete-encased electrodes, based on the ampacity of the largest service conductor or equivalent multiple conductors.

Table 44, referenced by Rules 8-010 and 28-704, provides full load current for three-phase AC motors by motor rating in horsepower, per rated voltage, and per induction type, squirrel-cage and wound rotor motors, or synchronous type unity power factor motors.


Table 45, referenced by Rules 28-010 and 28-704, provides the full load current for single-phase AC motors by horsepower per 115 or 230 volts.


Table 46 has been moved and is now Diagram 1.

Table 47 has been moved and is now Diagram 2.

Table 48, referenced by Rule 70-104, provides the minimum trade size of conduit for mobile homes per rating of the main overcurrent protection device and whether the system ground is excluded or included.

Table 49, has been moved and is now Diagram 3.

Table 50, referenced by Rule 26-250, for transformers provides the percentage of maximum setting or rating of the primary and secondary overcurrent protection device per the rated impedance of the transformer.

Table 51, referenced by Rules 36-300, 36-308 and Appendix B, provides the minimum size of bare copper grounding conductors for a high-voltage installation, based on the maximum available short-circuit current, the maximum fault duration, and whether the joint is brazed, made by an exothermic weld, compression or bolted joint.

Table 52, referenced by Rules 36-304, 36-306, 36-308, 36-310, and 36-312, provides tolerable touch and step voltages, based on type of ground, soil resistivity in ohms per meter, and fault duration.

Table 53, referenced by Rule 12-012, provides minimum cover requirements in millimeters for direct buried cables or insulated conductors in raceways, based on wiring method, and whether installed in vehicular or non-vehicular areas.


Table 54 has been moved and is now Diagram 4.

Table 55 has been moved and is now Diagram 5.

Table 56, referenced by Rule 2-308, provides the minimum working space around electrical equipment having exposed live parts, based on the nominal voltage to-ground.

Table 57, referenced by Rule 16-210 (6) and Table 5A, provides allowable ampacities for Class 2 copper conductors based on the size of conductor and whether it is a single conductor in free air, or not more than three copper conductors in raceway or cable, and an ambient temperature of 30 degrees centigrade. Where there are more than three conductors in raceway, use the derating factors provided by column 3.

Table 58, referenced by Rule 40-002, for short-time-rated crane and hoist motors, provides ampacities for up to four insulated copper conductors in raceway or cable for the operating temperature and duration, at an ambient temperature of 30 degrees centigrade. For five or more power conductors in raceway or cable, the ampacities shown in this table are reduced by 80%. For ambient temperatures over 30 degrees centigrade, apply the derating factors in Table 5A.

Table 59, referenced by Rule 60-704, provides the minimum size of protector grounding conductors for communications systems, based on the maximum number of protected circuits, and whether they are fused or fuseless.

Table 60, referenced by Rule 16-330, provides allowable ampacities for copper, eight-conductor, Class 2 power and data communication circuit cables, based on conductor and cable size, and number of cables in a bundle.

Table 61, referenced by Rule 68-056, provides the minimum horizontal separation from pools of buried cable, depending on the type of installation (communication or power) and, whether the cable is direct buried unjacketed with bare neutral, cables with a semi-conducting jacket, cables with a non-conducting jacket, or conductors in non-conducting ducts.
Table 62, referenced by Rules 38-013 (2) and 38-014, provides feeder demand factors for elevators, based on the number of elevators on a single feeder.


Table 63, referenced by Rule 20-034, outlines the hazardous areas for propane dispensing, container filling, and storage, based on location, extent of the hazardous location, and the Group IIA hazardous location.


Table 64, referenced by Rules 20-062 and J20-062, outlines the hazardous locations at NGV fuelling facilities, based on location, and the extent of the hazardous location zone or division.

Table 65, referenced by Rules 2-400 and 2-402, provides the enclosure selection table for non-hazardous locations, based on the degree of protection against the environmental conditions, the enclosure type, and whether its for indoor only or Indoor/outdoor use.

Table 66, referenced by Rule 4-004 (22), provides ampacities for bare or covered conductors in free air, based on 40 degrees centigrade ambient temperature, 80 degrees centigrade total conductor temperature, and 610 millimetres per second wind velocity, for both copper and aluminum conductors.

Table 67, referenced by Rule 62-200, provides the minimum clearance requirements for installed space heating systems, based on type of heating system and location, and the types of obstructions and protrusions.

Table 68, referenced by Rule 8-102, provides the maximum insulated conductor length, for 120 V single-phase circuits in dwelling units, measured from the supply side of the consumer’s service to the furthest point of utilization, on a circuit using 90-degree centigrade rated copper insulated conductors, at 30 degrees centigrade ambient temperature, based on size of conductor and overcurrent protection rating.


Table 69, referenced by Rule 20-202, outlines hazardous locations at bulk storage plants, by location, extent of the hazardous location, and the zone of the hazardous location.

In the next instalment, we will be discussing the Diagrams and the Appendices Sections of the Code.

* The source for this series of articles is the Canadian Electrical Code, Part I, (C22.1-18) published by CSA.

** Note the CEC Handbook is also published by CSA.

William (Bill) Burr is the former Chair of the Canadian Advisory Council on Electrical Safety (CACES), former Director of Electrical and Elevator Safety for the Province of BC, and former Director of Electrical and Gas Standards Development and former Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting billburr@gmail.com.

 

       Partnering For The Next Step                

Siemens CanadaWelcome to the Digital Enterprise Virtual Summit brought to you by Siemens

How quickly can you react to changing conditions and demands in your market? How can you ensure your production will run securely at any time in the future?

Industry’s digital and technological transformation is the answer for meeting today’s and tomorrow’s challenges and market needs.

With the right digitalization and automation solutions, expertise won from practical experience, and a partnership approach that benefits all involved parties.

To explore these possibilities, we’re bringing together top-level speakers, specialists and decision-makers from various industries and experts from Siemens

to the Digital Enterprise Virtual Summit under the motto “Partnering for the next step.”   

READ MORE

Changing Scene

  • Prev
Stay Wired to Win is a monthly at-home challenge designed to keep your competitive spark going ...
Join the Electrical Contractors Association of Ontario (ECAO) for a live webinar on July 7 at 2:00 ...
Following the latest COVID-19 announcements from the Ontario Government, ESA has decided to ...
Introducing Stay Wired to Win – a series of monthly at-home challenges designed to keep your ...
ESA’s response team has been working diligently to address the emerging issues. We are moving into ...
This recall involves Legrand / Pass & Seymour commercial-grade tamper resistant duplex ...
In response to the current COVID-19 crisis, IDEAL Canada was looking for ways to contribute to the ...
Join Nexans for a free webinar as Isaac Müller, Applications Engineer for Nexans discusses this ...
IDEAL INDUSTRIES has made the difficult but necessary decision to cancel the original ...
The Regional Electrical Inspector performs physical inspections on all types of electrical ...

“Re-envisioning Electrical Switchboards”: For light commercial applications, the status quo is no longer enough

Eaton

Whether you’re a contractor or consultant, compact footprint and shorter lead times are a priority. At Eaton, we understand these challenges. That’s why we have re-envisioned our traditional electrical switchboard to assess how it could better serve light commercial applications. The result? The Pow-R-Line CS. 

Join Eaton’s webinar on June 30th, 2020 and learn the secret to shorter lead times alongside the additional benefits of:

 -  Versatile Configuration - Cost Effectiveness - Plus a Complimentary 3D Product Demonstration!

Sign up and join our host Annu Yadav - Distributor Programs Manager and our presenter Aditya Ramesh - Product Manger of Panelboards & Switchboards. Looking forward to seeing you there!

Click Here To Register.

 

WestburneMany contractors prefer to deal with the people that they know, in their local branch. When doing a job out of town, it’s often inconvenient or simply impossible to return to your home branch to pick up material orders for the next day, within standard business hours.

Westburne’s new locker solution extends the branch’s pick up times to 24 hours, 7 days a week.

 

 

 


Read More

 

Latest Articles

  • Prev
Any contractor who has been on the jobsite during a difficult wire pull can attest to the ...
All electrical incidents are preventable! Keep employees safe with an up-to-date electrical ...
Vast quantities of renewables and bi-directional flows on the grid, along with rapid cost declines ...
Many organizations are at risk of continued interruption to operations due to coronavirus and ...
It is very scary to realize that our entire world has changed so drastically with the COVID-19 ...
The new electrical code includes several changes to support electrical workers in the safe ...

EmployeesBy Terry Becker

All electrical incidents are preventable! Keep employees safe with an up-to-date electrical safety program and complimentary training.

“Employees don’t do what you expect, they do what you inspect!” This is a great quote when it comes down to occupational health and safety. The need for ensuring that an audit is a key component of your overall occupational health and safety management system and your company’s electrical safety program is essential.

Read More

 

 

Michelle BraniganBy Michelle Branigan

Student workers may make up a relatively small portion of the sector workforce, but their impact is substantial. EHRC’s Empowering Futures wage subsidy program has placed 510 students, contributing $14.8 million to the Canadian economy (and counting). That’s no small figure, especially considering that many placements are only a few months long.

In challenging economic times, the tendency might be to pull back on initiatives not deemed essential to operating — why take a chance on an inexperienced employee for only a short time when resources are already stretched?

Read More

 

Product News

  • Prev
Engineered to provide customers with portable task-specific lighting in hazardous industrial ...
HPS is now offering three phase general purpose and k-rated transformers for solar applications ...
The EVduty from Elmec Inc. is a level 2 charging station for electric vehicles. It lets you ...
Smart, Accessible, and Easy-to-use, Noodoe EV Stands Out Against Other EV Chargers with its ...
Littelfuse have expanded its DCN Series of high voltage direct current (DC) contactors.   ...
The Pull-handle Butterfly Valve Lockout. Its simple, fold-over design effectively lockspull handles ...
LEDVANCE is launching, on July 2020, SYLVANIA SubstiTUBE PS Natural LED T8 Lamps and ...
Luminis has improved and expanded its Maya family of exterior luminaires. Improvements in design ...
A new 8” diameter size has been added to the 12” and 16” existing diameters. The translucent white ...
Universal’s EVERLINE® Vapor Tight is ideal for unforgiving lighting environments. These durable LED ...

 

Brady Pull-Handle Butterfly Valve LockoutThe Pull-handle Butterfly Valve Lockout. Its simple, fold-over design effectively lockspull handles in any desired position. And, it holds up to four padlocks for added safety. No matter what industry you’re in, this versatile, one-piece lockout device bolsters your safety lockout solution. And that’s a welcome addition to any lockout program. With this device you’ll also get:

  • A great fit – exclusive, anti-pivot lockout device that fits a variety of pull handle butterfly valve sizes

 

 

 

Read More

Peers & Profiles

  • Prev
Meredith Halfpenny is a Wind Site Technician with Boralex where she inspects, maintains, and ...
Rutul Bhavsar is a final year Electrical Engineering student at Mohawk College. He recently ...
Shannon Tymosko is a first-year apprentice with IBEW (International Brotherhood of Electrical ...
Hazmasters was founded with a dedication and focus on creating safer work environments. It is ...
ELG Electric is an electrical contractor based out of Goderich, Ontario serving the area’s ...
Founded by Warren Osak, Electromate specializes in Robotic and Mechatronic Solutions, distributing ...
 Will West is a first-year apprentice working in the solar industry with Hakai Energy ...
“It’s definitely the Olympics of our trade,” said Lance Giesbrecht of the Ideal National ...
Tommy Carducci is a 14-year industry veteran working with Seneca Electrical and was one of 18 ...
Legend Power Systems is an innovative Canadian company headquartered out of Vancouver, B.C. Their ...

Shannon TymoskoBy Blake Marchand

Shannon Tymosko is a first-year apprentice with IBEW (International Brotherhood of Electrical Workers) Local 105, something she undertook after 10 years working her way up the ranks of a payday loan company.

“One of the things I love, working in the trades, is you can see your progress and you can see at the end of the day the work that you have done.

 

Read More

 

 

Kerrwil Publications Great Place to Work. Certified December 2019 - December 2020

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2020 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil