Canadian Electrical Industry News Week

 

Dec 10, 2018

Bill BurrBy William (Bill) Burr

The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the information you need. This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook** but will hopefully provide some help in navigating, while reading the code.

The 24th Edition of the CE-C, Part I, (C22.1-18)* is now available from CSA Group. This discussion of Section 78 — Marine Wharves, Docking Facilities, Fixed and Floating Piers, and Boathouses is based on the new edition.

In this article: Tables — Part B. This section of the Code contains 99 tables of essential information that is referenced by various Rules of the Code. Tables referenced by Rules are considered normative (mandatory) elements of the Code. Note that the D tables of tabulated information in Appendix D are considered non-normative (non-mandatory) elements. The tables are in numerical order based on when that table was included in the Code. Since this is a large section it will be discussed in two parts. This is Part B covering Tables 36 to 69.

Tables 36A and 36B, referenced by Rule 4-004, provide maximum allowable ampacities for aluminum and copper conductor, respectively, neutral supported cables, based on phase conductor size, and type.

Table 37, referenced by, Rule 28-104, provides motor supply conductor minimum temperature rating based on, an ambient temperature of 30 degrees centigrade, type of motor enclosure, and class rating of the insulation.

Table 38, referenced by Rules 8-202 to 8-210 provides the demand factors for electric vehicle supply equipment, based on the number of automobile spaces or stalls per feeder, and the maximum load in watts per space or stall.

Table 39, referenced by Rule 4-004 (22), provides the minimum permitted service conductors (based on Tables 2 and 4), for 3-wire 120/240 V and 120/208 V for single dwellings and feeder conductor or cable size supplying single dwelling units of row housing, apartment, or similar buildings and terminating on equipment having a conductor termination temperature of not less than 75 °C, and based on the overcurrent device rating, calculated loads, and conductor size for copper or aluminum. Note that this table applies only to conductors sized for loads calculated in accordance with Rules 8-200(1) (a), 8-200 (2), or 8-202 (1).

Table 40, referenced by Rule 12-1006, provides the number of external threads per 25.4 mm (inch), and minimum and maximum length of thread in millimetres per trade size of rigid metal conduit.


Table 41, referenced by Rules 10-614 and 70-126, provides the minimum size of bonding jumper for service raceways per the ampacity of the largest service conductor or equivalent multiple conductors, for either copper or aluminum.

Table 42 is deleted.

Table 43, referenced by Rule 10-102, provides the minimum bare copper conductor size for concrete-encased electrodes, based on the ampacity of the largest service conductor or equivalent multiple conductors.

Table 44, referenced by Rules 8-010 and 28-704, provides full load current for three-phase AC motors by motor rating in horsepower, per rated voltage, and per induction type, squirrel-cage and wound rotor motors, or synchronous type unity power factor motors.


Table 45, referenced by Rules 28-010 and 28-704, provides the full load current for single-phase AC motors by horsepower per 115 or 230 volts.


Table 46 has been moved and is now Diagram 1.

Table 47 has been moved and is now Diagram 2.

Table 48, referenced by Rule 70-104, provides the minimum trade size of conduit for mobile homes per rating of the main overcurrent protection device and whether the system ground is excluded or included.

Table 49, has been moved and is now Diagram 3.

Table 50, referenced by Rule 26-250, for transformers provides the percentage of maximum setting or rating of the primary and secondary overcurrent protection device per the rated impedance of the transformer.

Table 51, referenced by Rules 36-300, 36-308 and Appendix B, provides the minimum size of bare copper grounding conductors for a high-voltage installation, based on the maximum available short-circuit current, the maximum fault duration, and whether the joint is brazed, made by an exothermic weld, compression or bolted joint.

Table 52, referenced by Rules 36-304, 36-306, 36-308, 36-310, and 36-312, provides tolerable touch and step voltages, based on type of ground, soil resistivity in ohms per meter, and fault duration.

Table 53, referenced by Rule 12-012, provides minimum cover requirements in millimeters for direct buried cables or insulated conductors in raceways, based on wiring method, and whether installed in vehicular or non-vehicular areas.


Table 54 has been moved and is now Diagram 4.

Table 55 has been moved and is now Diagram 5.

Table 56, referenced by Rule 2-308, provides the minimum working space around electrical equipment having exposed live parts, based on the nominal voltage to-ground.

Table 57, referenced by Rule 16-210 (6) and Table 5A, provides allowable ampacities for Class 2 copper conductors based on the size of conductor and whether it is a single conductor in free air, or not more than three copper conductors in raceway or cable, and an ambient temperature of 30 degrees centigrade. Where there are more than three conductors in raceway, use the derating factors provided by column 3.

Table 58, referenced by Rule 40-002, for short-time-rated crane and hoist motors, provides ampacities for up to four insulated copper conductors in raceway or cable for the operating temperature and duration, at an ambient temperature of 30 degrees centigrade. For five or more power conductors in raceway or cable, the ampacities shown in this table are reduced by 80%. For ambient temperatures over 30 degrees centigrade, apply the derating factors in Table 5A.

Table 59, referenced by Rule 60-704, provides the minimum size of protector grounding conductors for communications systems, based on the maximum number of protected circuits, and whether they are fused or fuseless.

Table 60, referenced by Rule 16-330, provides allowable ampacities for copper, eight-conductor, Class 2 power and data communication circuit cables, based on conductor and cable size, and number of cables in a bundle.

Table 61, referenced by Rule 68-056, provides the minimum horizontal separation from pools of buried cable, depending on the type of installation (communication or power) and, whether the cable is direct buried unjacketed with bare neutral, cables with a semi-conducting jacket, cables with a non-conducting jacket, or conductors in non-conducting ducts.
Table 62, referenced by Rules 38-013 (2) and 38-014, provides feeder demand factors for elevators, based on the number of elevators on a single feeder.


Table 63, referenced by Rule 20-034, outlines the hazardous areas for propane dispensing, container filling, and storage, based on location, extent of the hazardous location, and the Group IIA hazardous location.


Table 64, referenced by Rules 20-062 and J20-062, outlines the hazardous locations at NGV fuelling facilities, based on location, and the extent of the hazardous location zone or division.

Table 65, referenced by Rules 2-400 and 2-402, provides the enclosure selection table for non-hazardous locations, based on the degree of protection against the environmental conditions, the enclosure type, and whether its for indoor only or Indoor/outdoor use.

Table 66, referenced by Rule 4-004 (22), provides ampacities for bare or covered conductors in free air, based on 40 degrees centigrade ambient temperature, 80 degrees centigrade total conductor temperature, and 610 millimetres per second wind velocity, for both copper and aluminum conductors.

Table 67, referenced by Rule 62-200, provides the minimum clearance requirements for installed space heating systems, based on type of heating system and location, and the types of obstructions and protrusions.

Table 68, referenced by Rule 8-102, provides the maximum insulated conductor length, for 120 V single-phase circuits in dwelling units, measured from the supply side of the consumer’s service to the furthest point of utilization, on a circuit using 90-degree centigrade rated copper insulated conductors, at 30 degrees centigrade ambient temperature, based on size of conductor and overcurrent protection rating.


Table 69, referenced by Rule 20-202, outlines hazardous locations at bulk storage plants, by location, extent of the hazardous location, and the zone of the hazardous location.

In the next instalment, we will be discussing the Diagrams and the Appendices Sections of the Code.

* The source for this series of articles is the Canadian Electrical Code, Part I, (C22.1-18) published by CSA.

** Note the CEC Handbook is also published by CSA.

William (Bill) Burr is the former Chair of the Canadian Advisory Council on Electrical Safety (CACES), former Director of Electrical and Elevator Safety for the Province of BC, and former Director of Electrical and Gas Standards Development and former Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting billburr@gmail.com.

 



 

ABB RoboticsABB Robotics is driving automation in the construction industry with new robotic automation solutions to address key challenges, including the need for more affordable and environmentally friendly housing and to reduce the environmental impact of construction, amidst a labor and skills shortage.

Robotic automation offers huge potential to enhance productivity, efficiency and manufacturing flexibility throughout the construction industry, including automating the fabrication of modular homes and building components off-site, robotic welding and material handling on building sites and robot 3D printing of houses and customized structures. 



Read More


 

Canadian Electrical Contractor Discussion Group: Can You Count the Deficiencies?

EIN CECD 400Have you ever been called to fix the work of a 'handyman'?

"Was supposedly done by a"certified ' electrician....told the homeowner that he got a $266 permit....no record at TSBC. Can you count the deficiencies?"

"There is a second panel change in the triplex also.......even more deficiencies. Think the guy was a glorified handyman. Ones not obvious: 240 BB heat hooked up 120....drier on 2p20....range on 2p50....water heater fed with 2c14 Bx on 2p15."

Go HERE to join the discussion

 


 

Smart GridHarnessing Canada’s immense clean energy resources requires transformational investments to modernize our electricity grid. The Government of Canada is investing in renewable energy and upgrading the electricity grid to make clean, affordable electricity options more accessible in communities across Canada.

The Honourable Seamus O’Regan Jr., Minister of Natural Resources, today launched a $964-million program to support smart renewable energy and grid modernization projects that will lower emissions by investing in clean energy technologies, like wind, solar, storage, hydro, geothermal and tidal.

Read More

 


 

Latest Articles

  • Prev
The arc flash hazard has overwhelmed employers in all industries across Canada and in the United ...
This is the first of a series of articles detailing significant changes for the 2021 Canadian ...
Sense was founded by three partners, Chris Micali, Ryan Houlette and Michael Phillips, with ...
In January 2021, the International Code Council published the 2021 version of the International ...
Section 36 – High Voltage Installations applies to installations operating above 750 volts, which ...
The City of Cowansville in south-central Quebec is the largest city in the Brome-Missisquoi region, ...
Dave Hiemstra (CLCP, CTR) is the Controls Group Manager with Optics Lighting, he presented on ...
The writing was on the wall.  The closures would happen. But a lot of people were upset, ...
A lighting programming and control narrative is a document that is essential to coordinate the ...
My name is Shannon Tymosko. I am a 2nd year Electrical Apprentice with the International ...


Trilliant Partners with the City of CowansvilleThe City of Cowansville in south-central Quebec is the largest city in the Brome-Missisquoi region, with more than 15,000 residents. Despite being a smaller-sized city, it is known as an economic and industrial hub.

It also has a strong focus on innovation and efficiency — as demonstrated by decisions such as the one it made in 2017 to use beet juice to help combat icy winter roads, allowing the City to reduce the amount of salt it was using, thereby saving money and decreasing the impact on the environment. 

 

 

Read More


 

Keith SonesBy Keith Sones

The writing was on the wall.  The closures would happen. But a lot of people were upset, and I was one of them. 

In the early 2000s, my family and I were living in a mainly rural (at least by city dweller standards) valley in south central British Columbia.  The West Kootenay region is known for its diverse outdoor recreation activities and as a great place to raise a family.  It has a proud industrial history, evidenced through the longstanding pulp mill, a massive lead zinc smelter a few miles away and several hydroelectric dams, all of it within spitting distance of the mighty Columbia River. 

Read More


 

Dave HiemstraBy Blake Marchand

Dave Hiemstra (CLCP, CTR) is the Controls Group Manager with Optics Lighting, he presented on Designing & Deploying Budget Friendly, Code Compliant Lighting Controls as part of the Alberta Electrical Alliance Electrical Learning Expo.

“We have moved into a world of budget cuts – more than ever before we’re seeing value engineering on projects, we’re seeing budgets latched, everyone’s doing the bare minimum, at this point, on what needs to be done,” he explained at the top of his presentation, which ultimately puts the focus on being budget friendly when designing lighting control.

 

Read More


 

Product News

  • Prev
Introducing the new in-sourced, upgraded, and expanded vapor tight LED High Bay -- the ...
Klein Tools introduces the new Magnetic Wire Puller, to help professionals quickly and easily fish ...
Siemens new 3VA molded case circuit breakers offer safe, efficient and variable application options ...
Hubbell’s illuminated plugs and connectors are the latest addition to the already broad line of ...
The ABV is a specification high bay that provides high performance and reliability. Available with ...
The Vive PowPak phase select dimming module is a radio frequency (RF) control that operates phase ...
6 functions in one pair of pliers. Multifunctional pliers for the electrical installation; to grip ...
With the ABB StarTeck® selector web app you can match cables with Teck fittings quickly and easily. ...
WPS Gen 4 wall pack series is a classic and familiar design integrated with modern LED technology ...
These new controllers offer indoor or outdoor ON/OFF, photocell, dimming, scene and color tuning ...

 

Lumenquad New VersionsLumenpulse has announced the release of two additional smaller sizes of the Lumenquad, a rectilinear projector for both outdoor and indoor environments. Developed for architectural applications such as lighting landscapes, highlighting details, pathways and monuments, the Lumenquad Small and Medium are compact, low-wattage, high-performance projectors, complementing the two existing products in the family.

The Lumenquad Small and Medium are the latest additions to a family of sleek, elegant, high-performance projectors that has already been validated with honours, including recognition in the PIA Awards in 2019, together with a Lux Awards for Exterior Luminaire of the Year in 2019. 

Read More


 

 

Wiha Lineman's Pliers and CrimpersWiha Insulated SoftFinish® Cushion Grip Pliers and Cutters are the standard for premium quality featuring ergonomic cushion grip handles for comfort and control, dual durometer construction for long-lasting durability, and handles directly molded to the tool steel for a permanent bond.

The grips feature a slip guard handle design for added protection at the front-end and raised rear-finger steps for easy opening at the back-end. Wiha Insulated SoftFinish® Cushion Grip Pliers and Cutters consist of premium quality tool steel for strength and durability and induction hardened cutting edges and jaws for superior sharpness and longevity. 

Read More


 

 

eLumigen Poultry Lamps - 2000K, 3000K & 5000KIdeal for rough service applications, the A19 & PAR Series are engineered for high efficiency, vibration resistance, shatter-resistance, elevated heat environments, and wet locations. These dimmable LED Lamps help reduce energy costs, labor costs, and the headaches of frequent lamp changes in tough applications.

eLumigen employs a unique 21-point validation process that goes above and beyond industry standards. Our lamps have been tested to survive levels of vibration exceeding 20G forces. Our unique temperature foldback design improves both safety and thermal management of our lamps. 

Read More


 

Peers & Profiles

  • Prev
Bryan Smith started his now 20-year career at the ground floor, so to speak, as a draftsperson and ...
From small construction to sophisticated industrial projects, House of Electrical Supplies has been ...
Kyle Manfredi is the owner of ARK Electrical alongside his wife, Shannon. Operating out of ...
Like most major events over the last year, the COVID-19 pandemic put serious restrictions on the ...
This past December Jennifer Green was honoured with Canada’s Most Powerful Women Top 100 Award for ...
“It was quite surprising,” said Stephanie Smith of being named EHRC’s Leader of the Year. ...
As an advanced networked lighting controls company serving the industrial and large commercial ...
Trilliant, an international provider of utility solutions for advanced metering and smart grid ...
For more than a century, ABB has been investing in Canadian technologies and products to support ...
Mackenzie Gillan, a bright young lady from Baysville, Ontario, tells us about how she learned ...


House of Electrical SuppliesFrom small construction to sophisticated industrial projects, House of Electrical Supplies has been servicing clients in the industrial, OEM, entertainment, and construction markets across the Greater Toronto Area for just over 40 years. The company has earned a reputation for providing a high-quality customer experience.

As per President Austin Brennan, their experienced and knowledgeable team can be depended upon in any situation to deliver quick and efficient service. On top of their product solutions — ranging from electrical, automation, safety, lighting and portable power distribution — 

Read More


 

Copper $US Dollar price per pound

Kerrwil Publications Great Place to Work. Certified December 2019 - December 2020

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2021 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil