The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the information you need. This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook** but will hopefully provide some help in navigating, while reading the code.

The 24th Edition of the CE-C, Part I, (C22.1-18)* is now available from CSA Group. This discussion of Section 78 — Marine Wharves, Docking Facilities, Fixed and Floating Piers, and Boathouses is based on the new edition.

In this article: Tables — Part B. This section of the Code contains 99 tables of essential information that is referenced by various Rules of the Code. Tables referenced by Rules are considered normative (mandatory) elements of the Code. Note that the D tables of tabulated information in Appendix D are considered non-normative (non-mandatory) elements. The tables are in numerical order based on when that table was included in the Code. Since this is a large section it will be discussed in two parts. This is Part B covering Tables 36 to 69.

Tables 36A and 36B, referenced by Rule 4-004, provide maximum allowable ampacities for aluminum and copper conductor, respectively, neutral supported cables, based on phase conductor size, and type.

Table 37, referenced by, Rule 28-104, provides motor supply conductor minimum temperature rating based on, an ambient temperature of 30 degrees centigrade, type of motor enclosure, and class rating of the insulation.

Table 38, referenced by Rules 8-202 to 8-210 provides the demand factors for electric vehicle supply equipment, based on the number of automobile spaces or stalls per feeder, and the maximum load in watts per space or stall.

Table 39, referenced by Rule 4-004 (22), provides the minimum permitted service conductors (based on Tables 2 and 4), for 3-wire 120/240 V and 120/208 V for single dwellings and feeder conductor or cable size supplying single dwelling units of row housing, apartment, or similar buildings and terminating on equipment having a conductor termination temperature of not less than 75 °C, and based on the overcurrent device rating, calculated loads, and conductor size for copper or aluminum. Note that this table applies only to conductors sized for loads calculated in accordance with Rules 8-200(1) (a), 8-200 (2), or 8-202 (1).

Table 40, referenced by Rule 12-1006, provides the number of external threads per 25.4 mm (inch), and minimum and maximum length of thread in millimetres per trade size of rigid metal conduit.


Table 41, referenced by Rules 10-614 and 70-126, provides the minimum size of bonding jumper for service raceways per the ampacity of the largest service conductor or equivalent multiple conductors, for either copper or aluminum.

Table 42 is deleted.

Table 43, referenced by Rule 10-102, provides the minimum bare copper conductor size for concrete-encased electrodes, based on the ampacity of the largest service conductor or equivalent multiple conductors.

Table 44, referenced by Rules 8-010 and 28-704, provides full load current for three-phase AC motors by motor rating in horsepower, per rated voltage, and per induction type, squirrel-cage and wound rotor motors, or synchronous type unity power factor motors.


Table 45, referenced by Rules 28-010 and 28-704, provides the full load current for single-phase AC motors by horsepower per 115 or 230 volts.


Table 46 has been moved and is now Diagram 1.

Table 47 has been moved and is now Diagram 2.

Table 48, referenced by Rule 70-104, provides the minimum trade size of conduit for mobile homes per rating of the main overcurrent protection device and whether the system ground is excluded or included.

Table 49, has been moved and is now Diagram 3.

Table 50, referenced by Rule 26-250, for transformers provides the percentage of maximum setting or rating of the primary and secondary overcurrent protection device per the rated impedance of the transformer.

Table 51, referenced by Rules 36-300, 36-308 and Appendix B, provides the minimum size of bare copper grounding conductors for a high-voltage installation, based on the maximum available short-circuit current, the maximum fault duration, and whether the joint is brazed, made by an exothermic weld, compression or bolted joint.

Table 52, referenced by Rules 36-304, 36-306, 36-308, 36-310, and 36-312, provides tolerable touch and step voltages, based on type of ground, soil resistivity in ohms per meter, and fault duration.

Table 53, referenced by Rule 12-012, provides minimum cover requirements in millimeters for direct buried cables or insulated conductors in raceways, based on wiring method, and whether installed in vehicular or non-vehicular areas.


Table 54 has been moved and is now Diagram 4.

Table 55 has been moved and is now Diagram 5.

Table 56, referenced by Rule 2-308, provides the minimum working space around electrical equipment having exposed live parts, based on the nominal voltage to-ground.

Table 57, referenced by Rule 16-210 (6) and Table 5A, provides allowable ampacities for Class 2 copper conductors based on the size of conductor and whether it is a single conductor in free air, or not more than three copper conductors in raceway or cable, and an ambient temperature of 30 degrees centigrade. Where there are more than three conductors in raceway, use the derating factors provided by column 3.

Table 58, referenced by Rule 40-002, for short-time-rated crane and hoist motors, provides ampacities for up to four insulated copper conductors in raceway or cable for the operating temperature and duration, at an ambient temperature of 30 degrees centigrade. For five or more power conductors in raceway or cable, the ampacities shown in this table are reduced by 80%. For ambient temperatures over 30 degrees centigrade, apply the derating factors in Table 5A.

Table 59, referenced by Rule 60-704, provides the minimum size of protector grounding conductors for communications systems, based on the maximum number of protected circuits, and whether they are fused or fuseless.

Table 60, referenced by Rule 16-330, provides allowable ampacities for copper, eight-conductor, Class 2 power and data communication circuit cables, based on conductor and cable size, and number of cables in a bundle.

Table 61, referenced by Rule 68-056, provides the minimum horizontal separation from pools of buried cable, depending on the type of installation (communication or power) and, whether the cable is direct buried unjacketed with bare neutral, cables with a semi-conducting jacket, cables with a non-conducting jacket, or conductors in non-conducting ducts.
Table 62, referenced by Rules 38-013 (2) and 38-014, provides feeder demand factors for elevators, based on the number of elevators on a single feeder.


Table 63, referenced by Rule 20-034, outlines the hazardous areas for propane dispensing, container filling, and storage, based on location, extent of the hazardous location, and the Group IIA hazardous location.


Table 64, referenced by Rules 20-062 and J20-062, outlines the hazardous locations at NGV fuelling facilities, based on location, and the extent of the hazardous location zone or division.

Table 65, referenced by Rules 2-400 and 2-402, provides the enclosure selection table for non-hazardous locations, based on the degree of protection against the environmental conditions, the enclosure type, and whether its for indoor only or Indoor/outdoor use.

Table 66, referenced by Rule 4-004 (22), provides ampacities for bare or covered conductors in free air, based on 40 degrees centigrade ambient temperature, 80 degrees centigrade total conductor temperature, and 610 millimetres per second wind velocity, for both copper and aluminum conductors.

Table 67, referenced by Rule 62-200, provides the minimum clearance requirements for installed space heating systems, based on type of heating system and location, and the types of obstructions and protrusions.

Table 68, referenced by Rule 8-102, provides the maximum insulated conductor length, for 120 V single-phase circuits in dwelling units, measured from the supply side of the consumer’s service to the furthest point of utilization, on a circuit using 90-degree centigrade rated copper insulated conductors, at 30 degrees centigrade ambient temperature, based on size of conductor and overcurrent protection rating.


Table 69, referenced by Rule 20-202, outlines hazardous locations at bulk storage plants, by location, extent of the hazardous location, and the zone of the hazardous location.

In the next instalment, we will be discussing the Diagrams and the Appendices Sections of the Code.

* The source for this series of articles is the Canadian Electrical Code, Part I, (C22.1-18) published by CSA.

** Note the CEC Handbook is also published by CSA.

William (Bill) Burr is the former Chair of the Canadian Advisory Council on Electrical Safety (CACES), former Director of Electrical and Elevator Safety for the Province of BC, and former Director of Electrical and Gas Standards Development and former Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting billburr@gmail.com.

 

Changing Scene

  • Prev
During the recently held IMARK Canada 2019 meeting in Niagara Falls, executives from 14 of the ...
Valard has been selected by Wataynikaneyap Power LPto provide engineering, procurement ...
The Canadian Apprenticeship Forum-Forum Canadien sur l’Apprentissage (CAF-FCA) has announced ...
Electricity Human Resources Canada has announced this year's keynote speakers for Agents of Change ...
Kiashke Zaaging Anishinaabek (KZA)/Gull Bay First Nation (GBFN) and Ontario Power Generation (OPG) ...
The BCEA's Woman's Network THRIVE Summit is taking place on October 4th at the Executive Inn ...
NSI Industries has announced the acquisition of electrical products manufacturer Bridgeport ...
The National Electrical Trade Council (NETCO)—jointly sponsored by International Brotherhood ...
IDEAL Electrical has launched its fourth annual national competition to find the best ...
IDEAL Industries Canada has announced the appointment of Sean Bernard as Regional Sales Manager to ...

Electrician Forum Brought to you by Schneider Electric

As industry experts you know the products you use everyday better than anyone and should have input on what information you receive about products and what could improve them.

Therefore, we want your insight on the biggest challenges or issues you face when installing loadcentres, breakers (CAFI, GFI's…) and other surge protection devices. We ask that you do not provide product specific details but rather your general issues and concerns or any questions that have come to mind while working with these product types. Provide us with your valued expert insight into the issues you have faced so manufacturers can better inform you about the installation and use of these products. Lets generate some discussion that will help guide the Industry.

Make your comments  HERE

 

SoneparSonepar Canada has announced the launch of new mobile applications for Gescan Vallen, Sesco and Lumen.

The mobile apps were officially released as of June of this year and features barcode scanning, access to pricing, product availability, store locator and much more – 24 hours a day, 7 days a week.

The new mobile app is changing the way customers can interact with the Operating Companies within Sonepar Canada. The barcode scanning functionality is a popular feature amongst customers allowing them to scan an item easily and add it to their cart.

 

Read More

 

 

 

Fredericton Transmission LineNB Power recenly announced it will seek approval to build a new transmission line in the Fredericton area, which will improve the reliability of the power grid in the region for approximately 25, 000 customers.

The new proposed 15-kilometre transmission line will run from the Rainsford Substation, in Fredericton, to the Mactaquac Terminal.

“NB Power strives to offer its customer a reliable power grid that meets or exceeds all utility standards,” said NB Power’s President and CEO, Gaëtan Thomas. “This will increase transmission reliability for customers in the Fredericton region with fewer interruptions that can be restored within minutes rather than hours or days.”

Read More

 

 

Codes and Regulations Brought to You by the CSA Group

  • Prev
The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the ...
The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the ...
In this article: Tables — Part B. This section of the Code contains 99 tables of essential ...
In this article: Section 58 — Passenger Ropeways and Similar Equipment. Rule 58-000 ...
  Unauthorized CSA Group certification marks have been found on wiring by Triumph Cable ...
In this article: Section 52 — Diagnostic imaging installations. The CE code is a ...
In this article: Section 46 — Emergency Power Supply, Unit Equipment, Exit Signs, and ...
  In this article: Section 44 — Theatre Installations. The CE Code is a ...
CSA has published C22.2 No. 60947-7-3, the harmonized standard for low-voltage switchgear and ...
  Electric welders. The CE Code is a comprehensive document. Sometimes it can seem ...

 

Emergency Lighting PrinciplesBy Kevin Smee, Vice President Sales at AimLite

Most of us take light for granted. It has become so ubiquitous and cheap to use that we don’t really stop to think about emergencies. Thankfully most buildings are required by law since 1974 to be equipped with emergency lighting that automatically activates during power failures to facilitate our exit.

Emergency lighting is only one component of a building’s life safety systems, but perhaps one of the most important. 

 

 

Read More  

 

Open Office DesignOpen office design has exploded in popularity over the last 20 years. In fact, the New Yorker magazine claims that approximately 70% of all offices now have an open floor plan.[1]

How did we get here?

Although open offices have been around since the mid-1700s, the cubicle culture developed by Hermann Miller in 1964 became very popular in the 1980s and 1990s. By the early 2000s, open office design started to re-emerge in an effort to encourage more collaboration and Silicon Valley was among the first to embrace sleek, open office workspaces as the norm.

Read More

 

 


ArcflashBy Tony Oruga

Network crews were working in an electrical room tasked to install an 800 A disconnect for a temporary service on the network secondary. The 3-spot network was energized at 480 V on the secondary (34.5 kV on the primary) and all three network protectors were closed and serving load. Each network protector installed was a 3000 A, 480 V Eaton CM52 unit equipped with an Arcflash Reduction Maintenance SystemE (ARMS). Prior to performing their work, crews enabled the ARMS function on all three units in the spot. This put all three network protectors in a “hair-trigger” mode, ready to clear any current condition that exceeded 2.5x the nameplate rating.

Read More

 

Product News

  • Prev
Standard Stanpro’s LED Tapes work on direct line voltage 120V and can easily be installed ...
Standard Stanpro’s FLUO LED is designed for 120 V applications and is easy and quick to ...
The LCAN series is an indoor and outdoor surface mount with V-type light distribution.   ...
HPS Sentinel G ventilated stand-up distribution transformers meet the latest federally mandated ...
Advanced Performance in a Classic Form Factor The UFIT LED Low Bay is the perfect combination of a ...
The clean and elegant design of EG series 1X4FT led flat panel light provides a modern alternative ...
Signify has announced new smart light products, including an upgraded Hue Go, the Smart button and ...
HomeWorks by Lutron is a lighting and shading control solution for luxury homes.   ...
Signify unveiled its brand-new Philips Hue Filament collection, perfect for those who want to bring ...
These LED lamps are designed to meet or exceed the standards set out in the California Energy ...

 

EikoThese LED lamps are designed to meet or exceed the standards set out in the California Energy Commission’s Title 20 and Title 24 (JA8) Appliance Efficiency Regulations.

FEATURES

  • MR16 GU5.3 and GU10 base; B11 Decorative E12 and E26 base
  • 80% more efficient and 30x longer life than standard incandescent
  • Shatter-resistant plastic housing for reduced risk of injury and breakage
  • Compatible with a wide array of dimmers
  • ANSI construction compliant

Read More

 

 

Peers & Profiles

  • Prev
Ali Heighton is the Program Coordinator for IBEW Local 37 who has found success as a young ...
Flextherm was founded in 1991 by current company President, Philippe Charron. For more than 25 ...
Ouellet Electric Heating began humbly in 1960 with Charles-Emile Ouellet, who started manufacturing ...
Justin Harris is a Programmer/Electrician for COREngineering, a New Brunswick based mechanical ...
Bill Maki is an Electrical Engineer from Thunder Bay, Ontario working as a Control Systems ...
Benedict Electrical Contracting Limited is a locally owned and operated family business in Owen ...
Spark Power Corp. is one of North America’s leading independent providers of integrated ...
Marcia Ranger is a master construction and maintenance electrician, as well as a college professor ...
Con’s Electric Company Limited was established in 1985. Based in Timmins Ontario, only 700 ...
Mark Unsworth is an electrical engineer with over 35 years of experience in project management, ...

Copper $US Dollar price per pound

Kerrwil Publications

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2019 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil