Case Study: Temporary Power for Large Scale Residential Construction

Temporary Power

Ever wonder how large construction projects with sales offices and show suites get power when there is only a generator or temporary power established on the construction site?TheBC Safety Authority (BCSA) pays close attention to these types of installations, since fire alarms, sprinklers, and other building code safety systems are not up and running during the construction phase of the project.

Recently, a BCSA safety officer conducted an assessment of a large multi-family residential site under construction. Working collaboratively with electrical contractors, other trades, safety officials, utilities, and building departments to reach safety solutions is an important part of a BCSA safety officer’s role.

During the inspection, several significant hazards were found.Most notably, townhouses had been energized using the temporary construction service, creating a risk of overload to the service. Had these dwellings become occupied, this could have resulted in a serious fire and shock hazard.

An additional hazard was created by the power cable used to provide power from the temporary distribution system to the townhouses, which was not installed with the necessary mechanical protection.Construction sites typically have heavy machinery operating and it is imperative that the power cables be installed in a manner that protects them from mechanical damage.A break in the armoured cable can result in either a fire (if combustible material is near by) or a shock hazard if the bonding provisions have been compromised.

Addressing the hazards
The safety officer first documented his findings in a certificate of inspection and contacted the electrical contractor to develop a plan to rectify the identified non-compliances.The contractor submitted an application for a variance, as required by the Safety Standards Act, to energize the show rooms and sales offices.The variance included a request to energize a specific portion of the site, and outlined the wiring method used to provide power to this area of the site, and the signage required at strategic locations on the site, including mark ups on the site’s safety plans.The safety officer granted the variance and the electrical contractor completed the installation and the obligations outlined in the variance.

To reduce the safety hazards on the site, branch circuits inside each dwelling had all unnecessary circuit conductors disconnected from circuit breakers. The heavy loads such as space heating, furnaces, dryers, ranges were also disconnected.The safety officer then informed BC Hydro and the electrical contractor that a “hold connection” be placed on the permanent installation permit.This ensures that when the permanent installation is ready for power, the necessary work is completed to transfer and disconnect the temporary power in the showrooms to remove the risk of a possible back feed.

When dealing with sites that have both permanent and temporary electrical systems, closely review your electrical code, specifically the stating that interconnection of temporary power installations and permanent installations shall not be interconnected unless by special permission.

This article was first published online by the BC Safety Authority, http://safetyauthority.ca.

 

Related Articles


Latest Articles


Changing Scene

  • Luxxbox Launches Quick Ship Program to Accelerate Project Timelines

    Luxxbox Launches Quick Ship Program to Accelerate Project Timelines

    July 16, 2025 Luxxbox announces the launch of its new Quick Ship Program, designed to provide architects, designers, and project managers in the United States and Canada with expedited access to a curated selection of their most in-demand acoustic lighting products. With a two-week turnaround from order to dispatch, the program ensures that project timelines… Read More…

  • ECS Earns Platinum Status for 8th Consecutive Year in Canada’s Best Managed Companies Program

    ECS Earns Platinum Status for 8th Consecutive Year in Canada’s Best Managed Companies Program

    July 16, 2025 Electrical Cable Supply (ECS), Canada’s largest independently owned wire and cable distributors, is proud to announce its re-certification with the prestigious Platinum designation in Deloitte’s Canada’s Best Managed Companies program for the eighth consecutive year. This announcement recognizes ECS’s sustained excellence in strategy, innovation, culture, and strong financial performance. The Canada’s Best… Read More…

  • Nexans Canada Partners with Skills Compétences Canada to Sponsor WorldSkills Team Canada 2026

    Nexans Canada Partners with Skills Compétences Canada to Sponsor WorldSkills Team Canada 2026

    July 16, 2025 Nexans has announced its partnership with Skills Compétences Canada (SCC), a not-for-profit organization that actively promotes careers in skilled trades and technologies. As part of the partnership, Nexans will sponsor WorldSkills Team Canada 2026 as they prepare to compete at the 48th WorldSkills Competition, taking place in Shanghai, China, from September 22 to 27, 2026. “At Nexans,… Read More…

  • OEL Apprentice Success Project Available Until March 2026

    OEL Apprentice Success Project Available Until March 2026

    July 14, 2025 With renewed funding by Ontario’s Skills Development Fund, the OEL Apprentice Success Project is now available for another year until March 2026. The project is part of OEL’s Employer Engagement Program (EEP) consisting of wage, training, and equipment subsidies for apprentices. These funding opportunities are available to OEL Members and non-Members. For… Read More…