In this article: Section 40 — Electric cranes and hoists. The CE Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the information you need. This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook, but will hopefully provide some help in navigating the code.

40-000 Scope — this is a supplementary or amendatory section of the code and applies to the installation of electrical equipment and circuits for electric cranes, hoists, and monorails. The CEC Handbook provides additional notes and diagrams to better explain this section.

40-002 Supply conductor sizes — because of the short duty of crane and hoist motors, supply conductors are selected from Table 58, which specifically applies to crane and hoist installations.

40-004 Conductor protection — supply conductors for the main contactors of cranes and hoists must be in raceway, armoured cable, or mineral insulated, aluminum-sheathed or copper-sheathed cable. There is an exception to this where a conducting track of conducting rails is used as per 40-018. Where conductors supply the crane or hoist equipment directly and where a flexible connection is necessary, flexible type cord or festoon cable is permitted provided there is a take-up device provided to prevent damage and contact with the floor.

40-006 Overcurrent protection — for main contact supply conductors or directly supplied equipment, the overcurrent protection must be selected as per Rule 28-200 and Tables 29 and D16 for the motor load, plus any allowance as per Rule 14-104 where conductors have been selected with capacity for the other loads on the crane or hoist.

40-008 Disconnecting means — all ungrounded conductors of the main contact conductors must be capable of being simultaneously disconnected quickly for safety in an emergency and for maintenance. The disconnect must be within sight of the main contact conductors or the equipment. In addition, the disconnect must be accessible and be operable from the ground or floor over which the crane or hoist operates.

40-010 Main contact conductors — this rule requires that where there are bare main contact conductors, they must have an ampacity not less than the conductors supplying them and, if wire, shall be not smaller than No. 4 AWG copper, or No. 2AWG aluminum. If the conductors are more than 18 m long, then the minimum size must be No. 2 AWG copper or No. 1/0 AWG aluminum unless intermediate strain relief is provided by clamp type insulating supports. Bare conductors may be hard drawn copper, aluminum wire, or steel or other suitable metal in the form of angles, tees, T-rails, or other rigid shapes.

40-012 Spacing of main contact conductors —because bare main contact conductors depend on free air space to provide insulation between phases and to ground, this rule outlines the minimum support separation required of main contact conductor wires installed in a horizontal plane of 75mm for monorail hoists and 155 mm for other than monorail hoists. If installed in other than a horizontal plane, the separation of the main contact conductor wire supports must be 200mm. They should also be supported so that the extreme limit of displacement maintains a separation of 38mm from any surface. Where the bare main contact conductors are rigid, the supports must provide a minimum separation of 25mm between conductors, collectors, and any surface.

40-014 Supporting of main contact conductors — in addition to the spacing required in rule 40-012, the main contact conductor wires must be stretched between strain insulators at each end and supported throughout the length at 6m intervals. If building conditions preclude supporting at 6m intervals, it may be increased to a maximum of 12m intervals providing the separation between contact conductors is increased by the same proportion. In the case of rigid main contact conductors, insulated supports must be spaced at intervals of up to 80 times the vertical height of the conductor but not more than 4.5m. Refer to the CEC Handbook for diagrams illustrating support spacing and calculation notes.

40-016 Joints in rigid contact conductors — this rule outlines the importance of ensuring that any joints made in rigid main contact conductors must maintain the same ampacity of the conductors over the joint to eliminate any overheating.

40-018 Use of track as a conductor — this rule permits a single monorail, tramrail or crane runway track to be used as one of the main contact conductors or supply circuit conductors for one phase of a 3-phase circuit, providing it is derived from a single isolating transformer, does not exceed 300 v, is bonded to ground (see Rule 10-1100 to 10-1108), and any joints meet rule 40-016.

40-020 Guarding of contact conductors — requires that all contact conductors be guarded against inadvertent contact with bare current-carrying parts unless incorporated in an enclosed contact assembly. In addition, as long as a minimum clearance of 6 m between bare contact conductors and grade, floor, or any working surface (including a catwalk) is maintained, guarding of bare contact conductors may not be required.

40-022 Contact conductors not to supply other equipment — this rule prohibits the contact conductors supplying the crane, hoist or monorail feeding other equipment not essential to the operation of the crane, hoist or monorail.
40-024 Bonding — as per Rule 10-406 all exposed non-current carrying parts shall be bonded to ground. In addition, in the case of a track or rail used as a conductor, it shall be bonded in accordance with Rule 40-018. Note that metal wheels on metal rails may provide a low impedance grounding path. A flexible supply connection as per Rule 40-004(2) must contain a bonding conductor.

In the next instalment, we will be discussing Section 42 — Electric welders.

The source for this series of articles is the Canadian Electrical Code, Part I, published by CSA

William (Bill) Burr is the former Chair of the Canadian Advisory Council on Electrical Safety (CACES), former Director of Electrical and Elevator Safety for the Province of BC, and former Director of Electrical and Gas Standards Development and former Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting billburr@gmail.com.

 

 

Changing Scene

  • Prev
A New Brunswick provincial program aimed at supporting and mentoring women in apprenticeable trades ...
Government Relations Minister Lori Carr announced the transfer of gas and electrical licensing ...
IDEAL continues to recognize the essential work electricians are doing during this global crisis. ...
Total investment in building construction increased 60.1% to $13.4 billion in May, ...
IDEAL Industries recently put together a new supply catalogue focused on panel builders and ...
ECAO is piloting a young leaders group, named Future Leaders Advisory Council (FLAC).   ...
Cooper Lighting extends its commitment to education and support of its customers and specifiers. ...
Stay Wired to Win is a monthly at-home challenge designed to keep your competitive spark going ...
Join the Electrical Contractors Association of Ontario (ECAO) for a live webinar on July 7 at 2:00 ...
Following the latest COVID-19 announcements from the Ontario Government, ESA has decided to ...


 

LDS Aug Products Eaton AL Series Dimmers 400Eaton's Wiring Devices AL series dimmers offer a versatile option for any dimming application - fine tune the dimming performance to match your exact needs and change colors as needed to suit any décor.

Color change kits come with three color faceplates, offering design flexibility within one product. Select models are available in 4 different color combination packs.

 

 


Read More

 

ESAAs the government continues a gradual, staged approach to reopen Ontario, ESA is assessing how they can safely resume in-person classroom training while adhering to Ontario Public Health guidelines. ESA is continuing to monitor key public health indicators and Stage 3 restrictions as efforts begin to reschedule previously postponed in-person classroom courses.

If you are registered in a postponed ESA course, they will notify you in the next couple of weeks of the rescheduled date. Please note that online courses are continuing as scheduled.

 

Read More

 


 



Case Study: EikoPro Electric LLC had a customer that had just constructed a new horse barn and was looking to light it quickly. The barn was designed to be lit with ten high bay lights for maximum efficacy and efficiency. Together with EiKO’s distributor partner, Platt Electric Redmond located in Redmond, Oregon, Pro Electric selected the EiKO 200W BAY-C high bay fixture, which puts out an impressive 30,000+ lumens at a 5000K color temperature. This high lumen output and the long life of the fixture – 72,000 hours – made it an ideal choice for the application.

Obviously, when lighting a barn, the security and safety of the animals, riders, and care givers is paramount. EiKO’s LED high bay products fill the space with light, eliminating shadows and blind spots.

Read More

Product News

  • Prev
The SlimLED you know and love is now available with a 5-position CCT selectable switch.   ...
Intense Lighting, a Leviton company, today announced the launch of the highly anticipated V-Rail ...
Beluce has developed a line of social distancing signs and “face covering required” signs to remind ...
Eaton's Wiring Devices AL series dimmers offer a versatile option for any dimming application - ...
The YDD-L is an energy-efficient dusk to dawn yard light. It was designed for barns and ...
Arani's single-sided LED plastic running man sign comes in 2 versions: with battery, and without ...
With three shapes and 14 sizes available, Lumewerx’s latest addition to the Pop family comes in ...
Midwest’s Metallic RV power centers are a cost-effective favorite among campground owners ...
The IDEAL SLK® Disconnect Fuse Kit is a waterproof breakaway safety device that ...
The LED Edge-Lit ceiling luminaire has a very slim design for a modern and minimalist ...


 

Yard LightThe YDD-L is an energy-efficient dusk to dawn yard light. It was designed for barns and farms. It is a versatile and economic light source that is good on the environment and uses long-life LED’s. The YDD-L comes standard with photo control which helps to provide significant power savings.

Lens
Polycarbonate diffused lens encloses high performance LEDs.

 

 

 

Read More

 


 

Peers & Profiles

  • Prev
At 14, Tom Miguel was sitting in the counselor’s office of Silverthorn Collegiate Institute in ...
Meredith Halfpenny is a Wind Site Technician with Boralex where she inspects, maintains, and ...
Rutul Bhavsar is a final year Electrical Engineering student at Mohawk College. He recently ...
Shannon Tymosko is a first-year apprentice with IBEW (International Brotherhood of Electrical ...
ELG Electric is an electrical contractor based out of Goderich, Ontario serving the area’s ...
Founded by Warren Osak, Electromate specializes in Robotic and Mechatronic Solutions, distributing ...
 Will West is a first-year apprentice working in the solar industry with Hakai Energy ...
“It’s definitely the Olympics of our trade,” said Lance Giesbrecht of the Ideal National ...
Tommy Carducci is a 14-year industry veteran working with Seneca Electrical and was one of 18 ...
Legend Power Systems is an innovative Canadian company headquartered out of Vancouver, B.C. Their ...


Tom MiguelBy Sarah PickardTom Miguel

At 14, Tom Miguel was sitting in the counselor’s office of Silverthorn Collegiate Institute in Etobicoke with his entire life ahead of him. In 1981, the world was changing, and like so many young men and women, he was faced with a world of choices that would go on to define both his career and his life.

It was in this office that some counsellor suggested becoming an electrician, and Tom’s interest was piqued. “I knew from that point on what field of studies I needed to focus on to become an electrician,” Tom said.

 

Read More

 


Rutul Bhavsar 1 400By Blake Marchand

Rutul Bhavsar is a final year Electrical Engineering student at Mohawk College. He recently co-authored a whitepaper on Mohawk College’s Joyce Centre for Partnership & Innovation discussing the technologies utilized in the state-of-the-art zero-carbon/carbon-neutral facility. Rutul was the lead author on the project, supported by Dr. Mariano Arriaga, General Manager of Mohawk’s Energy and Power Innovation Centre (EPIC) and Dr. Tony Cupido Research Chair, Sustainability at Mohawk College. Rutul’s interests lie in the more progressive areas of the industry, automation, control, and energy efficient technologies.

Read More


 

Copper $US Dollar price per pound

Kerrwil Publications Great Place to Work. Certified December 2019 - December 2020

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2020 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil