Canadian Electrical Industry News Week

 

May 14, 2018

Safety FlukeBy James R. White

With the recent release of the 2018 edition of the NFPA 70E standard, many users are finding it challenging to interpret what it says and prioritize where they should focus their attention. The short answer is that the entire 70E standard is important, not just one chapter, article or section. However, this article highlights 10 changes that the author believes are most important. Here in Part 2: changes 6-10.

6. The first permanently-mounted absence-of-voltage test instrument is approved

A new exception was added to section 120.5, which states “Exception No. 1: An adequately rated permanently mounted test device shall be permitted to be used to verify the absence of voltage of the conductors or circuit parts at the work location, provided it meets the all following requirements:

• It is permanently mounted and installed in accordance with the manufacturer’s instructions and tests the conductors and circuit parts at the point of work;
• It is listed and labeled for the purpose of verifying the absence of voltage;
• It tests each phase conductor or circuit part both phase-to-phase and phase-to-ground;
• The test device is verified as operating satisfactorily on any known voltage source before and after verifying the absence of voltage.”

Why the change?

This is a watershed moment for the 70E. In the past, the committee has been approached by manufacturers of LED indicator lights wanting to gain approval for their devices as an absence-of-voltage tester. We pointed to the OSHA Letter of Interpretation dated December 12, 2012, which states in part:

“Question 1: Can the type of device described above be used to verify that isolation and de-energization of the machine or equipment have been accomplished under 29 CFR 1910.147(d)(6)?

Response: No. However, the type of device that you describe, if installed correctly and maintained, might serve only as a redundant indicator that the disconnecting device is in the open ("off") position.”

In the 2018 review cycle a company presented a product that met a new UL standard and meets the requirements of a true absence-of-voltage tester (see Figure 4). The committee questioned both the company’s representative and the UL representative at length, and determined that the device presented was acceptable. The new exception noted above was then added to 120.5.

Bottom line

An LED indicator light is not an absence-of-voltage test instrument. At the time of this writing, there is only one such test instrument currently manufactured. LED indicator lights can provide a first indication, but a qualified person must still perform a manual absence-of-voltage test using a hand-held test instrument and test phase-to-phase and phase-to-ground.
Figure 4










Figure 4
Permanently-mounted absence-of-voltage test instrument

7. All mandatory reference to other standards are removed

Standards that had been mandatory are now contained in Informational Notes. For example, one mandatory reference in the 2015 edition of 70E—130.7(F)—has been renumbered to 130.7(G) and now reads “Other protective equipment required in 130.7(D) shall conform to the applicable state, federal, or local codes and standards.
Informational Note: The standards listed in Table 130.7(G), which is part of this Informational Note, are examples of standards that contain information on other protective equipment.”

This change generated a lot of discussion among committee members, especially those from the standards organizations. In past editions, the 70E has stated that arc-rated clothing and PPE must meet the ASTM standards for those articles of PPE. This was done to prevent unsafe PPE, especially arc-rated clothing and PPE, from being used by workers.

Why the change?

The NFPA wanted to remove mandatory references to other standards because the 70E is used in many countries, not just the US. Requiring another country to follow a US-based standard when it may be required by law to follow another, created conflicts. So mandatory references to other standards were removed.

Bottom line

In most cases PPE is mandated by OSHA to meet ASTM and other standards, so this is not as serious as some expressed. This author would have kept the mandatory references to other standards, but acknowledges that it does limit the use of the 70E in other countries that do not use U.S. standards.

8. An added requirement for a conformity assessment for PPE

Section 130.7(C)(14)(b) requires that PPE comply with a conformity assessment. This requirement is based on ANSI/ISEA 125, American National Standard for Conformity Assessment of Safety and Personal Protective Equipment. Informative Annex H.4 contains detailed information about the conformity assessment requirements.

Why the change?

With mandatory references to other standards eliminated in the 70E, the committee believed that another mechanism was needed to ensure workers were provided with adequate arc-rated clothing and other types of PPE. Figure 5 below illustrates the importance of conformity assessments, even when there were mandatory requirements to meet ASTM standards. The clothing in Figure 5 was purchased because it had an ATPV (Arc Thermal Performance Value or arc rating) on a label and stated it had an HRC 2 rating.


Figure 5 1Figure 5 2

















Figure 5

Garment is mislabelled. It is not arc-rated.

The inside label stated that it meets NFPA 2112 for flash fires, but makes no mention of ASTM F1506. Workers in refineries and the like are often required to wear flame resistant (FR) protective clothing that meets NFPA 2112. However, electrical workers face a risk of arc flash. The difference? Flash fires are slow burning and the heat is much less. Arc flashes produce extreme heat for a very short period of time. Thus, electricians must wear F1506 (arc-rated) clothing.

Bottom Line

A conformity assessment would have caught the issue described above. The clothing carrying the labels shown above is FR, not arc-rated and is inadequate for workers exposed to arc flash events. Clothing can be rated for both flash fires and arc flash, but this example does not state that it meets the requirements for arc-rated clothing.
9. Revised footnote for Table 130.7(C)(7)

The footnote was revised to make it clear that new rubber insulating gloves being placed into service are required to have been tested within 12 months.
Figure 6
















Figure 6
Revised table footnote in the 2018 edition.

Why the change?

The previous table footnote was unclear. Even the representatives from OSHA and ASTM did not share the same opinion. However, the 70E committee and OSHA and ASTM representatives agreed that rubber insulating gloves should go no longer than 12 months without being tested. According to the OSHA representative, gloves are considered placed into service when they are purchased, not when they are handed out. He noted that rubberinsulating gloves are tested when they are manufactured, but could sit up to two years before being purchased by the end user. So the committee decided to revise the footnote to make its meaning more understandable (see Figure 6).

Bottom Line

When gloves are purchased they should be tested. They should then be tested every six months afterwards. If they are not in service, they can sit for up to 12 months, but then would require testing. Once tested, they must be tested every six months thereafter.

10. New human error risk assessment procedure

Section 110.1(H)(2) is a new requirement covering the risk assessment procedure for “Human Error”. It states:

“(2) Human Error. The risk assessment procedure shall address the potential for human error and its negative consequences on people, processes, the work environment, and equipment. Informational Note: The potential for human error varies with factors such as tasks and the work environment. See Informative Annex Q.”
New Informative Annex Q provides excellent guidance on human performance and its relationship to workplace safety. It includes human performance modes and their associated errors, tools to improve human performance, and human performance warning flags.

Why the change?

Experts estimate the percentage of incidents caused by some form of human failure to be from 75% to 85%. With that percentage of incidents so high, it is reasonable that efforts be made to try to reduce the number of human errors.

Bottom Line

If no effort is made to account for human performance errors, the chances of them occurring increase. This author doubts that anyone could list all the human errors possible for any one task. But that is not the intent of this new requirement or Informative Annex Q. The goal of the requirement is to try to determine what errors could be made, then apply human performance tools to try to account for them.

Conclusion

This article only touches on some of the revisions to the 2018 edition of NFPA 70E. Many recurring or global changes are not covered here. The NFPA 70E committee reviews the actions it has taken in the past, then tries to improve what is written to make the 70E as clear and usable for the field service technician as possible. It is up to the user to interpret the 70E and apply it in the workplace. The author suggests that each user visit the NFPA 70E page and review the actions and committee statements for each action. These provide even more insight into why the committee took a specific action and the intent of that action.

James R. White is Vice President of Training Services, Shermco Industries for Fluke Corp.

Read Part 1 here:http://www.electricalindustry.ca/latest-news/4261-the-10-most-important-changes-in-the-2018-nfpa-70e-standard-part-1
Image source: Graphic Products

 

 

Changing Scene

  • Prev
Last week's disastrous floods have left many B.C. residents homeless, stranded or in desperate need ...
The Canadian Apprenticeship Forum (CAF-FCA) will launch a new program to empower skilled trades ...
Sean Dunnigan, President of Techspan Industries Inc., is pleased to announce the appointment of ...
The Electrical Safety Authority (ESA) would like to advise that the Minister of Government and ...
LabTest Certification Inc. is proud to announce its most recent recognition by OSHA as a Nationally ...
On November 13th, the Universal Women’s Network virtually hosted the 2021 Women of ...
Soussanna Karas, Director of Licensing at ESA, breaks down the risks of the underground economy ...
BCEA U40 group invites you to their Professional Development virtual series...     ...
Three accomplished women with diverse backgrounds are the newest members of Ontario Power ...


 

EIN ABB logo 400ABB is an international company with a large global presence, but did you know that a significant percentage of the products sold in Canada are also designed and manufactured locally?

ABB’s Installation Products division, formerly known as Thomas & Betts, operates seven manufacturing facilities in Canada, six of them in Quebec and one in Alberta.

Many of their most well-known brands, including IBERVILLE®️️, Marrette®️️, Microlectric®️️, and Star Teck®️️, are products that started in Canada and are still manufactured locally to meet Canadian standards.

 

 


 

Canadian Electrical Contractor Discussion Group: Can You Count the Deficiencies?

EIN CECD 400Have you ever been called to fix the work of a 'handyman'?

"Was supposedly done by a"certified ' electrician....told the homeowner that he got a $266 permit....no record at TSBC. Can you count the deficiencies?"

"There is a second panel change in the triplex also.......even more deficiencies. Think the guy was a glorified handyman. Ones not obvious: 240 BB heat hooked up 120....drier on 2p20....range on 2p50....water heater fed with 2c14 Bx on 2p15."

Go HERE to join the discussion

 


 



 

 Siemens Built In Isolation Products 400By Alyssa Kerslake

Life safety today is top of mind for nearly everyone. There is a certain level of trust that fire alarm systems continue to work within a fire incident. With system survivability being a key concern to regulators, building managers, and the public, Siemens has developed systems that are designed to meet and exceed regulations that protect people, property, and assets. 

One of the most significant concerns, particularly in a large multi-story building, is implementing a secure and fully functional fire alarm system. Today, it is not uncommon to have power and data for hundreds of fire alarm devices connected over a single pair of wires. The concern is, if a fault occurs somewhere between the devices, the zone and location of the device may no longer be known, or the operation of that circuit reduced or possibly impaired. These scenarios could allow an undetected catastrophic event to develop within the space due to inoperable life safety devices. 

 

Read More


 

 

David Gordon

By Terry Becker, P.Eng., CESCP, IEEE Senior Member

The CSA Z462 Workplace electrical safety Standard published its 2021 Edition in January.  A mandatory requirement for an employer is developing, implementing, and auditing an Electrical Safety Program.  If you have an Electrical Safety Program, is it up to date in its policies, practices and procedural requirements, is it performing as expected?  Workers do not necessarily do what you expect, they do what you inspect!  Management of change is required.

I have been involved in supporting industry with respect to shock and arc flash hazards in the workplace and in understanding what needs to be done to ensure worker safety, that effective defendable due diligence is established, and evidence of compliance is available related to occupational health & safety regulations both Provincial, Territorially or Federally.  I am in Ontario this week completing a detailed Electrical Safety Audit at multiple enterprise facilities.


Read More


 

Product News

  • Prev
On the hottest days of the summer and the coldest of the winter, the Napoleon NS18 heat pump and ...
Lumenwerx is pleased to launch Aera, an innovative lighting family that marks a new era in recessed ...
Eaton’s humidity sensor and fan control (HDFS3P1) device is a single pole humidity sensor for ...
With an EC motor and smart control, ORA-EC40 series air curtains are ideal for commercial and ...
Klein Tools expands its line of insulated screwdrivers with new lengths and tips, as well as a new ...
EarthTronics LED High Lumen Wattage & Color Selectable Series to provide flexibility and full ...
Eaton’s astronomic programmable timer (AT18HM) device reduces energy consumption by automating ...
The HomeGuard LED family of residential security lights, with rugged die cast aluminum ...
This preassembled constant wattage heating cable from Ouellet is specialized for roof and gutter ...


 

Milwaukee M12 Cable Stripper

Connect plug-in lamps, holiday lighting, and small appliances to the top “Controlled” outlet, while the bottom “Powered” outlet remains always on. The DW15R features tamper resistant receptacles with built-in shutters to prevent the insertion of unintended foreign objects. As well, the integrated button with vanishing feedback LED provides manual push-button on/off control and clear indiciation at any time.

Simplify control of the residence - schedule lamps and connected loads to turn on/off at specific times or based on sunrise/sunset, easily group smart devices into rooms, and create scenes to activate multiple loads at once. Utilize the auto-shutoff feature as a countdown timer in closets, hallways and bathrooms.

Read More


 

 

Incoplas Hybrid

Now available for Siemens Class 52 Actuators and Indicator Lights are the new Class 1, Div. 2 contact blocks. Suitable for use in Hazardous Location, Class 1, Div. 2 applications when used in a suitable enclosure. No matter which style actuator you use, the common base provided attaches to the hazardous location contact blocks easily.

Hazardous Location (HL) Series Contact Blocks are good for Hazardous Location CL1, DIV2 Applications using a Standard Enclosure NEMA 1, 12, 13, 4, 4X.

HL Series Contact Blocks are rated for switching high inrush loads like Tungsten Lamps.

 

Read More


 

 

EarthTronics 25-Watt Emergency Driver for Linear Highbay

The 20A Outlet and 15A Outlet have the ability to allow function specific Inserts to be installed/removed/swapped making this platform an optimal choice for renovations and new construction. The Swidget Outlet is installed using the same wiring as a standard wall receptacle and when paired with a Swidget Insert turns into a powerful and flexible Smart Home device. The swapability of the Inserts ensures that this will work with Smart Home wireless systems now and in the future.

The Swidget product line targets the Home Automation and Smart Home markets with a unique future-proof solution. Swidget currently offers eight smart Inserts with different functionalities including Wi-Fi control, indoor air quality sensor, temperature, humidity, and motion sensors, as well as a USB charger guide light, and emergency lighting. They can all be controlled from anywhere with the Swidget App for iOS/Android or Alexa and Google Home.

Read More


 

Peers & Profiles

  • Prev
Allana Kellett-Jamieson loves working in the electrical sector and is proud of the great focus ...
As the head of ABB Canada's electrification business unit, Éric Deschênes is no newcomer to the ...
Karen Pullen knows what it’s like to be the only woman on a construction site, and as a proud ...
As of February 2021, Martin Stephenson is the new President and CEO of Signify Canada.   ...
This past July, Kerith Richards, who has worked for Service Wire Company for the last seven years, ...
EngWorks was formed in 2004 as an electrical engineering and consulting firm by Allan Bozek, “After ...
Headquartered in Concord, Ontario, Mercury Lighting services national retail, ...
Among the recipients of the 2021 Clean50 Awards announced last month is Carolina Gallo, Vice ...
Sarah Silverstein is a principal with Liteline along side her two brothers Mark and Daniel. ...
As a 34-year-old female owner of an electrical contracting business, Danielle Gray may be unique. ...


EngWorksBy Blake Marchand

EngWorks was formed in 2004 as an electrical engineering and consulting firm by Allan Bozek, “After a short time we realized there was a niche in hazardous locations, in particular in hazardous area classification design requirements for various facilities. And also helping people understand just how the Canadian Electrical Code applies to hazardous locations.”

Given the complexity of hazardous locations, Bozek saw a need for education while working in the field and began developing training courses designed.

Read More


 

Éric DeschênesBy Line Goyette

As the head of ABB Canada's electrification business unit, Éric Deschênes is no newcomer to the electrical industry. He has a long track record and a passion for finding practical solutions to optimize technology adoption. Deschênes took on his current role with ABB January of 2020, he joined ABB in 2017 as Executive VP of the Electrification business after 15 years with Schneider Electric.

We met with him recently to discuss his new role at the helm of ABB Canada and his plans moving forward. He began by pointing out that the recent change to ABB Canada's structure, as elsewhere in the world, was made to make customer relations more straightforward. 

Read More


 

Copper $US Dollar price per pound

Kerrwil Publications Great Place to Work. Certified December 2019 - December 2020

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2021 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil