By William (Bill) Burr

In this article: Section 44 — Theatre Installations. The CE Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the information you need. This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook, but will hopefully provide some help in navigating the code.

Rule 44-000 Scope states that Section 44 is a supplementary or amendatory section of the code and applies to electrical equipment and installations in buildings or parts thereof that are used for dramatic, operatic, motion picture or other shows. It should be noted that, because of rapid advances in the theatre industry, some rules in this section may refer to electrical equipment that may be obsolete. The CEC Handbook provides additional notes and diagrams to better explain this section.

The section is divided into five parts:

• General rules, which applies to all theatre installations
• Fixed stage switchboards
• Portable switchboards on stage
• Fixed stage equipment
• Portable stage equipment

General

Rule 44-100 Travelling shows requires that a permit must be obtained before any electrical equipment is used for the initial performance of a travelling theatre company, circus, or other type of travelling show, even if held in a theatre. This ensures that a qualified person oversees the installation.

Rule 44-102 Wiring method requires that all wiring, in the stage, stage wing areas, orchestra pits and projection booths must be in rigid metal conduit, electrical metallic tubing, mineral-insulated cable, flexible metal conduit, armoured cable, lead-sheathed armoured cable, aluminum-sheathed cable, or copper-sheathed cable. Note that surface raceways are not permitted on the stage side of the proscenium wall. Flexible cord or cable is permitted in accordance with rules 44-252, 44-320, 44-350, and 44-354 of this section and other wiring must be in accordance with Section 12 or Section 76. The proscenium is the frame separating the stage from the audience.

Rule 44-104 limits the number of border, stage pocket, or remote control circuit conductors to the requirements of rule 12-910. In addition, the fill of conductors is limited to 20% of the cross-sectional area of auxiliary gutters or metal wireways.

Rule 44-106 permits aisle light circuits to supply up to 30 - 25 watt lights.

Fixed stage switchboards

Rules 44-200 and 44-202 require fixed stage switchboards to

• be dead front
• have mechanical protection above the switchboard covering the full length as well as the space between the board and the wall behind
• have exposed live parts on the back of the board enclosed by the walls of the building, by wire mesh grilles, or by other acceptable methods
• have a self-closing door at the entrance of the enclosure

Rule 44-204 specifies that only externally operated enclosed switches shall be used.

Rule 44-206 requires that a pilot lamp

• protected by a 15 amp or less overcurrent device
• connected ahead of any master switch

be included in every switchboard enclosure that is connected to the circuit supplying the switchboard.

Rule 44-208 specifies that the fuse(s) for switchboards can be either plug or cartridge type but must be provided with an additional separate enclosure.

Rule 44-210 requires that an overcurrent device be connected in the ungrounded conductor of each circuit leaving the switchboard. Notwithstanding Rule 30-104, a 120-volt luminaire may be protected by an overcurrent device rated up to 100 A.

Rule 44-212 governs the installation of lighting dimmers and requires that

• they must be completely disconnected from the supply when they are in the open position
• resistance type dimmers that do not open the circuit may be connected in a grounded neutral conductor
• all current-carrying parts of dimmers must be enclosed to prevent accidental contact

Rule 44-214 requires that stage and gallery pockets, which are receptacles in the performance space used to power stage lighting, be controlled from the switchboard.

Rule 44-216 provides that, due to the high heat and vibration that may be associated with switchboards, some additional requirements that conductors must have are

• insulation suitable for the temperatures involved and not less than 125°C
• an ampacity concurrent with the switch or overcurrent device to which they are connected
• bushed holes where they pass through a metal enclosure
• wire strands soldered together fastening under a clamp or binding screw
• soldered into a lug or connected to a solderless lug, where the conductor is No.8 AWG or larger
Portable switchboards on stage

Rule 44-250 provides that portable switchboards must be constructed in substantial enclosures, which may be open during operation, if there are no exposed live parts except on dimmer faceplates.

Rule 44-252 requires that portable switchboards be supplied from an externally operated, enclosed, fused master switch within the switchboard that

• is supplied by a flexible cord or cable, type S, SO, or ST, that has sufficient ampacity to carry the total load current of the switchboard
• arranged to cut off current from all apparatus within the enclosure, except the pilot light
• has an ampere-rating of the fuses not greater than the total load current of the switchboard

Fixed stage equipment

Rule 44-300 specifies that footlights be installed in individual outlet boxes, where wired in rigid metal conduit or EMT, or in a metal trough to ensure bonding continuity.

Rule 44-302 provides minimum thickness of not less than

• 0.78 mm thick for metal work for footlights, borders, proscenium sidelights, and strips
• 0.53 mm thick for metal work of bunches and portable strips

Rule 44-304 requires that terminals of lampholders have a clearance of a minimum of 13mm from the metal trough.
Rule 44-306 calls for suitable guards to protect borders, proscenium sidelights and strips from mechanical damage and accidental contact with combustible material.
Rule 44-308 specifies that suspended luminaires in borders and strips must be electrically and mechanically safe.
Rule 44-310 — because of possible severe vibration, conductor terminations at lampholders need to have a positive and reliable connection by soldering or suitable solderless connections.
Rule 44-312 identifies that mogul lampholders need to be double walled with adequate ventilation between the walls.
Rule 44-314 requires that conductors supplying field assembled foot, border, proscenium, and portable strip luminaires must have insulation rating suitable for the high operating temperatures involved and not less than 125 °C.
Rule 44-316 reiterates that branch circuit overcurrent protection for footlights, border lights, and proscenium sidelights must be consistent with Rule 30-104.
Rule 44-318 states that pendant lights containing lamps with more than 100-watt capacity need to be provided with a minimum 13mm mesh guard to contain and prevent falling glass.
Rule 44-320 specifies that flexible cord or cable supplying border lights must be

• S, SO, or ST type
• fed from points on the grid iron or from other acceptable overhead points, but not from side walls
• arranged so that clamps and binding screws are free from strain
• provided with a metal bushing where passing through a metal or wooden enclosure
• located to permit convenient access to terminals or binding posts inside the switchboard enclosure

Rule 44-322 addresses the flexibility of wiring for arc pockets, which are receptacles that supply carbon-arc lighting fixtures.
Rule 44-324 states that at least one receptacle installed in gallery pockets be rated not less than 30 amps for use by higher capacity lighting equipment.
Rule 44-326 specifies that arc and incandescent receptacles cannot be interchangeable, and receptacles and plugs intended for the connection of

• arc lamps must be rated not less than 35 A and be supplied by a minimum No. 6 AWG copper conductor
• incandescent lamps be rated not less than 15 A and be supplied by a minimum No.12 AWG copper or No. 10 AWG aluminum conductor

Rule 44-328 requires that curtain motors must be the enclosed type.
Rule 44-330 governs the control and operation of flue dampers, which are located above the stage to allow smoke to exit in case of fire. Where stage flue dampers are released by an electrical device, it must be

• held in the closed position and automatically released on power interruption
• controlled by at least two single-pole switches enclosed in self-closing but unlocked or latched metal boxes, one located at the electrician’s station, and the other as per rule 28-604
• rated for full circuit voltage, with minimal circuit resistance, and located in a protective metal box in the loft above the scenery

Portable stage equipment

Rule 44-350 requires that electrical fixtures attached to scenery must be securely fastened and supplied with flexible cord or cable suitable for hard usage, and selected in accordance with Rules 4-012 and 4-040. In addition, bushings must be used where stems of fixtures extend through the scenery.
Rule 44-352 directs where festooned lighting is used that the joints be staggered and that guards or shades be used to prevent contact with combustible material.
Rule 44-354 states that supply conductors for arc lamps, bunches, or other portable equipment must be approved for extra-hard usage. Other miscellaneous portable equipment may be other than extra-hard usage. The supply conductors must all selected as per rules 4-012 and 4-040.
Rule 44-356 requires that special stage effects portable equipment must be acceptable to the local AHJ and located to prevent flames, sparks or hot particles from contacting combustible material.
In the next installment, we will discuss Section 46 — Emergency Power Supply, Unit Equipment, Exit Signs, and Life Safety Systems.

* The source for this series of articles is the Canadian Electrical Code, Part I, published by CSA

** Note the CEC Handbook is also published by CSA.

William (Bill) Burr is the former Chair of the Canadian Advisory Council on Electrical Safety (CACES), former Director of Electrical and Elevator Safety for the Province of BC, and former Director of Electrical and Gas Standards Development and former Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting billburr@gmail.com.

 

 

Changing Scene

  • Prev
The year was 2002: Jean Chrétien was Prime Minister, Avril Lavigne topped the charts, the ...
The company’s wholesale locations will be branded Robinson Supply, and the lighting and bath ...
The 500+ km transmission line from Edmonton to Fort McMurray includes two substations and involved ...
Poweska is currently BC Hydro’s Executive Vice President, Operations, with responsibility for ...
During E.B. Horsman & Son’s (EBH) Annual General Meeting on March 5, 2019, ABB Canada was ...
The Electrical Safety Association plans to implement a risk-based approach for electrical wiring by ...
Organized by the Hong Kong Trade Development Council, the Hong Kong International Lighting Fair ...
MCEE’s New Product Competition highlights the commitment to efficiency, conservation and ...
Desdowd Inc. has been chosen to serve as Thermon’s manufacturer's agent for the province of ...
Gerrie Electric Wholesale Limited’s website has a fresh new look but continues to offer the ...

Electrician Forum Brought to you by Schneider Electric

As industry experts you know the products you use everyday better than anyone and should have input on what information you receive about products and what could improve them.

Therefore, we want your insight on the biggest challenges or issues you face when installing loadcentres, breakers (CAFI, GFI's…) and other surge protection devices. We ask that you do not provide product specific details but rather your general issues and concerns or any questions that have come to mind while working with these product types. Provide us with your valued expert insight into the issues you have faced so manufacturers can better inform you about the installation and use of these products. Lets generate some discussion that will help guide the Industry.

Make your comments  HERE

 

CSAClimate change and its associated impacts will play a central role in Canada's electricity future. In fact, the Conference Board of Canada estimates that approximately $347.5 billion will need to be invested in electricity infrastructure to maintain the system reliability we have today. Making smart investments now can improve the system and help to avoid more severe climate related costs in the future.

“The critical infrastructure we rely on to power our daily lives must remain resilient to more damaging and frequent extreme weather events,” says Mary Cianchetti, President of Standards at CSA Group. “Standards play a critical role in making that happen.

Read more about climate change solutions...

 

 

 

BCEA Victoria Trade Show

The BC Electrical Association in conjunction with the Victoria distributors and manufacturers committee on Vancouver Island will be holding a tradeshow and golf tournament on May 2, 2019 at the Westin Bear Mountain Resort.

This will be a table top trade show. Distributors have agreed not to hold their own tradeshow three months on either side of this date to ensure a successful event.

 

 



Read more about the BCEA Victoria Trade Show...

 

 

Codes and Regulations Brought to You by the CSA Group

  • Prev
The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the ...
The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the ...
In this article: Tables — Part B. This section of the Code contains 99 tables of essential ...
In this article: Section 58 — Passenger Ropeways and Similar Equipment. Rule 58-000 ...
  Unauthorized CSA Group certification marks have been found on wiring by Triumph Cable ...
In this article: Section 52 — Diagnostic imaging installations. The CE code is a ...
In this article: Section 46 — Emergency Power Supply, Unit Equipment, Exit Signs, and ...
  In this article: Section 44 — Theatre Installations. The CE Code is a ...
CSA has published C22.2 No. 60947-7-3, the harmonized standard for low-voltage switchgear and ...
  Electric welders. The CE Code is a comprehensive document. Sometimes it can seem ...

 

EE LightingBy Blake Marchand

Energy Efficient Lighting is a LED lighting manufacturer with nearly 30 years of industry experience. One that was founded on principles of environmental sustainability and responsibility to future generations. Based out of Markham, Ontario, Energy Efficient Lighting are established veterans within the LED lighting industry. And with the prominence of LED lighting being a fairly recent industry trend, it is a claim that a select few can make. They offer complete lighting solutions for commercial and industrial applications. Their product lines include conventional lighting fixtures, LED retrofit kits, complete LED luminaires, LED systems, drivers and electronic ballasts.

Read more about Energy Efficient Lighting...

Tools for the Trade

  • Prev
  IDEAL Industries has introduced Combination Drill Taps to its tool lineup. Combining the ...
  Stripping and crimping device, 100 - 240 V input voltage, for insulated ferrules with a ...
Professional all-in-one cutter/stripper for coaxial and twisted pair cables     ...
  Klein Tools' Coax Explorrer 2 tests coaxial cable and maps up to 4 locations   ...
  Ideal Industries' T-14 wire stripper s are ideal for all professionals working within the ...
  The ATS850 conveyor eliminates all types of electro static discharge requirements. ...
  Lorik Tool & Automation has the experience and ability to manufacture a variety of ...
  Ideal Industries' 26 piece insulated Journeyman kit is ideal for new electricians or for ...
  Klein Tools Deluxe Fish Rod Set comes in 19 pieces that when assembled can fish wire and ...
  BendWorks Software was designed to help electrical contractors adopt this new process ...

Product News

  • Prev
MetGUARDZ Metatarsal and Lace Protectors deflect and disperse the impact of falling loads. ...
Featuring a patent-pending design that is unmatched within the industry, the C-Clamp with ...
NJZ Lighting new design Freedom II Series Omni-directional adjustable design LED high bay Light ...
The JP Series plug and play lamps from ForeverLamp are ballast driven LED replacement for Metal ...
Current’s newest outdoor product is the ERLC Compact Cobra Head which delivers the same lumen ...
The compact Fluke Norma Power Analyzer 4000 provides the latest measurement technology to assist ...
MI 3210 TeraOhm XA 10kV is a portable, battery or mains powered test instrument with excellent IP ...
Next-generation MicroScanner verifies voice/data/video cable and services with a revolutionary user ...
The E36312A/GPB from Keysight Technologies is an E36300 series triple output programmable DC power ...
Introducing VoltAware, the sleek, non-contact voltage tester designed by the innovative minds at ...

3-Phase Electrical Ltd.By Blake Marchand

Winnipeg-based 3-Phase Electrical prides themselves on the high calibre of work they produce and their attention to detail, always ensuring that all work is performed to the highest possible standards. Their success is attributed to understanding their customers’ needs and continuously exceeding customer expectations.


Their expertise is facilitated by a solid foundation of careful planning and diligent scheduling, both of which are key elements to delivering projects successfully.

Read more about 3-Phase Electrical Ltd....

 

 

HeatingBy Stéphane Lettre

Today the whole planet is talking about climate, reducing the ecological footprint, and energy efficiency. Various governments are making commitments to reduce greenhouse gas emissions and people are becoming more aware of the impact of choices they make on a daily basis. Another phenomenon that is accelerating in parallel is the search for lower costs among households with increasing levels of debt and companies seeking to remain competitive and profitable.



Read more about Thermostats...

 

 

 

Peers & Profiles

  • Prev
Energy Efficient Lighting is a LED lighting manufacturer with nearly 30 years of industry ...
Matt Stanson is a master electrician with over 30 years of experience. He now leads a team of ...
After eight months, 263 events, 17 broken clocks, and thousands of competitors, Ideal ...
The National Electrical Trade Council (NETCO) is an industry-funded, not-for-profit organization ...
After eight months, 263 events, 17 broken clocks, and thousands of competitors, Ideal ...
Born and raised in western India, Rupali’s passion for mathematics and science began at a ...
After eight months, 263 events, 17 broken clocks, and thousands of competitors, Ideal ...
Allison Wood and Dominique Rivet are two apprentices who had a wealth of career options available ...
  In a recent sit-down Electrical Industry Canada was able to learn a little ...
David Johns is a unique and dedicated individual both at home and in the workplace. At home he is a ...

Copper $US Dollar price per pound


 

EHRCIn a recent interview with the The National Post, Electricity Human Resources Canada CEO Michelle Branigan said the need for workers in Canada’s electricity industry is “extremely critical.”

The industry directly employs almost 107,000 people, but less than 1 in 20 is aged 25 or under, only 1 in 4 is a woman, and just over 1 in 10 is from a visbile minority.

These statistics are from EHRC’s Workforce in Motion, a labour market intelligence research initiative for the years 2017-2022. The research report is a planning and informing tool for a wide range of electricity sector stakeholders and provides critical information to the sector for both short and long term resource planning.

Read More

 

 

Kerrwil Publications

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2019 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil