Canadian Electrical Industry News Week

 

Canadian Electrical CodeJune 12, 2017

By William (Bill) Burr

In this article: Section 46 — Emergency Power Supply, Unit Equipment, Exit Signs, and Life Safety Systems. The CE Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the information you need. This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook, but will hopefully provide some help in navigating the code.


Rule 46-000 Scope states that Section 46 is a supplementary or amendatory section of the code and applies to the installation, operation and maintenance of emergency power supply and unit equipment intended to provide power to life safety systems, exit signs, and illumination of exit signs in the event of failure of the normal power supply in cooperation with the requirements of the National Building Code of Canada. Appendix B and the CSA CEC Handbook provide additional explanations and diagrams.


Rule 46-002 provides some special terminology for this section and defines emergency power supply, life safety systems and unit equipment in accordance with the terms in the National Building Code of Canada.


The section is divided into 4 parts:

• general rules, which applies to all emergency power supplies and unit equipment
• emergency power supplies
• unit equipment
• exit signs


General


Rule 46-100 specifies that an emergency power supply, including unit equipment, must have adequate capacity for all the equipment that is connected to it in case of a normal power failure.
Rule 46-102 requires that complete instructions for operation, care and monthly testing be posted, under glass, and on the premises, in conformance with the National Building Code of Canada.
Rule 46-104 states that, where batteries are used as the emergency power supply, they must be maintained in proper condition and fully charged.
Rule 46-106 specifies that emergency lights must be on a dedicated emergency circuit, with no other lamps connected to it, and need to be arranged so that the area covered is illuminated even if any one lamp fails.
Rule 46-108 outlines the wiring method for all conductors, with a few exceptions as noted below, required for life safety systems, emergency power supplies, exit signs, and between unit equipment and remote lamps. In addition to the methods outlined in this rule, the National Building Code of Canada or provincial building codes must be referenced for additional requirements for fire protection of conductors that may apply. For additional information see Appendix B and G.

These methods include:
• metal raceway of the totally enclosed type
• cable having a metal armour or sheath
• rigid non-metallic conduit
• electrical non-metallic tubing imbedded in at least 50mm of poured concrete or masonry

Exceptions to this rule include:
• conductors installed in buildings of combustible construction where rules 12-506 to 12-520 apply and may be run as NMSC or in totally enclosed non-metallic raceway
• use of flexible cord and attachment plug for unit equipment in accordance with Rule 46-304(3)
In addition, the above noted conductors must be kept separate from all other conductors and equipment, with the exception of transfer switches and exit and emergency lights with two sources of supply. Also, the supply for any other electrical equipment that is not part of the “life safety system” must not enter any busway, splitter, or other enclosure that is part of the emergency power supply as per rule 46-208.
Emergency power supply
Rule 46-200 notes that Rules 46-202 to 46-212 apply only to central standby power sourced emergency power supplies.

Rule 46-202 outlines that emergency power supplies, in conformance with the National Building Code of Canada, must consist of:
• an automatically rechargeable storage battery with sufficient capacity to maintain at least 91% of full load voltage for a minimum of 30 minutes, or
• an automatically and failure-free starting and transferring generator conforming to CSA C282 with sufficient capacity to carry the full load of the emergency power supply

Note that where storage batteries are used they should not be automobile or lead acid batteries unless they are of the totally enclosed glass-jar type, except by special permission granted under rule 2-030.
Rule 46-204 reaffirms that all power, control and communication conductors required for emergency power supply and installed outside the generator room, must, as per the requirements of the National Building Code of Canada, be protected against fire exposure to maintain continued operation.

Rule 46-206 specifies that an automatic transfer switch, solely accessible to authorized persons, that actuates upon failure of the normal power supply, must control the emergency power supply. Where an area is adequately illuminated by daylight and artificial light is only needed at night, an automatic light-actuated device may be used to control emergency illumination separately in this area.

Rule 46-208 requires that the overcurrent protection for an emergency power supply needs to be coordinated with OC devices, for feeders and circuits supplying life safety and other emergency power supply equipment, to provide selective operation in the event of a fault. These overcurrent devices must be accessible to authorized persons only.

Rule 46-210 outlines that all emergency power supplies need to be equipped with audible and visual trouble signal devices that
• warn of the normal source current failure
• indicate exit signs or life safety systems are supplied from the emergency power supply
• are wired so that they can be silenced, but continually show a red warning or trouble light
• when the system is returned to normal, continue to audibly indicate the need to restore or automatically reset the silencing switch to normal

Rule 46-212 specifies that remote lamps, located some distance from the power supply, must have a voltage drop limited to 5% of applied voltage.

Unit equipment
Rule 46-300 outlines that Rules 46-302 to 46-306 apply to unit equipment for emergency lighting only, as defined in Appendix B.
Rule 46-302 requires the bottom enclosure of unit equipment to be mounted at least 2 meters above the floor where practicable. Note that the definition of practicable includes the synonym “feasible”.

Rule 46-304 specifies the requirements that the supply connections for unit equipment include:
• permanent connection, if the voltage exceeds 250 volts or 24 amps
• flexible cord and attachment plug located 2.5 metres above the floor and within 1.5 metres of the unit equipment, where the ratings above are not exceeded
• automatic actuation upon failure of the normal lighting power supply to the area covered
Rule 46-306 provides the requirements for remote lamps to unit equipment and requires that
• the voltage drop of conductors be limited to 5% of the marked output voltage of the unit equipment
• remote lamps be included in the list of lamps provided for that unit
• the number of lamps connected to a single unit not exceed the power output rating of the unit for the duration of the emergency period
Exit signs

Rule 46-400 requires that exit signs be
• connected to a dedicated circuit, except where connected to a circuit supplying emergency lighting in the same area
• illuminated by an emergency power supply, where emergency lighting is required by the National Building Code of Canada. Note that the NBC requires that exit signs be illuminated continuously, so no switch, time clock, or other disconnecting means may be inserted in the circuit


In the next instalment, we will be discussing Section 50 — Diagnostic Imaging Installations. (Note: Sections 48 and 50 have been deleted in the 23rd Edition)
* The source for this series of articles is the Canadian Electrical Code, Part I, published by CSA
** Note the CEC Handbook is also published by CSA.

William (Bill) Burr is the former Chair of the Canadian Advisory Council on Electrical Safety (CACES), former Director of Electrical and Elevator Safety for the Province of BC, and former Director of Electrical and Gas Standards Development and former Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting billburr@gmail.com.

 

 

Changing Scene

  • Prev
In his new role as Stelpro's Vice-President, Sales and Business Development, ...
The Support Equity and Under-Represented Groups project will address the under-representation of ...
Show your support by sharing a photo or experience of how a lineworker has made an impact in your ...
Eleven highly accomplished Hamiltonians are being honoured by Mohawk College as Distinguished ...
Canada’s Minister of Natural Resources recently announced the Governor in Council has ...
ABB recently won an order of eBus charging solutions to support TTC as it modernizes its service ...
A consortium of Canadian energy organizations has been shortlisted to develop the electricity ...
Skills Ontario Summer Camp is a week-long day program for kids entering Grades 7-9.   ...
  Glen Dimplex Americas is proud to announce that its Vancouver facility was recently ...
May 13 to 19 is Powerline Safety Week in Ontario, which is meant to inform people across the ...

Electrician Forum Brought to you by Schneider Electric

As industry experts you know the products you use everyday better than anyone and should have input on what information you receive about products and what could improve them.

Therefore, we want your insight on the biggest challenges or issues you face when installing loadcentres, breakers (CAFI, GFI's…) and other surge protection devices. We ask that you do not provide product specific details but rather your general issues and concerns or any questions that have come to mind while working with these product types. Provide us with your valued expert insight into the issues you have faced so manufacturers can better inform you about the installation and use of these products. Lets generate some discussion that will help guide the Industry.

Make your comments  HERE

 

ABB TXploreOn May 30, 2019, ABB was honoured with an Electrical Review Excellence award for its ABB Ability inspection for transformers – TXplore -- in the ‘Power Product of the Year’ category. Electrical Review is the leading electrical industry publication in the UK.

The judging panel, under the leadership of the highly-respected industry figure – Prof. Ian F. Bitterlin, Consulting Engineer and Visiting Professor at University of Leeds, was impressed by the capability of TXplore to make transformer inspection a much safer activity while also boosting asset availability for power grid operators.

 

Read More

 

 

 

Codes and Regulations Brought to You by the CSA Group

  • Prev
The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the ...
The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the ...
In this article: Tables — Part B. This section of the Code contains 99 tables of essential ...
In this article: Section 58 — Passenger Ropeways and Similar Equipment. Rule 58-000 ...
  Unauthorized CSA Group certification marks have been found on wiring by Triumph Cable ...
In this article: Section 52 — Diagnostic imaging installations. The CE code is a ...
In this article: Section 46 — Emergency Power Supply, Unit Equipment, Exit Signs, and ...
  In this article: Section 44 — Theatre Installations. The CE Code is a ...
CSA has published C22.2 No. 60947-7-3, the harmonized standard for low-voltage switchgear and ...
  Electric welders. The CE Code is a comprehensive document. Sometimes it can seem ...

 

Lighting ProjectLocated at one of the busiest retail intersections in Montreal’s downtown core, 1411 Crescent is a beautiful art deco structure built in 1934. Four floors of offices sit above retail space on the northeast corner of Ste-Catherine Street. BTB Real Estate Investment Trust purchased the building in 2018 and with its own team growing, chose to move its company headquarters to the new space. They appreciated the charm of the building, and its ideal location in the Golden Square Mile.

To signify this important move, BTB REIT sought to enhance the building’s façade to make it more impactful on this vital city block.

 

Read More 

 

ABBTechFor decades, ABB has made intricate scientific instruments that measure and analyze gases in the atmosphere to help scientists better understand its composition and evolution. Now, ABB is helping to more accurately measure greenhouse gases (GHGs), which are trapping heat in the atmosphere, resulting in an increase in global surface temperature.

One such instrument is an ABB interferometer carried aboard the Greenhouse Gases Observing Satellite-2 (GOSAT-2), which was launched in October 2018 as part of a Japanese government project. 

Read More

 

 

Tools for the Trade

  • Prev
  IDEAL Industries has introduced Combination Drill Taps to its tool lineup. Combining the ...
  Stripping and crimping device, 100 - 240 V input voltage, for insulated ferrules with a ...
Professional all-in-one cutter/stripper for coaxial and twisted pair cables     ...
  Klein Tools' Coax Explorrer 2 tests coaxial cable and maps up to 4 locations   ...
  Ideal Industries' T-14 wire stripper s are ideal for all professionals working within the ...
  The ATS850 conveyor eliminates all types of electro static discharge requirements. ...
  Lorik Tool & Automation has the experience and ability to manufacture a variety of ...
  Ideal Industries' 26 piece insulated Journeyman kit is ideal for new electricians or for ...
  Klein Tools Deluxe Fish Rod Set comes in 19 pieces that when assembled can fish wire and ...
  BendWorks Software was designed to help electrical contractors adopt this new process ...

Product News

  • Prev
Single Phase Power Solutions introduces the 30 HP Belle Single-Phase Motor™ which uses ...
Emerson expands the innovative Greenlee Shear 30T with seven new die sets and a new bare kit ...
ASCO Power Technologies offers its Model 420 surge protective device for point-of -use ...
The new VALVETRAB MS Type 1+2 combined lightning current and surge arresters have a 3+V circuit. ...
A truly smart home does more than just connect you; it works for you. With iDevices' advanced smart ...
Previously available from one of the world’s largest line pulling companies, the PLCS is now ...
Fluke has revamped its entire line of industrial thermal cameras with more premium features packed ...
Emerson has improved AMS Machinery Manager predictive maintenance and analysis software ...
AEMC’s ten New Simple Logger® Data Loggers are small one channel recording devices ...
ASCO Power Technologies, a provider of critical power solutions, releases the third generation of ...

 

Banner VE Smart CameraFeatures included in the latest version of Vision Manager software simplify the integration of VE Series smart cameras into vision guided robotic (VGR) systems and make it easy to correct distortions caused by camera perspective. Also new to the software is the ability to view application images remotely via a built-in webserver. Vision Manager version 1.7.0 is available now for free download.

EASY INTEGRATION WITH VISION GUIDED ROBOTS

All the logic required to integrate a VE Series smart camera into a VGR system is in the software. 

Read More

 

 

Peers & Profiles

  • Prev
Bill Maki is an Electrical Engineer from Thunder Bay, Ontario working as a Control Systems ...
Benedict Electrical Contracting Limited is a locally owned and operated family business in Owen ...
Spark Power Corp. is one of North America’s leading independent providers of integrated ...
Marcia Ranger is a master construction and maintenance electrician, as well as a college professor ...
Con’s Electric Company Limited was established in 1985. Based in Timmins Ontario, only 700 ...
Mark Unsworth is an electrical engineer with over 35 years of experience in project management, ...
Manygo Ho is an electrical designer with AECOM’s Buildings and Places group. Manygo designs ...
Don Neigel is Manager of the CSA-certified panel shop at Delta, BC’s Optimil Machinery. ...
New Brunswick Power recently struck a deal with Joi Scientific to develop an innovative technology ...
The Shock Doctors is an electrical contracting company operating out of Orillia, Barrie and ...

Copper $US Dollar price per pound

Kerrwil Publications

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2019 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil