In this article: Section 58 — Passenger Ropeways and Similar Equipment. Rule 58-000 states that Section 58 is a supplementary or amendatory section of the code and applies to passenger ropeways as defined in the CSA Z98, Passenger Ropeways and Passenger Conveyers standard, which includes tramways, chairlifts, gondolas, surface ropeways, passenger conveyors, and similar equipment. In addition, ANSI B77.1, Passenger Ropeways – Aerial Tramways, Aerial Lifts, Surface Lifts, Tows and Conveyers - Safety Requirements, and Can/CSA-C22.3 No.1, Overhead Systems should be referenced.

 

 

Appendix B and the CE Code Handbook provide additional information.

Rule 58-002 provides special terminology definitions for Cabin, Messenger, Passenger Conveyor and Station.

General requirements

Rule 58-010 requires that, in addition to the spacing requirements of Rule 2-308, the headroom in working spaces around controllers, disconnecting means, and other electric equipment must be no less than 2.0 m. Part 2 of the rule provides that the requirements for headroom may be relaxed provided that

  • Only authorised persons have access to the area
  • The working space is kept clear of obstructions, and either
    • o live parts are guarded, isolated or insulated and the equipment can be examined, adjusted, serviced or maintained while energized without removing the protection, or
    • o a cautionary label advising that the equipment cannot be examined, adjusted, serviced, or maintained while energized is applied, or
    • o the applied voltage is equal or less than 30 V RMS or 42 V peak

Rule 58-012 specifies that circuits of less than 50 volts must be bonded to ground as per Rule 10-114.  Communication, control, remote control, monitoring, supervision, and signal circuits may be isolated, and grounded in accordance with Rule 10-206. The haul rope for these circuits may be isolated and ungrounded.

Rule 58-014 limits voltage for all circuits to 300 volts-to-ground except for

  • 750 volts-to-ground for motors, machine brakes, motor-generator sets, floodlighting, and heaters
  • 120 volts-to-ground for motor control circuits
  • 48 volts-to-ground for communication, control, remote control, monitoring, supervision, and signal circuits except for hand-crank-type telephone signal bell circuits
  • 30 volts-to-ground or 40 volts-to-ground peak for aerial conductors carried between towers that support the passenger ropeway, except hand-crank-type telephone signal bell circuits

Rule 58-016 provides that luminaires for night skiing or similar floodlighting applications may be installed on passenger ropeway towers and stations if there is a circuit breaker, installed in a lockable enclosure that disconnects all ungrounded conductors, and that each circuit to the luminaires is protected by a ground fault circuit interrupter (Class A GFCI).

Conductors

Rule 58-102 specifies that the minimum size of conductors for all communication, control, remote control, monitoring, supervision, and signal circuits shall be No. 26 AWG copper, except for circuits contained in travelling cables where the minimum size must be No. 20 AWG.

Rule 58-104 permits that

  • optical fibre cables, shielded cables, and conductors for operating devices, power, motor, heating, air conditioning, operating, signal, communication, control, safety, fire alarm, and lighting circuits may be grouped in raceway systems or travelling cables, providing the insulation rating for each conductor is not less than the conductor with the maximum circuit voltage
  • optical fibre cables, shielded cables, and conductors for operating devices, operating, signal, communication, control, safety, and fire alarm circuits may be run in the same aerial cable, providing that the insulation rating for each conductor is not less than the conductor with the maximum circuit voltage

Note that optical fibre cables include conductive, non-conductive and hybrid types as defined in Rule 56-102.

Wiring methods

Rule 58-200 outlines acceptable wiring methods in passenger ropeways and similar equipment:

  • Generally, all conductors, including optical fibre cables in machinery spaces, control spaces, in or on cabins, in machine rooms and control rooms must be installed in rigid metal conduit, EMT, rigid PVC conduit or wireways, except for travelling cables connecting the movable drive carriage or movable return carriage.
  • In addition, the following wiring methods may be used:
    • o mineral-insulated cable
    • o aluminum-sheathed cable
    • o armoured cable
    • o cable trays installed in accordance with Rules 12-2200 to 12-2210
    • o flexible conduit or liquid-tight flexible conduit between raceways and limit switches, interlocks, operating devices, or similar devices
    • o flexible conduit or liquid-tight flexible conduit between control panels and motors, machine brakes, motor-generator sets, disconnecting means, or pumping unit motors and valves
    • o jacketed cables installed between raceways and signal equipment and between raceways and operating devices where mechanical protection is provided and where the cables are supported including:
      • cables used in Class 1 extra-low voltage and Class 2 low-energy circuits, including but not limited to travelling cables connecting the movable carriage or movable return carriage
      • extra-low-voltage control cable
      • communication cable
      • fire alarm and signal cable
      • multi-conductor thermoplastic-insulated cable
      • hard-usage and extra-hard-usage cables
      • auxiliary gutters between controllers, starters, and similar apparatus
      • jacketed flexible cords and cables used in extra-low-voltage circuits (30 V or less), not greater than 2 m in length, supported and provided with mechanical protection

Rule 58-202 requires that supports for travelling cables be located and provided with suitable guards to prevent damage to the cables and contact with other equipment.

Protection and control

Rule 58-300 requires that motor control devices be arranged, as per rules 28-312 and 28-400, to prevent automatic restarting after shutdown where restarting could cause injury to persons.

Rule 58-302 provides that disconnecting means for the ungrounded conductors of the main drive motor and auxiliary drive motor, including their ventilation and control circuits, for each passenger ropeway or passenger conveyor must not contain a provision to automatically close the disconnecting means, and must be

  • a single disconnect which also disconnects power to the driving machine brake(s) control circuit directly or through an auxiliary contact that is positively opened mechanically (the opening not being solely dependent on springs)
  • an externally operated fusible switch or a circuit breaker, capable of being locked in the open position, and clearly labelled describing the connected load
  • readily accessible to authorized persons and located where it is visible on entry to the control room or machinery area
  • provided with a sign to identify the location of the supply side overcurrent protective device
  • a single disconnect for motors and control circuits of multiple driving machines or motors connected to a single passenger ropeway or passenger conveyor

Rule 58-304 provides that disconnecting means for utilization equipment must be

  • a single disconnect for all ungrounded conductors
  • capable of being locked in the open position and located in the machine room, control room, machine space, or control space
  • provided with a sign to identify the location of the supply side overcurrent protective device

Rule 58-306 requires that overcurrent protection be coordinated with any upstream overcurrent protective devices.

Rule 58-308 requires that every 125 V, single-phase receptacle installed in machine rooms, control rooms, machine spaces, control spaces, and counterweight enclosures be protected with a Class A type ground fault circuit interrupter.

Rule 58-310 specifies that motor controllers be rated to comply with Rule 28-500(1) except where the controller limits the available power and is labelled “power limited”. 

Branch circuits

Rule 58-400 requires that each machine room, control room, machinery space, and control space must have

  • luminaires, not supplied from the load side of the ground fault circuit interrupters required by Rule 58-308, and controlled by lighting switches within easy reach of the point of entry
  • a 125 V, single-phase, duplex receptacle, having a configuration in accordance with Diagram 1
  • a separate branch circuit for the supply of luminaires and receptacles

Rule 58-402 requires that where counterweights are installed in a building or room, luminaires, not supplied from the load side of the ground fault circuit interrupters required by Rule 58-308, must be provided and a separate branch circuit must supply lighting and receptacles.

Rule 58-404 specifies that utilization equipment other than that identified in rules 58-400 and 58-402, must be supplied by a separate branch circuit with overcurrent devices located in the machinery room, control room, machinery space or control space.

Regenerative power

Rule 58-500 requires that means must be provided to absorb regenerative power that cannot be absorbed under overhauling load or braking conditions.

In the next installment, we will be discussing Section 60 — Electrical Communications Systems.

The source for this series of articles is the Canadian Electrical Code, Part I, published by CSA. Note the CEC Handbook is also published by CSA.

William (Bill) Burr is the former Chair of the Canadian Advisory Council on Electrical Safety (CACES), former Director of Electrical and Elevator Safety for the Province of BC, and former Director of Electrical and Gas Standards Development and former Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting; billburr@gmail.com

 

Nexans Webinar - Key 2021 Electrical Code Changes Impacting Wire and Cable

Nexans Free WebinarJoin NEXANS for a free webinar with Isaac Müller, Applications Engineer for Nexans as he reviews and discusses the changes to the 2021 Canadian Electrical Code related to wire and cable. This free webinar will take place Wed, Jan 27, 2021 2:00 PM - 3:00 PM EST

This webinar includes:
- Updated rules to protect cables (12-514,12-516)
- New conditions of use for wire & cable (Table 19)
- An opportunity to ask your questions

Click here to register today. 


 

Changing Scene

  • Prev
Organizers behind the MEET (Mechanical Electrical Electronic Technology) Show have announced its ...
Be sure not to miss your opportunity to participate at EDIST 2021 The Power of Resiliency, January ...
Teledyne Technologies Incorporated and FLIR Systems, Inc.jointly announced that they have entered ...
In today's ever changing Canadian work environment, an organization that wants to succeed at ...
B.C.’s building-sector businesses can tap into an additional $8 million for projects to ...
Rittal Systems Ltd., Canada would like to announce that Tim Rourke will be resigning as President, ...
In a fast-changing world, it can be hard to keep up with the latest developments in technology and ...
This recall involves Southwire branded coiled, pre-cut red electrical wire sold in shrink wrap ...
Jennifer Green, Director of Competitions and Young Women’s Initiatives at Skills Ontario, has been ...


With close to 400 exhibitors and more than 6,000 attendees from throughout Canada and the United States, MEET is the second-largest industry event of its type in Canada, and the largest trade event east of Montreal. Given the size and nature of the show and the travel that comes along with it, the COVID-19 pandemic has forced the rescheduling of the event several times.

Read More

 


Canadian Electrical Contractor Discussion Group

CECD Zac recetacleOne CECD group memeber recently posed a quick code question regarding some new arc fault requirements and powering a hallway receptical with a bedroom receptical. 

Go HERE to join the discussion

 

 

 

 

 

 

 



The Beard and the Respiratory Protection MaskHalf-masks and full-facepiece respirators require an optimal seal to guarantee their effectiveness, and the beard can impede it considerably.

DID YOU KNOW THAT A BEARD’S REGROWTH AS LITTLE AS ONE DAY OLD CAN AFFECT THE MASK’S SEAL IN PLACE?

What does it mean exactly?

Since many masks have been tested on different face types, the results of these tests vary considerably. However, it should be noted that in 100% of cases, after 7 days without shaving, the respiratory protection masks showed a leak of more than 1%. This means that the air inside the mask contained more than 1% of unwanted particles!

Read More


 

Product News

  • Prev
Providing high quality illumination, LytePro’s low profile design complements and blends in with ...
The 6590 Gaslight I is a large scale Victorian authentically detailed fixture which consists of a ...
The WaveLinx industrial high bay and low bay sensors offer passive infrared (PIR) occupancy with a ...
The Swidget Motion Sensor Insert* uses infrared radiation to detect whether someone or something ...
Standard extruded inside and outside corner LED tape mud-in channels. Aluminum construction. ...
Traditional style, cost-effective, DLC-listed wall pack offered in 42, 80, and 120 watts. The ...
Lumenwerx is pleased to launch the Via Weather Series, a new subgrouping composed of ...
SATCO continues to expand its wall pack selection with options that make installation flexible and ...
Milwaukee Tool has added to its lineup of hand tool solutions ...
The Littelfuse LS6 (available in 1000 and 500 V) and the LS6R (available in 1500 V) series are ...

 

Signify LytePro LED Wall Pack Gen 3Providing high quality illumination, LytePro’s low profile design complements and blends in with its surroundings. Available in 3 sizes, LytePro offers two optical distributions, multiple lumen packages, and is suitable for a range of mounting heights.

Lumen output ranges from 1,000 to 9,600 with efficacies up to 114 LPW, and all models are DLC qualified. The LPW32 even features button photocell, motion response, battery pack, and field adjustable wattage options.

Read More

 

 


 

SATCO CCT Selectable Wall PacksSATCO continues to expand its wall pack selection with options that make installation flexible and stock versatile. The latest additions in the line include the CCT Selectable Small Wall Pack and the CCT Selectable Compact Round Wall Pack.

 
The Small Wall Pack is perfect for light commercial uses such a smaller storage units and municipal lighting, as well as commercial Main Street buildings. As with all of the fixtures in this exterior family, these wall packs offer advanced features, are built durable and are able to withstand harsh, all-weather conditions.

 

Read More


 

 

Peers & Profiles

  • Prev
Trilliant, an international provider of utility solutions for advanced metering and smart grid ...
For more than a century, ABB has been investing in Canadian technologies and products to support ...
Mackenzie Gillan, a bright young lady from Baysville, Ontario, tells us about how she learned ...
Energy Efficient Lighting is a LED lighting manufacturer with nearly 30 years of industry ...
Dee Durant is an industrial electrician apprentice attending Conestoga College and an Ambassador ...
ECAO recently launched a new program called Future Leaders Advisory Council (FLAC). Their inaugural ...
At 14, Tom Miguel was sitting in the counselor’s office of Silverthorn Collegiate Institute in ...
Meredith Halfpenny is a Wind Site Technician with Boralex where she inspects, maintains, and ...
Rutul Bhavsar is a final year Electrical Engineering student at Mohawk College. He recently ...
Shannon Tymosko is a first-year apprentice with IBEW (International Brotherhood of Electrical ...


Libra Smart MeterBy Blake Marchand

Trilliant, an international provider of utility solutions for advanced metering and smart grid systems, recently announced a custom-made product for the North American market with the release of its Trilliant Libra Series Edge-Ready Smart Electric Meter.


The meter’s technology will allow utilities to enter the connectivity sphere by providing peer-to-peer data acquisition and analytics, while enabling new energy management features that benefit both customer and utility. 

 

Read More


 

Copper $US Dollar price per pound

Kerrwil Publications Great Place to Work. Certified December 2019 - December 2020

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2021 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil