William (Bill) BurrBy William (Bill) Burr

Rule 28-000 - Scope states that Section 28 - Motors and Generators is a supplementary or amendatory section of the code and provides additional and specific requirements for the installation, wiring methods, conductors, protection, and control of all motors and generators. Appendix B contains important additional helpful notes, and the CEC Handbook contains helpful information on determining conductor sizes and protection ratings.

General

This section is divided into several parts, with rules 28-010 to 28-016 applying to all motors and generators, and additional parts that deal with specific installation, protection, control and particular motor applications and generators.

Rule 28-010 - Special terminology has definitions for terms specifically used in this section:

Locked rotor current rating — usually marked on the equipment or deemed equal to 6 times full load current or as per Table 44 or 45.

Non-continuous duty motor — a motor having characteristics or ratings described as Short-time duty, Intermittent duty, Periodic duty, and Varying duty.

Rated load current — marked on a hermetic motor compressor to ascertain wiring, protection, and control for the unit.

Refrigerant motor-compressor — an appliance consisting of a refrigerant gas compressing section and a motor that may include a terminal box, cover, and other electrical components such as starting and overload components, heaters, fans, or electronic controls.

Refrigerant motor-compressor, hermetic — a refrigerant motor-compressor in which the refrigerant gas compressing section and motor are enclosed in the same housing.

Refrigerant motor-compressor, semi-hermetic – a refrigerant motor-compressor in which the refrigerant gas compressing section and motor are each enclosed in separate housings.

Service

Continuous duty service — application where the motor can operate continuously with load.

Non-continuous duty service — a motor with short-time, intermittent, periodic or varying duty as per Section 0 definitions.

Service factor — a multiplier applied to the rated horsepower of a motor or generator indicating the permissible continuous loading at rated voltage and frequency.

Rule 28-012 provides for the guarding of live parts of motors and controllers and conditions where live parts may be exposed.

Rule 28-014 describes methods of guarding motors having exposed live parts.

Rule 28-016 outlines ventilation methods to prevent overheating of motors, including using suitable enclosed motors in dust or flyings situations where ventilation is not possible.

Wiring methods


Rule 28-100 and Rule 28-102 state that all wiring methods for stationary motors follow the requirements of Section 12 or Section 36, and that portable motors may be wired with a minimum type S flexible cord.

Rule 28-104 outlines the use of Table 37 to determine the insulation temperature rating and ampacity of motor supply insulated conductors.

Rules 28-106 to 28-112 outline the use of Table 27 to determine the ampacity rating of insulated conductors supplying individual motors, two or more motors, or feeder and secondary insulated conductors. A chart in Appendix B will help with these calculations.


Overcurrent protection

Rule 28-200 provides the requirements for motor branch circuit overcurrent protection and requires that each ungrounded conductor of a motor branch circuit shall be protected by an overcurrent device in accordance with Subrules (2) to (5), including references to Table 29. In addition, Appendix B and Figure B28-1 contain a diagram of circuits, control, and protective devices for motors which you will find invaluable in determining the requirements for the type and rating of conductors, control, protection, and other elements of motor circuits.

Rule 28-202 requires that, notwithstanding the options in 28-200 above, if the characteristics and ratings of the branch circuit overcurrent protection devices for motor control equipment are marked on the equipment, they shall not be exceeded.

Rule 28-204 specifies the conditions and methods for rating and setting feeder overcurrent protection.

Rule 28-206 permits the grouping of motors on a single branch circuit overcurrent device under the conditions outlined in subrules (a) to (f).

Rule 28-208 prohibits the size of fuseholders smaller than the maximum rating in Table 29 except under the conditions outlined in subrules (a) to (c).

Rule 28-210 governs the use, rating, and adjustment of instantaneous-trip circuit breakers for branch circuit protection.

Rule 28-212 permits the use of semiconductor fuses that are integral to an approved controller.

Overload and overheating protection

Rule 28-300 requires that, in addition to overcurrent protection as outlined in the rules above, the branch circuit conductors and control equipment of each motor, except with the conditions under 28-308 below, must have overload protection.

Rule 28-302 outlines the types of overload protection devices or fuses to be used.

Rule 28-304 prescribes the number and location of overload devices required, whether fuses or other devices, as specified in Table 25, are used. The note in Appendix B regarding the location of overload devices for three-phase motor circuits provides additional information.

Rule 28-306 provides that the rating or trip selection of overload devices shall be set for the service factor marked on the motor or 115% of full load current if not marked.

Rule 28-308 allows that overload protection for motors is not required under the conditions outlined in subrules (a) to (c).

Rule 28-310 permits the shunting of overload protection during the starting period of the motor provided that the overcurrent device is maintained throughout and the overload protection is restored to the circuit after the starting period.

Rule 28-312 prohibits automatic restarting of a motor after an overload shutdown to prevent injury to persons.

Rules 28-314 to 28-318 provides that overheating protection is required for each motor, the types of overheating protection required, and conditions where overheating protection is not required.

Undervoltage protection

Rule 28-400 states that undervoltage protection is required for motors to prevent hazards on restart either by low-voltage protection or low-voltage release depending on conditions outlined in Subrules (a) or (b).

Control

Rule 28-500 specifies that a motor starter or controller is required with a horsepower rating not less than that of the motor and need not be the disconnecting means of the motor. Subrule (3) provides exemptions to this rule for specified applications.

Rule 28-502 requires the motor control to be in a location suitable to prevent accidents due to contact of persons with live or moving parts, or to allow the machine to be stopped in an emergency.

Rule 28-504 requires that for starters having different running and starting positions the construction must not allow remaining in the starting position.


Rule 28-506 specifies that no accidental grounded control circuit conductor can cause the motor to start or prevent the stopping of the motor by a safety device.


Disconnecting means

Rule 28-600 requires that each motor branch circuit, starter or controller, and each motor be provided with a separate disconnecting means. A single disconnecting means may serve more than one function or motor grouped on a single branch circuit.

Rules 28-602 and 28-604 provide for the types, ratings, application, and location of disconnecting means depending on the conditions outlined in Subrules 28-604 (1) to (7).


Refrigerant motor-compressors

Rules 28-700 to 28-714 apply to refrigerant motor compressors, including hermetic refrigerant motor-compressors, and semi-hermetic refrigerant motor-compressors, hereafter referred to as motor-compressors, and supplement or amend some of the other rules of this section. There are separate rules for marking, horsepower rated equipment, insulated conductor ampacity, overcurrent protection, overload protection, control equipment, and disconnecting means for motors in this application.

Multi-winding and part winding-start motors

Rule 28-802 states that where the windings are in a permanent connection configuration, the motor is treated as a single winding motor.

Rules 28-804 to 28-812 provide for selecting the insulated conductor sizes, overcurrent protection, overload protection, control and disconnecting means for multi-winding and part winding-start motors.

Protection and control of generators

Rule 28-900 specifies the configuration and provision of disconnecting means required for generators and all control apparatus and protective devices.

Rule 28-902 outlines the required protection for constant-voltage generators with noted exceptions.

Rule 28-904 requires a generator not driven by electricity supplying a 2-wire grounded system to have a protective device that disconnects both insulated conductors.

Rule 28-906 requires balancer sets to have protective devices to disconnect the system in the case of an excessive unbalanced voltage.

Rule 28-908 provides requirements for circuit breakers and tripping elements on three-wire dc generators.

In the next instalment, we will be discussing Section 30 - Installation of Lighting Equipment.

* The source for this series of articles is the Canadian Electrical Code, Part I, published by CSA.

William (Bill) Burr is the former Chair of the Canadian Advisory Council on Electrical Safety (CACES), former Director of Electrical and Elevator Safety for the Province of BC, and former Director of Electrical and Gas Standards Development and former Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting billburr@gmail.com.


Salex Announces Promotion of Paul Manson to GTA Sales Manager     

Paul MansonJanuary 26, 2021 – Salex, a facilitator of commercial lighting installations and control systems for Canada’s architectural lighting community, is excited to announce the promotion of Paul Manson to GTA Sales Manager. Paul joined Salex back in 2015, and has over 25 years of invaluable industry experience.

Dedicated to the education and promotion of quality, high-efficiency lighting and controls, Manson’s extensive background in on-site electrical installation, national accounts, relationship building, manufacturers, and sales team management at Philips Lighting, will provide valuable experience to fulfill his new role.

Read More


 

Changing Scene

  • Prev
 EWEL has announced the plan to move its Sherwood Park branch into a brand-new facility at ...
Energy Savings for Business supports local skilled trades, contractors, and suppliers such as HVAC ...
Eaton has signed an agreement to acquire Tripp Lite, a supplier of power quality products and ...
Rexel announced it has acquired the Canadian Utility business of WESCO International (WESCO Canada ...
This questionnaire is designed for people who work in the electrical industry as part of a project ...
Organizers behind the MEET (Mechanical Electrical Electronic Technology) Show have announced its ...
Be sure not to miss your opportunity to participate at EDIST 2021 The Power of Resiliency, January ...
Teledyne Technologies Incorporated and FLIR Systems, Inc.jointly announced that they have entered ...
In today's ever changing Canadian work environment, an organization that wants to succeed at ...
B.C.’s building-sector businesses can tap into an additional $8 million for projects to ...


 

www.liteline.com

 

 

 

 


 

Canadian Electrical Contractor Discussion Group: Can You Count the Deficiencies?

EIN CECD 400Have you ever been called to fix the work of a 'handyman'?

"Was supposedly done by a"certified ' electrician....told the homeowner that he got a $266 permit....no record at TSBC. Can you count the deficiencies?"

"There is a second panel change in the triplex also.......even more deficiencies. Think the guy was a glorified handyman. Ones not obvious: 240 BB heat hooked up 120....drier on 2p20....range on 2p50....water heater fed with 2c14 Bx on 2p15."

Go HERE to join the discussion

 


 

electrical apprentice1 400The Canadian government is making targeted investments, so that key groups facing barriers—like women, newcomers, Indigenous people, persons with disabilities, and Black and racialized Canadians—can better find work in the skilled trades through projects led by unions and their partner organizations.

The investment will be $63.5 million, over five years, for 68 projects as part of the Union Training and Innovation Program (UTIP) 2020 call for proposals. The aim is to help certify skilled tradespeople and prepare them to fill available jobs as the economy restarts. Minister Qualtrough made the announcement during a virtual event hosted by one of the funding recipients, the UA Piping Industry College of British Columbia, in Delta, B.C.

Read More


 



LightingBy Steve Mesh

Are you an electrical contractor? Are you new to the world of Networked Lighting Controls (NLCs)? Are you looking for new opportunities to strengthen your business in these uncertain times?

If you answered yes to all three of these questions, read on. NLCs are a (relatively) new introduction to the lighting industry. I say “relatively” because, in point of fact, some networked control systems have been available for decades. If you haven’t had any prior experience with installing NLCs, then you might think these are fancy and highfalutin. 

Read More


 

CEW EWEL Sherwood 400EWEL has announced the plan to move its Sherwood Park branch into a brand-new facility at #130 3001 Buckingham Drive, Sherwood Park, Alberta. Relocation has proceeded in staged phases since late summer 2020 and will conclude by late February 2021.

The new unit space is approximately 9,500 square feet with a 4,500 square foot yard, which makes it nearly three times larger than the previous location. The expansion stems from EWEL’s steady growth over the last four decades, necessitating space for increased inventory, more comfortable spaces for employees, and for more streamlined warehousing processes.

Read More

 


 

Product News

  • Prev
Champion Strut is a fiberglass non-metallic channel framing system that includes a complete ...
The PowPak 20 A Relay Receptacle Control Module is a radio-frequency (RF), receptacle switching ...
Occupancy sensor turns ON in low light only and when motion is detected. Turns off after 1 minute ...
Innovative Design for Versatile Applications. Easy to lock horizontally into place with a ...
NightFox Pro Series Photocontrols offer protection to typical, enhanced, or extreme electrical ...
The UHB LED is a round high bay luminaire designed for a variety of mounting heights and customer ...
When designing lighting for a space, why not consider a luminaire that can also solve an often ...
MaxLite expands their RCF Series with wattage and CCT selectable models that enable installers to ...
The Lithonia Lighting® TWX LED family has been re-invented from the ground up, delivering ...
LBR is everything you need in a retrofit downlight at an affordable price. Whether it’s the ...

 

Milwaukee 2Milwaukee HOLE DOZER Bi-Metal Hole Saws new 3.5 TPI tooth design offers you longer life in metal applications. The Bi-Metal Hole Saws also feature Lifetime Tooth Break Warranty and can take on all general-purpose applications.

The ALL-ACCESS SLOTS solve the frustration of plug removal, making you more productive with less downtime between holes.

 

 

 

 

Read More


 

SATCO CCT Selectable Wall PacksSATCO continues to expand its wall pack selection with options that make installation flexible and stock versatile. The latest additions in the line include the CCT Selectable Small Wall Pack and the CCT Selectable Compact Round Wall Pack.

 
The Small Wall Pack is perfect for light commercial uses such a smaller storage units and municipal lighting, as well as commercial Main Street buildings. As with all of the fixtures in this exterior family, these wall packs offer advanced features, are built durable and are able to withstand harsh, all-weather conditions.

 

Read More


 

 

Leviton Mini-Meter Power Meters in Indoor EnclosureVerifEye™ 0.5% Mini Meter Kits offer a fully integrated, line-powered wireless Automated Meter Readings (AMR) solution with 0.5% accuracy for multi-tenant applications.

Designed to provide a simple and effective energy monitoring solution, the 0.5% Mini Meter Kits accurately capture measurements of power consumption and meet the rigorous requirements of ANSI C12.20 (0.5) Code for Electricity Metering. The 0.5% Mini Meters offer an all-in-one, low cost bundled solution for tenant billing applications, new construction and retrofits.

 

Read More


 

Peers & Profiles

  • Prev
“It was quite surprising,” said Stephanie Smith of being named EHRC’s Leader of the Year. ...
As an advanced networked lighting controls company serving the industrial and large commercial ...
Trilliant, an international provider of utility solutions for advanced metering and smart grid ...
For more than a century, ABB has been investing in Canadian technologies and products to support ...
Mackenzie Gillan, a bright young lady from Baysville, Ontario, tells us about how she learned ...
Energy Efficient Lighting is a LED lighting manufacturer with nearly 30 years of industry ...
Dee Durant is an industrial electrician apprentice attending Conestoga College and an Ambassador ...
ECAO recently launched a new program called Future Leaders Advisory Council (FLAC). Their inaugural ...
At 14, Tom Miguel was sitting in the counselor’s office of Silverthorn Collegiate Institute in ...
Meredith Halfpenny is a Wind Site Technician with Boralex where she inspects, maintains, and ...


Libra Smart MeterBy Blake Marchand

Trilliant, an international provider of utility solutions for advanced metering and smart grid systems, recently announced a custom-made product for the North American market with the release of its Trilliant Libra Series Edge-Ready Smart Electric Meter.


The meter’s technology will allow utilities to enter the connectivity sphere by providing peer-to-peer data acquisition and analytics, while enabling new energy management features that benefit both customer and utility. 

 

Read More


 

Copper $US Dollar price per pound

Kerrwil Publications Great Place to Work. Certified December 2019 - December 2020

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2021 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil