Canadian Electrical Industry News Week

2015 CE Code ChangesPierre McDonald

There are so many revisions expected in the 2015 Edition of the Canadian Electrical Code (CE Code) that several articles have been required to help disseminate the information. My past articles have covered changes within the Definitions, Section 4, 12 and 18.

This month I’d like to focus on the changes beginning in Section 2 and moving through to Section 10. Specifically, this article will focus on those changes that affect the equipment installed and the way installers do their work.

Section 2
Rule 2-024 has always mandated that electrical equipment be approved. A certain amount of confusion existed with equipment located on the load side of overcurrent protection, transformers or current-limiting devices for Class 2 circuits. Does this equipment need to be approved or just be acceptable for the particular application? A new Subrule 2 to Rule 2-024 should clear up any confusion as it will specify that equipment described in Rule 16-222(1)(a) shall not be required to be approved. Of course, the authority having jurisdiction (AHJ) has the final say as to what equipment is approved or not.

A new rule will also appear in Section 2 regarding field installed warning and caution markings. Whenever the code requires field markings, they shall be written in the language or languages mandated by the AHJ adopting and enforcing the code. This would mean the labeling requirements of 2-306, Shock and arc flash protection, or 36-006, Warning notices, will be required to be in the languages mandated by the AHJ. This could include one or both of the official languages of Canada or even the four languages used in the Nunavut Territory depending on the jurisdiction where the installation occurs.

Another new rule destined for Section 2 will provide clarification with respect to electrical equipment ratings. Subrule 1 of this new rule provides for a safe installation by mandating electrical equipment marked with a short circuit current rating or with a withstand current rating meet the voltage and fault current available at the point of installation. Subrule 2 will require equipment marked with both the line-to-line voltage and the line-to-ground voltage to be connected only to circuits that are solidly grounded. Examples of these markings include 125/250V, 120/240V, 208Y/120V, 480Y/277V or 600Y/347V.

Rule 2-324 has been revised to stipulate the clearance between a combustible gas relief discharge device or vent and a source of ignition to be stipulated in CSA B149.1-10 Natural Gas and Propane Installation Code. This change will ensure that correlation now exists between the two codes. An Appendix B note to this rule will indicate that this clearance must be a minimum of 1m for natural gas and 3m for propane gas.

Section 6
Two changes are expected to the rules of Section 6. In Rule 6-114, the term “rain-tight” will be replaced with “suitable for use in wet location.” This change better aligns with recent changes to the product standard for Conduit, Tubing and Cable fittings, C22.2 No. 18.3. This change will also take place in Section 12.

Rule 6-402(2) is being revised to allow for supply service to be as high as 320A without current transformers provided the metre mounting device is equipped with by-pass means. These bypass-means associated with the 320A meter base allow for insertion and removal of the meter with no implications of an arc flash. This new requirement is especially good news for those installations with large heating and other loads where the alternative was always to install a transformer rated service.

Section 10
A number of rules have been changed in Section 10, with several of them now accepting “other than copper” as a bonding or grounding conductor depending on the rule which applies. “Other than copper” conductors include aluminum or a conductor resistant to any corrosive condition existing at the installation site or a conductor protected against corrosion. This change appears in Rules 10-402, 10-406, 10-626, 10-702, 10-802, 10-806, 10-812, 10-1000 and 10-1108.

Rule 10-106 has a Subrule 3 added which echoes the Appendix B note presently in the 2012 edition CE Code. This change effectively takes the information item from the appendix and creates a mandatory requirement by placing it in the rules.

Rule 10-208, Grounding connections for two or more buildings or structures supplied from a single service, has been changed to mandate that buildings housing livestock and supplied from distribution equipment must have non-current carrying metal parts of the electrical equipment bonded to ground with the bonding conductor run with feeder or branch circuit conductors supplying that building. In past editions of the CE Codes, the installer had the choice to use the bonding conductor of the feeder or establish a new ground with grounding electrodes and bonding the feeder neutral to ground. This practice will no longer be allowed, resulting in a reduction of stray voltages in buildings housing livestock.

A new Subrule 5 has been added to Rule 10-618, which requires a separate bonding conductor to bond fixed equipment to ground when single conductors are used and the metallic sheath has been isolated at one end in conformance with rule 4-010.

Rule 10-902 has been revised to simply require that the grounding conductor be attached to the electrode at a point that will ensure a permanent ground. If the electrode is a metallic water pipe in-situ type, then this connection must be as close as practical to the point where the pipe enters the building. In either case, where it is practical, this point of attachment should be accessible. As Rule 10-904 requirements have been rolled into the changes with Rule 10-902, Rule 10-904 will be deleted.

In Rule 10-906, the words “bonding connection” have been replaced with “bonding conductor.” This simple change now allows, in non-metallic wiring systems, one bonding conductor to be connected to the bonding screw at the back of a box, and then all bonding conductors entering the box can be twisted together under a wire nut. Prior to this change, all bonding conductors entering the box were required to be connected to individual bonding screws at the back of a box.

Finally, several rules within Section 10 have also been adjusted by deleting the term “mechanical injury” and replacing it with the term “mechanical damage.” This change fortifies the correct terminology in that equipment cannot be injured but it can be damaged.

The changes cited here are but a few of the many coming to the 2015 edition CE Code. While some are editorial, most will affect electrical installations in some way or another. Keep in mind that these changes only come in to effect once the particular AHJ has adopted this 2015 edition CE Code.


Pierre McDonald, CET, is Senior Regulatory Affairs Representative/Répresentant Principal, Affaires Réglementaires, Underwriters Laboratories of Canada Inc. Based in St. Albert, AB, Pierre has been a member of the Canadian Electrical Code Part 1 technical committee as well as several subcommittees including serving as Chair of Sections 6 and 76 and as a member representing regulators on several other CSA committees. Pierre is still active with code development and interpretation.

Changing Scene

  • Prev
In his new role as Stelpro's Vice-President, Sales and Business Development, ...
The Support Equity and Under-Represented Groups project will address the under-representation of ...
Show your support by sharing a photo or experience of how a lineworker has made an impact in your ...
Eleven highly accomplished Hamiltonians are being honoured by Mohawk College as Distinguished ...
Canada’s Minister of Natural Resources recently announced the Governor in Council has ...
ABB recently won an order of eBus charging solutions to support TTC as it modernizes its service ...
A consortium of Canadian energy organizations has been shortlisted to develop the electricity ...
Skills Ontario Summer Camp is a week-long day program for kids entering Grades 7-9.   ...
  Glen Dimplex Americas is proud to announce that its Vancouver facility was recently ...
May 13 to 19 is Powerline Safety Week in Ontario, which is meant to inform people across the ...

Electrician Forum Brought to you by Schneider Electric

As industry experts you know the products you use everyday better than anyone and should have input on what information you receive about products and what could improve them.

Therefore, we want your insight on the biggest challenges or issues you face when installing loadcentres, breakers (CAFI, GFI's…) and other surge protection devices. We ask that you do not provide product specific details but rather your general issues and concerns or any questions that have come to mind while working with these product types. Provide us with your valued expert insight into the issues you have faced so manufacturers can better inform you about the installation and use of these products. Lets generate some discussion that will help guide the Industry.

Make your comments  HERE

 

ABB TXploreOn May 30, 2019, ABB was honoured with an Electrical Review Excellence award for its ABB Ability inspection for transformers – TXplore -- in the ‘Power Product of the Year’ category. Electrical Review is the leading electrical industry publication in the UK.

The judging panel, under the leadership of the highly-respected industry figure – Prof. Ian F. Bitterlin, Consulting Engineer and Visiting Professor at University of Leeds, was impressed by the capability of TXplore to make transformer inspection a much safer activity while also boosting asset availability for power grid operators.

 

Read More

 

 

 

Codes and Regulations Brought to You by the CSA Group

  • Prev
The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the ...
The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the ...
In this article: Tables — Part B. This section of the Code contains 99 tables of essential ...
In this article: Section 58 — Passenger Ropeways and Similar Equipment. Rule 58-000 ...
  Unauthorized CSA Group certification marks have been found on wiring by Triumph Cable ...
In this article: Section 52 — Diagnostic imaging installations. The CE code is a ...
In this article: Section 46 — Emergency Power Supply, Unit Equipment, Exit Signs, and ...
  In this article: Section 44 — Theatre Installations. The CE Code is a ...
CSA has published C22.2 No. 60947-7-3, the harmonized standard for low-voltage switchgear and ...
  Electric welders. The CE Code is a comprehensive document. Sometimes it can seem ...

 

Lighting ProjectLocated at one of the busiest retail intersections in Montreal’s downtown core, 1411 Crescent is a beautiful art deco structure built in 1934. Four floors of offices sit above retail space on the northeast corner of Ste-Catherine Street. BTB Real Estate Investment Trust purchased the building in 2018 and with its own team growing, chose to move its company headquarters to the new space. They appreciated the charm of the building, and its ideal location in the Golden Square Mile.

To signify this important move, BTB REIT sought to enhance the building’s façade to make it more impactful on this vital city block.

 

Read More 

 

ABBTechFor decades, ABB has made intricate scientific instruments that measure and analyze gases in the atmosphere to help scientists better understand its composition and evolution. Now, ABB is helping to more accurately measure greenhouse gases (GHGs), which are trapping heat in the atmosphere, resulting in an increase in global surface temperature.

One such instrument is an ABB interferometer carried aboard the Greenhouse Gases Observing Satellite-2 (GOSAT-2), which was launched in October 2018 as part of a Japanese government project. 

Read More

 

 

Tools for the Trade

  • Prev
  IDEAL Industries has introduced Combination Drill Taps to its tool lineup. Combining the ...
  Stripping and crimping device, 100 - 240 V input voltage, for insulated ferrules with a ...
Professional all-in-one cutter/stripper for coaxial and twisted pair cables     ...
  Klein Tools' Coax Explorrer 2 tests coaxial cable and maps up to 4 locations   ...
  Ideal Industries' T-14 wire stripper s are ideal for all professionals working within the ...
  The ATS850 conveyor eliminates all types of electro static discharge requirements. ...
  Lorik Tool & Automation has the experience and ability to manufacture a variety of ...
  Ideal Industries' 26 piece insulated Journeyman kit is ideal for new electricians or for ...
  Klein Tools Deluxe Fish Rod Set comes in 19 pieces that when assembled can fish wire and ...
  BendWorks Software was designed to help electrical contractors adopt this new process ...

Product News

  • Prev
Single Phase Power Solutions introduces the 30 HP Belle Single-Phase Motor™ which uses ...
Emerson expands the innovative Greenlee Shear 30T with seven new die sets and a new bare kit ...
ASCO Power Technologies offers its Model 420 surge protective device for point-of -use ...
The new VALVETRAB MS Type 1+2 combined lightning current and surge arresters have a 3+V circuit. ...
A truly smart home does more than just connect you; it works for you. With iDevices' advanced smart ...
Previously available from one of the world’s largest line pulling companies, the PLCS is now ...
Fluke has revamped its entire line of industrial thermal cameras with more premium features packed ...
Emerson has improved AMS Machinery Manager predictive maintenance and analysis software ...
AEMC’s ten New Simple Logger® Data Loggers are small one channel recording devices ...
ASCO Power Technologies, a provider of critical power solutions, releases the third generation of ...

 

Banner VE Smart CameraFeatures included in the latest version of Vision Manager software simplify the integration of VE Series smart cameras into vision guided robotic (VGR) systems and make it easy to correct distortions caused by camera perspective. Also new to the software is the ability to view application images remotely via a built-in webserver. Vision Manager version 1.7.0 is available now for free download.

EASY INTEGRATION WITH VISION GUIDED ROBOTS

All the logic required to integrate a VE Series smart camera into a VGR system is in the software. 

Read More

 

 

Peers & Profiles

  • Prev
Bill Maki is an Electrical Engineer from Thunder Bay, Ontario working as a Control Systems ...
Benedict Electrical Contracting Limited is a locally owned and operated family business in Owen ...
Spark Power Corp. is one of North America’s leading independent providers of integrated ...
Marcia Ranger is a master construction and maintenance electrician, as well as a college professor ...
Con’s Electric Company Limited was established in 1985. Based in Timmins Ontario, only 700 ...
Mark Unsworth is an electrical engineer with over 35 years of experience in project management, ...
Manygo Ho is an electrical designer with AECOM’s Buildings and Places group. Manygo designs ...
Don Neigel is Manager of the CSA-certified panel shop at Delta, BC’s Optimil Machinery. ...
New Brunswick Power recently struck a deal with Joi Scientific to develop an innovative technology ...
The Shock Doctors is an electrical contracting company operating out of Orillia, Barrie and ...

Copper $US Dollar price per pound

Kerrwil Publications

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2019 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil