Canadian Electrical Industry News Week

April 12, 2022

EIN EFC ESA Code 400By Blake Marchand

On March 30th, the EFC (Electro-Federation Canada) in collaboration with Ontario’s ESA (Electrical Safety Authority) presented on the top changes to the Ontario Electrical Code with the upcoming adoption of the 2021 Canadian Electrical Code. The presentation was hosted by EFC Ontario Region Chair John Hadley and presented by Ray Yousef of ESA.

In total there were 330 closed subjects, 217 approved revisions and 9 approved interpretations. Yousef’s top three changes included a new section for farm buildings housing livestock, Rules 22-800s; a new section for energy storage systems, Rules 64-900s; and an amendment to GFCI requirement for outdoor receptacles, Rule 26-704.

The change for Farm Buildings Housing Livestock is a new subjection of section 22. As mentioned, it is listed under 22-800.

All buildings housing livestock are determined to be Category 1 (wet location) and 2 (corrosive environment) unless deviation is granted. All connections need to be corrosion resistant, Type 4X plug set. And all electrical equipment must be suitable for the location, except specialty type equipment and ventilation fans.

The recommendation came from a specific working group that included regulators, manufacturers, insurance companies, farmers, farming associations, “it was a really well-rounded working group that came up with that proposal,” Yousef noted. ESA’s Nancy Hannah served the chair of the working group.

“The main motivation to start this working group is a letter we received from Ontario Office of the Fire Marshal,” the letter consisted of incidents collected between the years of 2009 to 2017 and it shows more than 2100 incidents in barns, “Most of them were, I would say, 35% of them were barns housing animals.”

“The main change we will see in that subsection is that now all buildings housing livestock are determined to be Category 1, which is wet location, and Category 2, which is corrosive environment. Electrical need to be installed there based on that categorization, and all connection to be corrosion resistant Type 4X.”

Yousef added that, “This is major, and we believe it will enhance safety in these buildings and we’ll hopefully see a reduced number of incidents in these buildings based on the better, more robust, and more suitable electrical equipment.

The 2021 edition of the electrical code requires all 15A and 20A receptacles, within 2.5 meters of finished grade, to be protected by Class A type GCFI, listed under Rule 26-704. Additionally, vehicle heater receptacles are no longer excluded from GFCI requirements. Previously this rule only applied to residential areas, now it applies to all areas.

This change was an important one for Yousef, “this is a great improvement to safety, because it doesn’t matter where this outlet is installed outdoors, a residence or a commercial building or a parking lot, anywhere, it’s the same hazard, it’s the same exposure for anyone plugging in equipment, it doesn’t matter what the occupancy is, so in my opinion this is overdue and very good change for safety.”

Energy Storage Systems, Rules 64-900 is a new section added to the 2021 code outlining requirements for disconnecting means, including disconnecting means for self-contained ESS (Energy Storage Systems). It also includes requirements for where ESSs can be located and separated from structure and equipment.

“We have seen this coming over and over again. In Ontario and all over Canada see involvement of energy storage systems every single day – with new products, with new technologies.”

“In Ontario 2018 code, we had an Ontario amendment of Rule 64-900s, that gave some direction on installation of energy storage systems. The technical subcommittee for Section 64 in CE code took that as a seed and formed a very intensive working group,” noted Yousef, to expand on the direction provided in 2018 Ontario amendment.

“The new sub-section in CE Code 2021 addresses a lot of things: disconnection means, overcurrent protection, and battery installation.” Yousef noted that they moved battery installation from Section 26 to Section 64 but there weren’t major changes to the requirements around battery installation.

“One of the major things that section in the CE Code has is Rule 64-918, which is location of energy storage systems. It’s good to have rules, but this time it may not have 100% hit the nail on the head.”

Yousef said they heard a lot of questions and concerns surrounding the rule since the 2021 Code was published in January.

“Basically, the way it’s written right now, literally, word to word, it will prevent installing ESS in dwelling units, period. The reason for that is the marking requirement. Because it says any ESS installed in dwelling should be marked for residential use, while we have no equipment on the market now with that marking.”

“There are other things around location, it can no longer be below grade, so no more basements. It has to be away from certain doors, so even in garages its questionable. The way this rule is currently written, it’s very hard for these systems to be installed. In Ontario, we have listened to all that.”

Yousef said they reformed the sub-committee for Section 64 based on what they heard from the industry to work out the issues for the 2024 CE Code.

“ESA had been involved a lot in this working group to correct this set of rules and specifically Rule 64-918. I would say the proposal that’s written now to be presented for Part 1, 2024 is way better and improved from what we have currently in 2021 CE Code.”

“In Ontario we are issuing Bulletin 64-8, this will be coming very soon, in May 2022 when the OCS (Ontario Safety Code) will be in force May 5th, 2022.”

Yousef added that the bulletin will mainly be to address energy storage systems in residential areas.

“We believe that it’s in line with the proposal for 2024 CE Code, and we believe it will provide a lot of relief and a lot of realistic approach to installing ESS in dwelling units.”

Rule 2-318 is a new rule for receptacles for mobile structures connected to transfer equipment.

The rule says that at least one receptacle shall be available for portable equipment: chargers, tools, lighting, and similar uses when the mobile industrial or commercial structure is supported from the automatic power supply through the transfer equipment.

This rule is based off a recommendation from the coroner’s report where there was an unfortunate fatality.

Table 39 has been deleted from the CE Code but is included in the Ontario version to provide relaxation on service and feeder size for single dwellings.

Here Yousef provided a little background on how the ESA processes changes included in the CE Code, “when we receive a list of changes for the CE Code, we go through an intensive exercise called ‘Impact Assessment’. In this Impact Assessment we go through every single change, we categorize them substantive or non-substantive.”

“In the substantive ones we categorize them in terms of impact on safety and economic. We would like to see the all the changes either neutral on safety or positive on safety. For the economics, if its neutral on safety, I would like to see it neutral on impact as well, or not increasing cost. For the ones that have a positive impact on safety, I might see some increase in cost, but it will be weighted by the increase in safety.”

For this change, Yousef said referring to Table 39, “when we read the proposal, we found the rationale is not providing any evidence that the service or feeder conductors required by Table 39 – which used to be standard practice for a long time – are overloaded or present any safety or fire hazard.”

“With deleting Table 39, basically, we would be enforcing Table 2 and 4, which we know is a higher sized and sometimes, it’s not available on the market and it’s an increase in cost to construction residential or construction industrial,” said Yousef.

After careful review, as Yousef explained, Ontario re-instated Table 39 in the Ontario code, with a few changes.

One of the major changes is that the marking on the panels used to be associated with the reduced sizes, “this is what we heard from the industry over and over again: these markings sometimes cause us grief with clients and homeowners, ‘how come you’re marking my panel 81 amps when I have 100 amp service?’”

Yousef said they dropped the marking because they know they have a good buffer, even when using Tables 2 and 4. “This is a good change, we’re maintaining the reduced sizes for dwelling units in Ontario and I believe this is a positive change for the people of Ontario, saving them money by keeping the current practice.”

Rule 2-032 3) for electrical equipment exposed to ingress of water is a new sub rule added to require electrical equipment that has been exposed to ingress of water to be subjected to evaluation, to ascertain whether the equipment may be put back into service.

The Authority Having Jurisdiction needs to establish criteria on how to properly valuate damaged equipment.

Yousef noted equipment can become contaminated with chemicals or oil etc. and can cause a fire or shock hazard.

Several new rules have been added surrounding electrical installations in flood hazard zones:

Rule 6-206 1) c) vi), service box shall not be located in areas below the flood elevation.

New Rule 26-562 requires ranch circuit located below grade level in areas designated as flood zone to be provided with ground fault protection.

New Rule 26-712, requires, for buildings in flood zone, sub-pump receptacles to be located above the flood elevation or be marked as suitable for submersion.

New Rule 12-022 for cables in roof decking systems.

“All these rules make a lot of sense, the challenge we had as an Authority Having Jurisdiction, as a regulator, we need to establish a process on how to identify flood hazard zones and the flood elevations in Ontario or in Canada. We are working diligently with the government, keeping our eye on anything that will come up as a tool for us,” Yousef explained, so they can efficiently determine where flood zone areas are. “Without this identification it’s very hard for us, as a regulator, to enforce it.”

Yousef said that it’s in the code, but until they have maps or tools to determine where flood zones are it will be “on the shelf.”

Rule 12-022, cables or raceway systems shall not be installed in locations concealed within a roof decking system – this change was already in the OESC 2018.

Notwithstanding Subrule 1) the following circuits shall be permitted:

  1. Class 2 circuits in which the open-circuit voltage does not exceed 30V.
  2. Embedded trace heat. 3) A warning label is required.

There is not specification in the code where the warning label should be.

This came from incidents where people cut into a roof decking system and hit a conductor, with no indication for them to see or know the conductor was there. Yousef noted the rule is not retroactive.

New Rule 64-1124) for control as an option to limit the input and output current of the interconnected systems. The sum of the ampere rating of the overcurrent devices is permitted to exceed the rating of the busbar or conductor where means are provided to limit the input and output current of the interconnected systems to ensure the busbar or conductor cannot be overloaded based on the total current loading (input and output current of the interconnected systems).

This rule is for when renewable energy systems interconnect to an existing distribution. It amends the rule that the busbar rating should not be exceeded by 120% for non-residential and 125% for residential.

“However, there should be means to monitor the ampere rating on any bus so it can loadshed or disconnect that interconnected system if there is any potential overload on that busbar. It’s recognizing new methodology of monitoring and control of individual sources that can prevent the feeder or busbars from being overloaded while making efficient use of the interconnected system to the maximum.”

Rule 86-304 3) is added to permit a single disconnecting means to control two or more electrical vehicle supply equipment (EVSE) assemblies, supplied by the same branch circuit.

The existing requirements are amended – requiring a separate disconnecting means for each EVSE rated more than 60 A (excluding 60 A – and to remove requirement for a disconnecting means to be within sight and accessible to EVES but be lockable.

This change was submitted by ESA, it has been permitted in Ontario by Bulletin 86-1 since October 2019. “This represents a cost saving for the industry by reducing the number of disconnecting means required for multiple chargers,” noted Yousef.

Rule 26-656 b) is a new rule for interconnection of smoke alarms in an additional dwelling unit created by subdivision of dwelling units. This rule is a result of the current housing market in Ontario. People are investing in housing and splitting them into multiple units. The rule has been part of the Ontario code for 3 years but now it is in the CE Code.

When an additional dwelling unit is created by subdivision of a dwelling unit, the smoke alarms and carbon monoxide alarms are permitted to be installed in the additional dwelling unit and connected to a branch circuit installed in the original dwelling unit, as required by Rule 32-200.

Marking is required at the panelboard to indicated that it supplies smoke alarms and carbon monoxide alarms installed in the additional dwelling unit.

Marking is required at the panelboard in the additional dwelling unit to indicate that the breaker for the respective smoke and carbon monoxide alarm circuit is in the original dwelling unit.

In addition, new Subrule c), a single panelboard is permitted to be installed in a common area to supply smoke alarms and carbon monoxide alarms in both units.

Control for trace heater sets and heating panel sets in adjacent rooms, Rule 62-202 2).

New Subrule 2) is added to permit trace heater sets and heating panel sets, to extend into adjacent rooms and be controlled by a single temperature control device.

This is another rule that originated in Ontario, ESA has an existing bulletin regulating it.

Rules 30-500 to 30-510 for luminaires and control in residential occupancy have been deleted. The change reduces administrative burden. When permitted by NBCC or OBC, wireless switches and other innovation and systems could be used that were not supported by Rules 30-500 to 30-510.

Deleted:

  • 30-500 Lighting equipment at entrances
  • 30-502 Luminaires in dwelling units
  • 30-504 Stairways
  • 30-506 Basements
  • 30-508 Storage rooms
  • 30-510 Garages or carports

Protection of cables in non-concealed locations, Rule 12-514 has been amended.

It includes dimensions for running boards and guard strips and requires them to project at least 12mm beyond the cable.

The rule clarifies protection requirement for all exposed ceiling joists, rather than being only applicable to basement joists.

It is harmonized with Rule 12-518 by clarifying that cables are required to be protected from mechanical damage where they are less than 1.5 m above the floor.

Title: Ready, Set, Scale: How to Grow Your Field Service Business

SimProThrough many trials and tribulations, you’ve grown your business to where it is today. It’s taken blood, sweat, tears, long hours and sacrifice. But, it’s all been worth it to have something which you can call your own. It’s even more worth it when you can finally take that next step to grow your business even further and expand your service, project and maintenance work.

That moment when your hard work has finally paid off and you’re able to take your field service business to the next level. But, then it hits you - you’re not sure how to take those next steps or what you might need to make sure you don’t fail.

Read More


 

Become a Wiser Approved Installer

Schneider

Get access to exclusive benefits, product discounts and resources that will help you drive more business, and lower energy bills for your clients.

 

 

 

 

 

 

 

 

Read More


 

Switch to Smart, Switch to Easy, Switch to Beautiful

Schneider Connected LivingScrewless wall plates. Smart Outlets. Square D™ Switches and Receptacles are raising the bar on aesthetics, ease of installation, remote lighting control and connectivity.

 

 

 

 

 

 

 

Read More


 

Liteline Continues Canadian Investment

EIN BC Liteline 400Adding continued investment in Canada to its core foundation of innovative Design, installation efficiency, and personal customer service, Liteline has just announced the opening of its 12,729 square foot Showroom and Lighting Distribution Center in Langley BC.

The new Liteline Facility is located at 26550 Gloucester Way, Unit A110 and will house the new Liteline Distribution Center along with a product showroom. Stocking our 2-day QuickShip items, this new facility will service B.C. to Saskatchewan, as well as the Pacific Northwest and California in the United States allowing product to be delivered faster.

Read More


 

Changing Scene

  • Prev
E.B. Horsman & Son (EBH) has announced their Victoria location will be officially moving to a ...
 The Maritime’s largest Mechanical and Electrical event took place last Wednesday and ...
IDEAL INDUSTRIES, INC. is calling all professional and student-apprentice electricians to come out ...
Vivi White has been appointed to the Board of Directors of the Electrical Safety Authority ...
The Sonepar Ontario Region is proud to announce the relocation of their SESCO Central Distribution ...
The Electrical Safety Authority (ESA) is looking for a seasoned business executive drawn from an ...
David Rellinger, Vice President of Systems Transformation for Schneider Electric (SE), has been ...
The National Electrical Trade Council (NETCO) is pleased with the direction of the 2022 budget with ...
The Executive of Gerrie Electric Wholesale Limited is very pleased to announce the acquisition of ...
The Labour Mobility Tax deduction will provide tax recognition on up to $4000 per year, in eligible ...


Vivi WhiteVivi White has been appointed to the Board of Directors of the Electrical Safety Authority (ESA) by the Honourable Ross Romano, Minister of Government and Consumer Services.

“As Chair, I am pleased that the Ontario Government recently appointed Vivi White to the Board,” said Annette Bergeron. “The Electrical Safety Authority’s efforts over the years have greatly improved the safety of the people of Ontario. It’s an important mandate and requires a strong, talented and diverse board as we transform into a modern regulator.”

 

Read more


 

Omnicable joins ETIMETIM North America announced that OmniCable has joined the product classification standards organization. Headquartered in West Chester, PA, OmniCable has 24 locations throughout North America, and also owns Houston Wire & Cable (HWC). The company partners with many electrical manufacturers and only sells to distributors.

According to John Dean, Director of Marketing & E-Commerce, OmniCable/HWC, “The wire and cable industry is often called commodities, but there are very distinct features and attributes for the different products our manufacturers produce. 

Read More

 


 

Canadian Electrical Contractor Discussion Group: Can You Count the Deficiencies?

EIN CECD 400Have you ever been called to fix the work of a 'handyman'?

"Was supposedly done by a"certified ' electrician....told the homeowner that he got a $266 permit....no record at TSBC. Can you count the deficiencies?"

"There is a second panel change in the triplex also.......even more deficiencies. Think the guy was a glorified handyman. Ones not obvious: 240 BB heat hooked up 120....drier on 2p20....range on 2p50....water heater fed with 2c14 Bx on 2p15."

Go HERE to join the discussion

 


 



 

FlukeElectrical distribution problems are not always immediately identified as issues with power quality. An example of this is a thermal-magnetic circuit breaker. When it trips, the indication is generally a short circuit, ground fault, or overload. At times this can be put down to an old breaker that needs replacing.

However, it’s important to investigate the types of loads on the system and monitor harmonics for a potential disturbance. This article explores common issues with power quality and how to troubleshoot those issues.

 

 

Read More


 

EIN Romex 12 2 Recall 400This recall involves a yellow electrical wire, 12/2 NMD90 75M Romex SIMpull cable, sold by the spool. Products were also sold at Home Depot designated as article 108196.  Only cables with a time stamp between 12:41 and 18:02 are affected by this recall. 

The recalled product contains a neutral wire that is a smaller 14-gauge wire, contrary to the stamp on the wire identifying both the neutral and “hot” wires as 12-gauge (i.e., "12/2"). 

The recalled product contains a 14-gauge neutral wire instead of 12-gauge (as labelled), thus it may not perform as expected in 12-gauge applications, resulting in a risk of those applications having impaired performance and/or compliance with safety codes or standards.

Go HERE for more information


 

Product News

  • Prev
The SYM-IN "In Table" model provides an attractive user interface while solid construction ...
The NEW Contractor Select™ version of the Juno Podz™ Canless Downlight is now easier than ever ...
Introducing the NEW Hi-Tech Valiant™ full-range current-limiting fuse for fire mitigation. No one ...
Appleton™ explosionproof and dust-ignition proof GR, GRF and GRTS conduit outlet boxes are ...
Southwire's new 100' LED string lights with 12,000 Lumens.    
Help provide comfort and functionality to your bathroom with the addition of the Broan BHF110 ...
The PWB-CMU8 is the first dedicated Masonry Wall Box engineered for installation in 8” block walls. ...
Now with pre-sized labels and even more materials to take on the toughest on-site labelling jobs. ...
The STACK Family is now complete! These four performance-tiered solutions were designed to help you ...
This 8’’ boot with internal metatarsal protection has a ¾ welt construction and heel stabilizer ...


Greenlee Mobile Bending Table for 881 Series Hydraulic BendersGreenlee is bringing secure and easy-to-transport conduit bending capabilities to jobsites with the introduction of its Mobile Bending Table for 881 Series Hydraulic Benders. The new product combines the latest in anti-theft protection with enhanced mobility, easy set-up and quick teardown.

“Electricians are constantly trying to do work more efficiently. Anytime we can shave time off a job, it’s a win – and this product delivers that with easier set-up and portability. At the same time, we know that protecting equipment from theft is an issue for a lot of tradespeople. The new Greenlee Mobile Bending Table for the 881 Series Hydraulic Benders is our latest solution to help professionals safeguard their investments and increase productivity,” 

Read More


 

 

Klein Tools Upgraded Testing KitKlein Tools introduces the Premium Electrical Test Kit.

Premium Electrical Test Kit (Cat. No. 69355)

  • Refreshed kit that features three new product releases geared towards a variety of electrical testing applications.
  • Kit includes instructions and all required batteries.

Manual-Ranging Digital Multimeter with Right-Angle Test Leads (Cat. No. MM320 – Exclusive to Cat. No. 69355 and Cat. No. MM320KIT)

  • Measures up to 600V AC/DC voltages, 10A DC current and 2-ohm resistance
  • Also tests batteries, diodes and continuity.

Read More


 

 

Brady M211Design, preview and print – all from your phone. Simple and intuitive, the M211 Label Printer is built for the job site, running all day on a full charge while resisting drops, shocks and crushes.

  • Simple. Easy. Intuitive.  Seamlessly design, preview and print labels from the industry leading Express Labels App on your familiar smartphone and swiftly connect to your printer.
  • Label it once.  Now with both pre-sized and continuous labels in 90+ cartridges, filled to the brim with reliable, tested and dedicated label materials that stay attached and remain legible on every surface and in any environment.

 

Read More


 

Peers & Profiles

  • Prev
Watt’s the Word is a recently launched Electrical Industry Podcast hosted by Zack Hartle and ...
Allana Kellett-Jamieson loves working in the electrical sector and is proud of the great focus ...
As the head of ABB Canada's electrification business unit, Éric Deschênes is no newcomer to the ...
Karen Pullen knows what it’s like to be the only woman on a construction site, and as a proud ...
As of February 2021, Martin Stephenson is the new President and CEO of Signify Canada.   ...
This past July, Kerith Richards, who has worked for Service Wire Company for the last seven years, ...
EngWorks was formed in 2004 as an electrical engineering and consulting firm by Allan Bozek, “After ...
Headquartered in Concord, Ontario, Mercury Lighting services national retail, ...
Among the recipients of the 2021 Clean50 Awards announced last month is Carolina Gallo, Vice ...
Sarah Silverstein is a principal with Liteline along side her two brothers Mark and Daniel. ...


Brent NeillyBy Blake Marchand

Brent Neilly is the Group Marketing Manager with Milwaukee, he has a background in business communications with a B.A. from Brock University, as well as experience working in the construction industry.

“When I joined TTI (Milwaukee’s parent company) it was kind of a perfect match, I had some marketing knowledge from my business degree and some industry experience from working in the trades.” Neilly gained his experience covering an area from Orillia to Timmins, Ontario when he first joined the company as a Field Sales Rep, as well as on their Job Site Core Trade Specialists in the GTA where he found his niche working with utility clients. 

Read More


 

Copper $US Dollar price per pound

Kerrwil Publications Great Place to Work. Certified December 2019 - December 2020

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2022 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil