In this article: Section 40 — Electric cranes and hoists. The CE Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the information you need. This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook, but will hopefully provide some help in navigating the code.

40-000 Scope — this is a supplementary or amendatory section of the code and applies to the installation of electrical equipment and circuits for electric cranes, hoists, and monorails. The CEC Handbook provides additional notes and diagrams to better explain this section.

40-002 Supply conductor sizes — because of the short duty of crane and hoist motors, supply conductors are selected from Table 58, which specifically applies to crane and hoist installations.

40-004 Conductor protection — supply conductors for the main contactors of cranes and hoists must be in raceway, armoured cable, or mineral insulated, aluminum-sheathed or copper-sheathed cable. There is an exception to this where a conducting track of conducting rails is used as per 40-018. Where conductors supply the crane or hoist equipment directly and where a flexible connection is necessary, flexible type cord or festoon cable is permitted provided there is a take-up device provided to prevent damage and contact with the floor.

40-006 Overcurrent protection — for main contact supply conductors or directly supplied equipment, the overcurrent protection must be selected as per Rule 28-200 and Tables 29 and D16 for the motor load, plus any allowance as per Rule 14-104 where conductors have been selected with capacity for the other loads on the crane or hoist.

40-008 Disconnecting means — all ungrounded conductors of the main contact conductors must be capable of being simultaneously disconnected quickly for safety in an emergency and for maintenance. The disconnect must be within sight of the main contact conductors or the equipment. In addition, the disconnect must be accessible and be operable from the ground or floor over which the crane or hoist operates.

40-010 Main contact conductors — this rule requires that where there are bare main contact conductors, they must have an ampacity not less than the conductors supplying them and, if wire, shall be not smaller than No. 4 AWG copper, or No. 2AWG aluminum. If the conductors are more than 18 m long, then the minimum size must be No. 2 AWG copper or No. 1/0 AWG aluminum unless intermediate strain relief is provided by clamp type insulating supports. Bare conductors may be hard drawn copper, aluminum wire, or steel or other suitable metal in the form of angles, tees, T-rails, or other rigid shapes.

40-012 Spacing of main contact conductors —because bare main contact conductors depend on free air space to provide insulation between phases and to ground, this rule outlines the minimum support separation required of main contact conductor wires installed in a horizontal plane of 75mm for monorail hoists and 155 mm for other than monorail hoists. If installed in other than a horizontal plane, the separation of the main contact conductor wire supports must be 200mm. They should also be supported so that the extreme limit of displacement maintains a separation of 38mm from any surface. Where the bare main contact conductors are rigid, the supports must provide a minimum separation of 25mm between conductors, collectors, and any surface.

40-014 Supporting of main contact conductors — in addition to the spacing required in rule 40-012, the main contact conductor wires must be stretched between strain insulators at each end and supported throughout the length at 6m intervals. If building conditions preclude supporting at 6m intervals, it may be increased to a maximum of 12m intervals providing the separation between contact conductors is increased by the same proportion. In the case of rigid main contact conductors, insulated supports must be spaced at intervals of up to 80 times the vertical height of the conductor but not more than 4.5m. Refer to the CEC Handbook for diagrams illustrating support spacing and calculation notes.

40-016 Joints in rigid contact conductors — this rule outlines the importance of ensuring that any joints made in rigid main contact conductors must maintain the same ampacity of the conductors over the joint to eliminate any overheating.

40-018 Use of track as a conductor — this rule permits a single monorail, tramrail or crane runway track to be used as one of the main contact conductors or supply circuit conductors for one phase of a 3-phase circuit, providing it is derived from a single isolating transformer, does not exceed 300 v, is bonded to ground (see Rule 10-1100 to 10-1108), and any joints meet rule 40-016.

40-020 Guarding of contact conductors — requires that all contact conductors be guarded against inadvertent contact with bare current-carrying parts unless incorporated in an enclosed contact assembly. In addition, as long as a minimum clearance of 6 m between bare contact conductors and grade, floor, or any working surface (including a catwalk) is maintained, guarding of bare contact conductors may not be required.

40-022 Contact conductors not to supply other equipment — this rule prohibits the contact conductors supplying the crane, hoist or monorail feeding other equipment not essential to the operation of the crane, hoist or monorail.
40-024 Bonding — as per Rule 10-406 all exposed non-current carrying parts shall be bonded to ground. In addition, in the case of a track or rail used as a conductor, it shall be bonded in accordance with Rule 40-018. Note that metal wheels on metal rails may provide a low impedance grounding path. A flexible supply connection as per Rule 40-004(2) must contain a bonding conductor.

In the next instalment, we will be discussing Section 42 — Electric welders.

The source for this series of articles is the Canadian Electrical Code, Part I, published by CSA

William (Bill) Burr is the former Chair of the Canadian Advisory Council on Electrical Safety (CACES), former Director of Electrical and Elevator Safety for the Province of BC, and former Director of Electrical and Gas Standards Development and former Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting billburr@gmail.com.

 

 

Changing Scene

  • Prev
Skills Ontario Summer Camp is a week-long day program for kids entering Grades 7-9.   ...
  Glen Dimplex Americas is proud to announce that its Vancouver facility was recently ...
May 13 to 19 is Powerline Safety Week in Ontario, which is meant to inform people across the ...
Divisional Lighting Manager Salma Siddiqui, the initiative will focus on making Westburne the ...
As of April 30, Natural Resources Canada has new dry-type transformer energy efficiency ...
Ontario Power Generation (OPG), in partnership with the Six Nations of the Grand River Development ...
The Energy Council of Canada has chosen of Fort St. John, BC Mayor Lori Ackerman as Canadian Energy ...
The winners of the New Products Competition at the MCEE 2019 trade show were announced tonight; ...
The year was 2002: Jean Chrétien was Prime Minister, Avril Lavigne topped the charts, the ...
The company’s wholesale locations will be branded Robinson Supply, and the lighting and bath ...

Electrician Forum Brought to you by Schneider Electric

As industry experts you know the products you use everyday better than anyone and should have input on what information you receive about products and what could improve them.

Therefore, we want your insight on the biggest challenges or issues you face when installing loadcentres, breakers (CAFI, GFI's…) and other surge protection devices. We ask that you do not provide product specific details but rather your general issues and concerns or any questions that have come to mind while working with these product types. Provide us with your valued expert insight into the issues you have faced so manufacturers can better inform you about the installation and use of these products. Lets generate some discussion that will help guide the Industry.

Make your comments  HERE

 

ESA Powerline SafetyThe invisible impact of powerlines should never be underestimated. In the past decade alone, 19 people in Ontario have lost their lives from overhead powerline contact. May 13 to 19 is Powerline Safety Week, which is meant to inform people across the province to stay vigilant of powerlines when doing work at home or on the job.

"Our work in raising awareness of powerline safety won't be finished until there are zero injuries or lives lost from contact," says Dr. Joel Moody, Chief Public Safety Officer, Electrical Safety Authority (ESA). "All it takes is a misstep or careless error to change the life of you, your colleagues or family."



Read More

 

 

 

 

ABB Eco FactoryABB has an extensive portfolio of eco-efficient solutions and services that can help decouple economic growth from environmental impacts. In fact, over half of ABB's worldwide revenues are generated by technologies that combat the causes of climate change. The company’s goal is to increase this contribution from 57 percent in 2018 to 60 percent by 2020.

The company’s commitment to combatting climate change includes limiting the environmental impact of its own operations. ABB’s current target for climate action is to reduce its own GHG emissions by 40 percent by 2020 from a 2013 baseline.



Read More

 

 

Codes and Regulations Brought to You by the CSA Group

  • Prev
The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the ...
The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the ...
In this article: Tables — Part B. This section of the Code contains 99 tables of essential ...
In this article: Section 58 — Passenger Ropeways and Similar Equipment. Rule 58-000 ...
  Unauthorized CSA Group certification marks have been found on wiring by Triumph Cable ...
In this article: Section 52 — Diagnostic imaging installations. The CE code is a ...
In this article: Section 46 — Emergency Power Supply, Unit Equipment, Exit Signs, and ...
  In this article: Section 44 — Theatre Installations. The CE Code is a ...
CSA has published C22.2 No. 60947-7-3, the harmonized standard for low-voltage switchgear and ...
  Electric welders. The CE Code is a comprehensive document. Sometimes it can seem ...

 

Wind Energy

Canada’s wind energy industry further expanded its installed capacity in 2018, while solidifying its status as the lowest-cost source of new electricity generation. Newly commissioned projects brought total national wind energy capacity to close to 13,000 megawatts (MW). Meanwhile, competitive auction results in Saskatchewan and Alberta confirmed the wind industry’s ability to continue to deliver record-low prices.

The six wind energy projects that were powered up in 2018 added 566 MW of installed capacity — a continuation of steady growth that contributed to an average annual growth rate of 20% per year since 2008.

Read more about Wind Energy...

Latest Articles

  • Prev
Britech Corp, one of Canada’s largest heating cable companies has signed a formal agreement ...
Electrical enclosures serve to protect electrical devices from adverse environmental influences, ...

Tools for the Trade

  • Prev
  IDEAL Industries has introduced Combination Drill Taps to its tool lineup. Combining the ...
  Stripping and crimping device, 100 - 240 V input voltage, for insulated ferrules with a ...
Professional all-in-one cutter/stripper for coaxial and twisted pair cables     ...
  Klein Tools' Coax Explorrer 2 tests coaxial cable and maps up to 4 locations   ...
  Ideal Industries' T-14 wire stripper s are ideal for all professionals working within the ...
  The ATS850 conveyor eliminates all types of electro static discharge requirements. ...
  Lorik Tool & Automation has the experience and ability to manufacture a variety of ...
  Ideal Industries' 26 piece insulated Journeyman kit is ideal for new electricians or for ...
  Klein Tools Deluxe Fish Rod Set comes in 19 pieces that when assembled can fish wire and ...
  BendWorks Software was designed to help electrical contractors adopt this new process ...

Solar Cell

A joint research team has developed a new type of highly flexible and stable solar cell that could be used in wearable electronics.

The power supply is vital to the safety of wearable electronics. Perovskite solar cell (PSC) has been widely used to manufacture flexible batteries because it is highly efficient, cheap, and easy to use. Perovskite is a material with the same type of crystal structure as calcium titanium oxide.

The flexible substrate is the key factor to determine the performance of PSCs.

Read more about Flexible Solar Cells...

 

 


BritechBritech Corp, one of Canadas largest heating cable companies has signed a formal agreement with Heat Trace Limited, of Cheshire, England. Heat Trace, founded in England in 1974, Heat Trace is one of the world’s leading industrial heat trace cable manufacturers.

The company is known mainly for innovative solutions in self-regulating high temperature heat tracing cables up to 275°C, their exclusive high temperature, 425°C, cut to length, industrial, in the field replacement for mineral insulated cables, and their high temperature Long Line heating cables that can be installed on pipes in one length up to 10 kilometers long.

Read More...

 

Product News

  • Prev
Lutron Electronics is helping contractors save time and secure more jobs with quick lighting ...
Single Phase Power Solutions introduces the 1-to-3 Power Source features a BELLE Motor which uses ...
Rolling Motion Industries (RMI) has released for production the next two in it's series of highly ...
Take a step towards the factory of the future with an ultra compact machine automation controller ...
Available immediately, the FE060-25-EM is the first servo drive of the new FlexPro digital drive ...
Kollmorgen has launched the VLM servo motor series to fill the gap between stepper and ...
Altivar Machine ATV340, a variable speed drive designed for Original Equipment Manufacturers ...
You can wire conductor cross sections of up to 185 mm² very quickly using the PTPOWER 185 ...
Fluke's award-winning 754 does the work of several tools - sourcing, simulating and measuring ...
B&R's latest addition to its Compact-S series is a compact controller with an ...

Flir VP40FLIR Systems have released the FLIR VP40, a non-contact voltage detector for use in North America designed for field-troubleshooting and verification of residential, commercial, and industrial electrical installations. The VP40 makes it easy to quickly troubleshoot live and neutral wiring to ensure a safe job site.

With its built-in flashlight and CAT IV safety rating, the FLIR VP40 is a must-have for preliminary job site checks for live wiring. The durable, pen-sized tester quickly identifies the presence of AC voltage without contacting wires, even in the latest safety outlets.


Read More

 

 

NP DRMSExpanding on its extensive product line for motion control applications, Sensata Technologies recently released the Crydom DRMS Series hybrid motor starters.

These new hybrid starters integrate the benefits of both solid state and electromechanical relay technologies to produce a compact device that can control electrical power delivery to motors as large as 4kW. Suitable applications range from access control, packaging equipment, lifts and escalators to industrial process control and machine tooling systems.

 


Read More...

Copper $US Dollar price per pound

Kerrwil Publications

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2019 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil