By William (Bill) Burr

In this article: Section 42 — Electric welders. The CE Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the information you need. This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook, but will hopefully provide some help in navigating the code.

Rule 42-000 Scope — states that Section 42 is a supplementary or amendatory section of the code and applies to the installation of electric welders. The CEC Handbook provides additional notes and diagrams to better explain this section. There are two main types of welders: arc and resistance welders. Arc welders use a sacrificial rod to weld the metal target material together. Resistance welders fuse the metal target material together. Arc welders are divided further into transformer and motor-generator types.

Rule 42-002 Special terminology — contains definitions for special terms that apply to section 42 that are not defined in Section 0 such as: actual primary current, duty cycle, and rated primary current. These terms will be important when calculating the ampacity of the supply conductors for welders.

Rule 42-004 Receptacles and attachment plugs — outlines that, where receptacles are installed for the plug and cord-connection of a portable welder, the ampacity rating of the overcurrent protection for the circuit can be more than the rating of the receptacle, but the receptacle must have a rating equal to or greater than the ampacity of the supply conductors for the welder. This is important because the high instantaneous inrush start-up current of the welder will exceed the branch circuit conductor ampacity. This prevents nuisance tripping.

Transformer arc welders

Rule 42-006 Supply conductors — provides the factors in determining the ampacity of supply conductors for transformer type arc welders. The ampacity depends on the duty cycle of a single welder, as in sub-rule (1) and the demand factors where a group of welders are supplied by one circuit as in sub-rule (2). The CEC Handbook contains Tables 42-1 and 42-2, which show the correlation between duty cycle and demand factor and determination of the demand factor for multiple welder installations.

Rule 42-008 Overcurrent protection for transformer arc welders — specifies the factors to be used in calculating the rating of circuit overcurrent protection per the ampacity of supply conductors and welders as in sub-rule (1). Sub-rule (2) outlines the factors in calculating the rating of the overcurrent protection for the supply conductors using Tables 1,2,3, or 4. Sub-rule (3) provides the factors in calculating the rating of the overcurrent protection for a feeder supplying a group of transformer arc welders.

Rule 42-010 Disconnecting means — requires that where there is no integral disconnect on the welder, one must be provided to disconnect the supply conductors, and it must have sufficient current rating capacity to accommodate the overcurrent protection.

Motor-generator arc welders

Rule 42-012 Conductors, protection, and control of motor-generator arc welders — specifies that the rules of Section 4 and Section 28 generally apply to the determination of supply conductor ampacity, and selection of protection and control. The CEC handbook outlines methods of calculation of duty-related demand factors through Table 42-1, 42-2 and 42-3.

Resistance welders

Rule 42-014 Supply conductors for resistance welders — provides the factors in determining the ampacity of supply conductors depending on the primary current or duty cycle of either an individual seam resistance welder or an automatically fed resistance welder. Table 42-4 in the CEC Handbook shows the relationship between duty cycle and demand factors.

Rule 42-016 Overcurrent protection — specifies the factors in determining the rating of the overcurrent protection based on the rated primary current of the welder and the allowable ampacity of the supply conductors based on Tables 1,2,3 or 4. The CEC Handbook outlines methods of calculation of duty related demand factors through Tables 42-3 and 42-4. For determining the rating of overcurrent Protection for a group of resistance welders use the factors contained in rule 42-014.

Rule 42-018 Control of resistance welders — requires that a resistance welder have a disconnecting switch or circuit breaker rated for the capacity of the supply conductors to isolate the welder from the supply circuit.

Rule 42-020 Nameplate data for resistance welders — requires data specific to the resistance welder be provided on the nameplate, including rated KVA at 50% duty cycle, maximum and minimum open-circuit secondary voltage, short circuit current, and the throat and gap setting.

In the next installment, we will be discussing Section 44 — Theatre installations

* The source for this series of articles is the Canadian Electrical Code, Part I, published by CSA

** Note the CEC Handbook is also published by CSA.

William (Bill) Burr is the former Chair of the Canadian Advisory Council on Electrical Safety (CACES), former Director of Electrical and Elevator Safety for the Province of BC, and former Director of Electrical and Gas Standards Development and former Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting billburr@gmail.com.


The source for this series of articles is the Canadian Electrical Code, Part I, published by CSA
William (Bill) Burr is the former Chair of the Canadian Advisory Council on Electrical Safety (CACES), former Director of Electrical and Elevator Safety for the Province of BC, and former Director of Electrical and Gas Standards Development and former Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting billburr@gmail.com.

 

 

Changing Scene

  • Prev
During the recently held IMARK Canada 2019 meeting in Niagara Falls, executives from 14 of the ...
Valard has been selected by Wataynikaneyap Power LPto provide engineering, procurement ...
The Canadian Apprenticeship Forum-Forum Canadien sur l’Apprentissage (CAF-FCA) has announced ...
Electricity Human Resources Canada has announced this year's keynote speakers for Agents of Change ...
Kiashke Zaaging Anishinaabek (KZA)/Gull Bay First Nation (GBFN) and Ontario Power Generation (OPG) ...
The BCEA's Woman's Network THRIVE Summit is taking place on October 4th at the Executive Inn ...
NSI Industries has announced the acquisition of electrical products manufacturer Bridgeport ...
The National Electrical Trade Council (NETCO)—jointly sponsored by International Brotherhood ...
IDEAL Electrical has launched its fourth annual national competition to find the best ...
IDEAL Industries Canada has announced the appointment of Sean Bernard as Regional Sales Manager to ...

Electrician Forum Brought to you by Schneider Electric

As industry experts you know the products you use everyday better than anyone and should have input on what information you receive about products and what could improve them.

Therefore, we want your insight on the biggest challenges or issues you face when installing loadcentres, breakers (CAFI, GFI's…) and other surge protection devices. We ask that you do not provide product specific details but rather your general issues and concerns or any questions that have come to mind while working with these product types. Provide us with your valued expert insight into the issues you have faced so manufacturers can better inform you about the installation and use of these products. Lets generate some discussion that will help guide the Industry.

Make your comments  HERE

 

SoneparSonepar Canada has announced the launch of new mobile applications for Gescan Vallen, Sesco and Lumen.

The mobile apps were officially released as of June of this year and features barcode scanning, access to pricing, product availability, store locator and much more – 24 hours a day, 7 days a week.

The new mobile app is changing the way customers can interact with the Operating Companies within Sonepar Canada. The barcode scanning functionality is a popular feature amongst customers allowing them to scan an item easily and add it to their cart.

 

Read More

 

 

 

Fredericton Transmission LineNB Power recenly announced it will seek approval to build a new transmission line in the Fredericton area, which will improve the reliability of the power grid in the region for approximately 25, 000 customers.

The new proposed 15-kilometre transmission line will run from the Rainsford Substation, in Fredericton, to the Mactaquac Terminal.

“NB Power strives to offer its customer a reliable power grid that meets or exceeds all utility standards,” said NB Power’s President and CEO, Gaëtan Thomas. “This will increase transmission reliability for customers in the Fredericton region with fewer interruptions that can be restored within minutes rather than hours or days.”

Read More

 

 

Codes and Regulations Brought to You by the CSA Group

  • Prev
The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the ...
The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the ...
In this article: Tables — Part B. This section of the Code contains 99 tables of essential ...
In this article: Section 58 — Passenger Ropeways and Similar Equipment. Rule 58-000 ...
  Unauthorized CSA Group certification marks have been found on wiring by Triumph Cable ...
In this article: Section 52 — Diagnostic imaging installations. The CE code is a ...
In this article: Section 46 — Emergency Power Supply, Unit Equipment, Exit Signs, and ...
  In this article: Section 44 — Theatre Installations. The CE Code is a ...
CSA has published C22.2 No. 60947-7-3, the harmonized standard for low-voltage switchgear and ...
  Electric welders. The CE Code is a comprehensive document. Sometimes it can seem ...

 

Emergency Lighting PrinciplesBy Kevin Smee, Vice President Sales at AimLite

Most of us take light for granted. It has become so ubiquitous and cheap to use that we don’t really stop to think about emergencies. Thankfully most buildings are required by law since 1974 to be equipped with emergency lighting that automatically activates during power failures to facilitate our exit.

Emergency lighting is only one component of a building’s life safety systems, but perhaps one of the most important. 

 

 

Read More  

Latest Articles

  • Prev
Pick up a newspaper or scan your preferred electronic newsfeed and you’ll likely see a series ...
Britech Corp, one of Canada’s largest heating cable companies has signed a formal agreement ...
Electrical enclosures serve to protect electrical devices from adverse environmental influences, ...

 

Open Office DesignOpen office design has exploded in popularity over the last 20 years. In fact, the New Yorker magazine claims that approximately 70% of all offices now have an open floor plan.[1]

How did we get here?

Although open offices have been around since the mid-1700s, the cubicle culture developed by Hermann Miller in 1964 became very popular in the 1980s and 1990s. By the early 2000s, open office design started to re-emerge in an effort to encourage more collaboration and Silicon Valley was among the first to embrace sleek, open office workspaces as the norm.

Read More

 

 

Tools for the Trade

  • Prev
  IDEAL Industries has introduced Combination Drill Taps to its tool lineup. Combining the ...
  Stripping and crimping device, 100 - 240 V input voltage, for insulated ferrules with a ...
Professional all-in-one cutter/stripper for coaxial and twisted pair cables     ...
  Klein Tools' Coax Explorrer 2 tests coaxial cable and maps up to 4 locations   ...
  Ideal Industries' T-14 wire stripper s are ideal for all professionals working within the ...
  The ATS850 conveyor eliminates all types of electro static discharge requirements. ...
  Lorik Tool & Automation has the experience and ability to manufacture a variety of ...
  Ideal Industries' 26 piece insulated Journeyman kit is ideal for new electricians or for ...
  Klein Tools Deluxe Fish Rod Set comes in 19 pieces that when assembled can fish wire and ...
  BendWorks Software was designed to help electrical contractors adopt this new process ...

ArcflashBy Tony Oruga

Network crews were working in an electrical room tasked to install an 800 A disconnect for a temporary service on the network secondary. The 3-spot network was energized at 480 V on the secondary (34.5 kV on the primary) and all three network protectors were closed and serving load. Each network protector installed was a 3000 A, 480 V Eaton CM52 unit equipped with an Arcflash Reduction Maintenance SystemE (ARMS). Prior to performing their work, crews enabled the ARMS function on all three units in the spot. This put all three network protectors in a “hair-trigger” mode, ready to clear any current condition that exceeded 2.5x the nameplate rating.

Read More

 

Product News

  • Prev
Standard Stanpro’s LED Tapes work on direct line voltage 120V and can easily be installed ...
Standard Stanpro’s FLUO LED is designed for 120 V applications and is easy and quick to ...
The LCAN series is an indoor and outdoor surface mount with V-type light distribution.   ...
HPS Sentinel G ventilated stand-up distribution transformers meet the latest federally mandated ...
Advanced Performance in a Classic Form Factor The UFIT LED Low Bay is the perfect combination of a ...
The clean and elegant design of EG series 1X4FT led flat panel light provides a modern alternative ...
Signify has announced new smart light products, including an upgraded Hue Go, the Smart button and ...
HomeWorks by Lutron is a lighting and shading control solution for luxury homes.   ...
Signify unveiled its brand-new Philips Hue Filament collection, perfect for those who want to bring ...
These LED lamps are designed to meet or exceed the standards set out in the California Energy ...

 

EikoThese LED lamps are designed to meet or exceed the standards set out in the California Energy Commission’s Title 20 and Title 24 (JA8) Appliance Efficiency Regulations.

FEATURES

  • MR16 GU5.3 and GU10 base; B11 Decorative E12 and E26 base
  • 80% more efficient and 30x longer life than standard incandescent
  • Shatter-resistant plastic housing for reduced risk of injury and breakage
  • Compatible with a wide array of dimmers
  • ANSI construction compliant

Read More

 

 

Copper $US Dollar price per pound

Kerrwil Publications

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2019 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil