Bill BurrBy William (Bill) Burr


The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the information you need. This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook** but will hopefully provide some help in navigating, while reading the code. The 24th Edition of the CE-C, Part I, (C22.1-18)* is now available from CSA Group.

In this article: diagrams and appendices. The Diagrams section of the Code contains 10 diagrams that illustrate essential information referenced by various rules of the Code. Diagrams referenced by rules are considered normative (mandatory) elements of the Code.

Diagram 1, which is referenced by Rules 26-700, 26-720, 26-744, 38-023, 58-400, 78-052, 78-102, and 86-306, as well as Diagram 2 and Appendix B, provides face illustrations for the CSA configurations for non-locking receptacles based on nominal voltages and amperages.


Diagram 2, which is referenced by Rules 12-020, 26-700, 78-052, 78-102, and 86-306, as well as Diagram 1 and Appendix B, provides face illustrations for the CSA configurations for locking receptacles based on nominal voltages and amperages.

Diagram 3, which is referenced by Rule 14-102 and Appendix B, illustrates the ultimate point of conductor de-energization of a faulted circuit, downstream from the point or points marked with an asterisk.

Diagram 4, referenced by Rule 20-302 (2), illustrates the extent of the Zone 2 hazardous location from the open face of a paint spray booth.

Diagram 5, referenced by Rule 20-302, illustrates the extent of the Zone 1 and Zone 2 hazardous locations for spraying operations not conducted in spray booths.

Diagram 6, referenced by Rule 20-302 (7), illustrates the extent of the Zone 1 and Zone 2 hazardous locations for spraying operations not conducted in spray booths, but with the ventilation system interlocked with the spraying equipment.


Diagram 7, which is referenced by Rule 20-034 and Part B of Table 63, illustrates the extent of the Zone 1 and Zone 2 hazardous locations for tank vehicle and tank car loading and unloading.


Diagram 8, which is referenced by Rule 20-034 and Part E of Table 63, illustrates the extent of the Zone 1 and Zone 2 hazardous locations for pumps, vapour compressors, gas-air mixers, and vapourizers outdoors, in open air.

Diagram 9, which is referenced by Rule 20-034 and Part J of Table 63, illustrates the extent of the Zone 1 and Zone 2 hazardous locations for container filling outdoors in open air.

Diagram 10, which is referenced by Rule 20-302 (3), illustrates the extent of the Zone 2 hazardous locations adjacent to openings in a closed spray booth or room.


The Appendices section of the Code contains both normative (mandatory) and informative (non-mandatory) appendices providing information associated with rules of the Code.


Appendix A - Safety Standards for Electrical Equipment is a normative section and lists the standards used to certify electrical equipment for the purpose of being “approved” as defined in Section 0. Note that adopted international standards listed in this appendix may include Canadian deviations, and compliance with them is required for implementation in Canada. Also note that CSA and other accredited standards development organizations (SDOs) may publish new Canadian standards for electrical equipment, or periodically amend or publish new editions of standards listed in this appendix, and they may be used for product approval purposes by accredited certification organizations. In accordance with the mandatory procedures in Appendix C, the SDO publishing or amending a standard must notify the project manager of the Committee on Part I for distribution to the committee.

Appendix BNotes on Rules is an informative (non-mandatory) section of the Code that provides information and illustrations clarifying various diagrams, tables and rules in the Code.


Appendix COrganization and Rules of Procedure is a normative (mandatory) section of the Code and outlines the structure of the Canadian Electrical Code, Part I Committee, sub-committees, Executive Committee and the Regulatory Authority Committee, as well as the operating procedures for developing the code. It includes:

• procedures for amendments to the Code, interpretations of the Code, and appeals, if procedures are not followed
• the format and Rule terminology of the Code
• procedures for inclusion of reference standards to Appendix A as noted above, a flow chart, and a declaration checklist
• a standard form for subcommittee reports
• a form to be used to request an amendment to the Canadian Electrical Code, Part I
• a guide to subcommittee chairs for evaluation of proposals and subcommittee reports


Appendix D - Tabulated general information is an informative (non-mandatory) section that provides 17 tables and 4 diagrams of tabulated general information.


Appendix E - Dust-free rooms is an informative (non-mandatory) section and outlines construction of dust-free rooms built adjacent to or as part of buildings that, by the nature of their use or occupancy, are subject to accumulations of dusts that may create a fire or explosion hazard, and allows you to supplant the requirements of Appendix J for Class II and Class III hazardous locations.


Appendix F - Engineering guidelines is an informative (non-mandatory) section and provides engineering guidelines for preparing descriptive system documents for intrinsically safe electrical systems and non-incendive field wiring circuits as referenced by Rules 18-002, 18-064, J18-002, and J18-064.

Appendix G - Electrical installations of fire protection systems is an informative (non-mandatory) section that lists requirements related to electrical installations of fire protection systems that are not governed by rules of the Canadian Electrical Code, Part I but are required by the National Building Code of Canada.


Appendix H - Combustible gas detection equipment is an informative (non-mandatory) section that lists requirements and recommendations for combustible gas detection equipment for use in explosive gas atmospheres as referenced by Rules 18-068 and J18-066.


Appendix I - Interpretations is an informative (non-mandatory) section and includes committee interpretations of the Canadian Electrical Code, Part I that have been requested in writing to the project manager of the Committee on Part I. The form of a question must be such that it can be answered by a categoric “yes” or “no”. These interpretations are based on rules in the 2015 Code, so rule numbering and content in the 2018 Code may differ from the 2015 edition.


Appendix J - Class and Division System Installations contains normative rules and informative notes to rules for additions, modifications, renovations to, or operation and maintenance of existing facilities employing the Class and Division system permitted by Rules 18-000 (3) 18-000 (4), 20-000 (2), and 20-000 (3). The rules of Annexes J18, J20, JD and JT of this appendix are normative (mandatory, and the notes and illustrations contained in Annex JB are informative (non-mandatory). Note: Annexes J18, J20, JD and JT, because of their length, will be discussed in future instalments.


Appendix K - Extract from IEC 60364-1 is an informative (non-mandatory) section that is an extraction from IEC Standard 60364-1 Chapter 13. Chapter 13 of Section 131 outlines the fundamental principles to provide for the safety of persons, livestock and property against dangers and damage that may arise in the reasonable use of electrical installations, and is quoted in the second paragraph of the Object of the Code.

Appendix L - Engineering guidelines is an informative (non-mandatory) section and provides engineering guidelines for determining hazardous area classifications in facilities where explosive atmospheres can occur, as required by Rule 18-004. This appendix can be used as a guide to classify both the zone system and the class and division system of hazardous locations.

Appendix M - Translated caution and warning markings is an informative (non-mandatory) section and provides a chart of caution and warning markings translated from English into French.

In the next instalment, we will be discussing Annex J18, of Appendix J.

* The source for this series of articles is the Canadian Electrical Code, Part I, (C22.1-18) published by CSA.

** Note the CEC Handbook is also published by CSA.

William (Bill) Burr is the former Chair of the Canadian Advisory Council on Electrical Safety (CACES), former Director of Electrical and Elevator Safety for the Province of BC, and former Director of Electrical and Gas Standards Development and former Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting billburr@gmail.com.

 

AD Spotlight                                                                                                            

Changing Scene

  • Prev
EFC’s exciting new product section on Electric Vehicle Systems conducted its first face-to-face ...
Canadian battery material specialist Hydro-Québec partners with Mercedes-Benz AG as part ...
Employer response to emerging technologies’ impact on the electricity sector workforce is critical ...
The National Electrical Manufacturers Association (NEMA) has published two new standards on ...
This fall, Canada's elite electricians and apprentices will be heading to Nashville, Tennessee for ...
The Electrical industry is “Powering a Changing World” in areas such as digitization, ...
Prior to joining ABB in 2017 as Executive Vice President of the Electrification business, Deschenes ...
The Canadian Apprenticeship Forum-Forum Canadien sur l’Apprentissage (CAF-FCA) has announced ...
The Support Equity and Under-Represented Groups project will address the under-representation of ...

SIemens Light+BuildingAt this year’s Light+Building trade fair, Siemens will showcase its vision for transforming today’s passive buildings into learning and adaptive environments that intelligently interact with people. The company’s focus at this year’s show is “Building the future today”, outlining the innovations that will make this possible. These include cloud-based technologies, digital planning, occupant-centric building automation and services. New solutions for smart electrical infrastructure that seamlessly connects to the Internet of Things (IoT) are also at the core of this transformation.

Read More

 

 

 

Latest Articles

  • Prev
I once took a class where the professor would explain concepts in two ways. First, he would dive ...
A broadening of the role of luminaires and a continued focus on people and energy efficiency are ...
There’s been a lot of confusion and misinformation disseminated regarding LED emergency lighting ...
We are in an Age of Disruption. Extant and emerging technologies are driving significant evolution ...
Often, code users encounter situations where they find themselves at odds with the rules contained ...
The new electrical code includes several changes to support electrical workers in the safe ...
Anyone working in the electricity sector in Canada knows the reality of how few women we have in ...
 Anyone working in the electrical industry knows the importance of labelling for both safety ...

Michelle BraniganBy Michelle Branigan

We are in an Age of Disruption. Extant and emerging technologies are driving significant evolution in the way work is done across all sectors of Canada’s economy and no industry, including electricity, will be immune.

Think of the technologies and businesses that have changed the way we live, work and connect with each other. Uber. Airbnb. Spotify. Facebook. Twitter. Duolingo. The list is long and what’s fascinating is that these are companies that did not exist 20 years ago. Yet these are common words in our lexicon today.

Read More

 

 


Greenlee Voltage DetectorsProfessionals searching for a reliable voltage detection solution have two new Greenlee options — the newly redesigned GT13 and TR13 non-contact voltage detectors. The new testers identify the presence of voltage from 50 volts to 1,000 volts AC. The redesigned GT13 and TR13 are now equipped with a more ergonomic grip and button location, along with a bright LED flashlight for use in dark work areas.


 

Read More

 

Product News

  • Prev
The controlHUBB Mobile App provides Bluetooth® wireless setup and configuration of NX Room Control ...
The LED filament lamps distinguish themselves by their sparkling white light, blending perfectly ...
Stanpro offers a wide range of Linear Fluorescent lamps for all lighting applications and needs. ...
This modern design series is a family of highly efficient and powerful LED flood lights and area ...
Our new 60W and 100W Temporary LED High Bays are the ideal substitute for traditional 250W and 400W ...
These high quality luminaires are equipped with a frosted lens that diffuses the light comfortably. ...
Arlington’s #300 non-metallic cable strap offers the easy way to attach flat NM cable to concrete ...
EiKO's Emergency Batery Kit is an LED emergency driver that allows the same LED fixture to be used ...
The LED Gimbal High Output downlight combines a sleek design with a small aperture without any ...
LPDL (Low Profile Downlight) gives you all the flexibility you need during installation, especially ...

 

Lumenwerx AcoustixLumenwerx is pleased to announce the launch of a new suite of acoustic luminaires to reduce ambient noise – ACOUSTIX family.

Developed in conjunction with acoustics experts, the new ACOUSTIX family of luminaires combines exceptional optics and precision sound absorbing technology to create a new paradigm in acoustic lighting. The lineup’s flagship fixture, the Audia, can increase sound absorption up to 30% more than competing products.

 

 

Read More

 

 


 

Leviton Nick FosterBy Blake Marchand

Nick Foster is Territory Manager, New Brunswick & P.E.I for Leviton. Foster was recently appointed as the Atlantic Regional Chair for Electro-Federation Canada’s (EFC) Young Professional Network (YPN).

Nick joins newly appointed National Chair, Sean Bernard of Ideal Industries, Ontario Region Chair, Joanna Kwant of Gerrie Electric, and Quebec Region Chair, Jean-Francois Gravel also with Leviton.

 

 

Read More

 

 

Copper $US Dollar price per pound

Kerrwil Publications Great Place to Work. Certified December 2019 - December 2020

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2020 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil