By William (Bill) Burr

In this article: Section 46 — Emergency Power Supply, Unit Equipment, Exit Signs, and Life Safety Systems. The CE Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the information you need. This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook, but will hopefully provide some help in navigating the code.


Rule 46-000 Scope states that Section 46 is a supplementary or amendatory section of the code and applies to the installation, operation and maintenance of emergency power supply and unit equipment intended to provide power to life safety systems, exit signs, and illumination of exit signs in the event of failure of the normal power supply in cooperation with the requirements of the National Building Code of Canada. Appendix B and the CSA CEC Handbook provide additional explanations and diagrams.


Rule 46-002 provides some special terminology for this section and defines emergency power supply, life safety systems and unit equipment in accordance with the terms in the National Building Code of Canada.


The section is divided into 4 parts:

• general rules, which applies to all emergency power supplies and unit equipment
• emergency power supplies
• unit equipment
• exit signs


General


Rule 46-100 specifies that an emergency power supply, including unit equipment, must have adequate capacity for all the equipment that is connected to it in case of a normal power failure.
Rule 46-102 requires that complete instructions for operation, care and monthly testing be posted, under glass, and on the premises, in conformance with the National Building Code of Canada.
Rule 46-104 states that, where batteries are used as the emergency power supply, they must be maintained in proper condition and fully charged.
Rule 46-106 specifies that emergency lights must be on a dedicated emergency circuit, with no other lamps connected to it, and need to be arranged so that the area covered is illuminated even if any one lamp fails.
Rule 46-108 outlines the wiring method for all conductors, with a few exceptions as noted below, required for life safety systems, emergency power supplies, exit signs, and between unit equipment and remote lamps. In addition to the methods outlined in this rule, the National Building Code of Canada or provincial building codes must be referenced for additional requirements for fire protection of conductors that may apply. For additional information see Appendix B and G.

These methods include:
• metal raceway of the totally enclosed type
• cable having a metal armour or sheath
• rigid non-metallic conduit
• electrical non-metallic tubing imbedded in at least 50mm of poured concrete or masonry

Exceptions to this rule include:
• conductors installed in buildings of combustible construction where rules 12-506 to 12-520 apply and may be run as NMSC or in totally enclosed non-metallic raceway
• use of flexible cord and attachment plug for unit equipment in accordance with Rule 46-304(3)
In addition, the above noted conductors must be kept separate from all other conductors and equipment, with the exception of transfer switches and exit and emergency lights with two sources of supply. Also, the supply for any other electrical equipment that is not part of the “life safety system” must not enter any busway, splitter, or other enclosure that is part of the emergency power supply as per rule 46-208.
Emergency power supply
Rule 46-200 notes that Rules 46-202 to 46-212 apply only to central standby power sourced emergency power supplies.

Rule 46-202 outlines that emergency power supplies, in conformance with the National Building Code of Canada, must consist of:
• an automatically rechargeable storage battery with sufficient capacity to maintain at least 91% of full load voltage for a minimum of 30 minutes, or
• an automatically and failure-free starting and transferring generator conforming to CSA C282 with sufficient capacity to carry the full load of the emergency power supply

Note that where storage batteries are used they should not be automobile or lead acid batteries unless they are of the totally enclosed glass-jar type, except by special permission granted under rule 2-030.
Rule 46-204 reaffirms that all power, control and communication conductors required for emergency power supply and installed outside the generator room, must, as per the requirements of the National Building Code of Canada, be protected against fire exposure to maintain continued operation.

Rule 46-206 specifies that an automatic transfer switch, solely accessible to authorized persons, that actuates upon failure of the normal power supply, must control the emergency power supply. Where an area is adequately illuminated by daylight and artificial light is only needed at night, an automatic light-actuated device may be used to control emergency illumination separately in this area.

Rule 46-208 requires that the overcurrent protection for an emergency power supply needs to be coordinated with OC devices, for feeders and circuits supplying life safety and other emergency power supply equipment, to provide selective operation in the event of a fault. These overcurrent devices must be accessible to authorized persons only.

Rule 46-210 outlines that all emergency power supplies need to be equipped with audible and visual trouble signal devices that
• warn of the normal source current failure
• indicate exit signs or life safety systems are supplied from the emergency power supply
• are wired so that they can be silenced, but continually show a red warning or trouble light
• when the system is returned to normal, continue to audibly indicate the need to restore or automatically reset the silencing switch to normal

Rule 46-212 specifies that remote lamps, located some distance from the power supply, must have a voltage drop limited to 5% of applied voltage.

Unit equipment
Rule 46-300 outlines that Rules 46-302 to 46-306 apply to unit equipment for emergency lighting only, as defined in Appendix B.
Rule 46-302 requires the bottom enclosure of unit equipment to be mounted at least 2 meters above the floor where practicable. Note that the definition of practicable includes the synonym “feasible”.

Rule 46-304 specifies the requirements that the supply connections for unit equipment include:
• permanent connection, if the voltage exceeds 250 volts or 24 amps
• flexible cord and attachment plug located 2.5 metres above the floor and within 1.5 metres of the unit equipment, where the ratings above are not exceeded
• automatic actuation upon failure of the normal lighting power supply to the area covered
Rule 46-306 provides the requirements for remote lamps to unit equipment and requires that
• the voltage drop of conductors be limited to 5% of the marked output voltage of the unit equipment
• remote lamps be included in the list of lamps provided for that unit
• the number of lamps connected to a single unit not exceed the power output rating of the unit for the duration of the emergency period
Exit signs

Rule 46-400 requires that exit signs be
• connected to a dedicated circuit, except where connected to a circuit supplying emergency lighting in the same area
• illuminated by an emergency power supply, where emergency lighting is required by the National Building Code of Canada. Note that the NBC requires that exit signs be illuminated continuously, so no switch, time clock, or other disconnecting means may be inserted in the circuit


In the next instalment, we will be discussing Section 50 — Diagnostic Imaging Installations. (Note: Sections 48 and 50 have been deleted in the 23rd Edition)
* The source for this series of articles is the Canadian Electrical Code, Part I, published by CSA
** Note the CEC Handbook is also published by CSA.

William (Bill) Burr is the former Chair of the Canadian Advisory Council on Electrical Safety (CACES), former Director of Electrical and Elevator Safety for the Province of BC, and former Director of Electrical and Gas Standards Development and former Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting billburr@gmail.com.

 

 

Changing Scene

  • Prev
 Canada’s National Electrical Trade Council (NETCO) is pleased to announce that IDEAL ...
The Government of Saskatchewan is engaging the public to help ensure health and safety legislation ...
Despite electrical shock being a serious and potentially dangerous event, it is frequently ...
Acuity Brands, Inc. has announced its Care222® filtered far-UVC module with patent-pending ...
LEDVANCE, the makers of SYLVANIA general lighting in the United States and Canada, recently ...
The federal governemnt launched a Call for Proposals under the new Apprenticeship Service, to ...
ECAO and OEL are working on obtaining more contractor experiences with the ESA permit system. ...
Agents of Change is an event for stakeholders from Canada's electricity and beyond to build ...
Schneider Electric is introducing a personalized digital experience for logged in customers ...
Teledyne Technologies Incorporated announced the successful completion of the acquisition of FLIR ...


 

SaskatchewanThe Government of Saskatchewan is engaging the public to help ensure health and safety legislation meets the needs of employers and workers in the province. From August 16 to October 18, 2021 citizens can provide input on part III (occupational health and safety) of The Saskatchewan Employment Act.

"Our province has a plan for growth that includes ensuring we have safe and healthy workplaces" Labour Relations and Workplace Safety Minister Don Morgan said. 

 


Read More


 

Canadian Electrical Contractor Discussion Group: Can You Count the Deficiencies?

EIN CECD 400Have you ever been called to fix the work of a 'handyman'?

"Was supposedly done by a"certified ' electrician....told the homeowner that he got a $266 permit....no record at TSBC. Can you count the deficiencies?"

"There is a second panel change in the triplex also.......even more deficiencies. Think the guy was a glorified handyman. Ones not obvious: 240 BB heat hooked up 120....drier on 2p20....range on 2p50....water heater fed with 2c14 Bx on 2p15."

Go HERE to join the discussion

 


 

Latest Articles

  • Prev
In 2018, the Canadian Electrical Code (CE Code) was revised so that liquid-tight flexible metal ...
The CSA Z462 Workplace electrical safety Standard published its 2021 Edition in January.  ...
In just 18 months, our industry has seen businesses locked down and borders closed. Lead times ...
 Rule 42-000 Scope – states that Section 42is a supplementary or ...
This summer EiKO is launching its Z10 product offering. I know, what is Z10 other than the sports ...
Steven Lupo, Managing Director of Trilliant Canada says this is a critical time for utilities as ...
As electronic components become increasingly smaller and are positioned closer together in the ...
It could be argued that we have planned cities and constructed buildings to support human health ...
The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the ...
IEEE 1584.1 Guide for Specification of Scope and Deliverable Requirements for an Arc-Flash ...


 

Desert HomeA combination of stunning design, a spectacular desert setting, and exceptional architectural lighting is a winning combination for a private residence just outside of St. George, Utah. JRC Lighting was hired by the homeowner to create the lighting concept for the showpiece home.

"The house has an almost industrial look to it, with a focus on clean lines," said Kevin Meredith, principal at JRC Lighting. "My goal was to keep the lighting understated and let the architecture, and the views, sell themselves.”

 

Read More


 

 

David GordonBy David Gordon

This summer EiKO is launching its Z10 product offering. I know, what is Z10 other than the sports cars some of us remember (’69 Z10 Camaro or a 2009 BMW Z10, but let’s go with an American muscle car!)?

So, since it seemed like a sports car “name” (since sports car naming seems to be in numbers), we reached out to Sarah Eastman, VP Marketing for EiKO, who shared that Z10 is an alliance of manufacturers who have developed standards to support an easier lighting controls process within fixtures (remember, I’m not a product maven).
Read More


 

AMIBy Blake Marchand

Steven Lupo, Managing Director of Trilliant Canada says this is a critical time for utilities as the industry shifts towards more-connected technologies.

“Of course, anyone in the municipal services industry would comment that there’s always some form of disruption and challenge going on from various factors,” he said. However, the utility sector is on its way toward the second technological wave of Advanced Metering Infrastructure (AMI). Similar to Industry 4.0 in industrial and manufacturing sectors, AMI 2.0 represents the implementation of edge computing, cloud services, IT, and software data analytics...

Read More


 

 

Milwaukee M12 Cable StripperM12™ Cable Stripper Kit for Cu THHN / XHHW aims to improve the cable stripping experience. With no exposed blades, the cordless cable stripper provides safer stripping than with a knife. The cable stripper's compact, right-angle design allows you to maneuver it more easily in tight spaces with less strain on the wrist. The bushing design and adjustable depth gauge deliver cleaner, more accurate and consistent strips across all sizes.

The cable jacket stripping tool is not only compatible with all MILWAUKEE® bushings but is also compatible with competitive quick-change bushings.

 

Read More


 

 

Incoplas HybridThe Incoplas® LED Hybrid is a durable multi-purpose and corrosion-resistant LED lighting solution that can be used in heavy industrial applications where hazardous location lighting is required.

Certifications

Class 1:

Flammable Gases and Liquids

Division 2: The hazardous atmosphere is only available infrequently (i.e. in case of spill).

 

Read More


 

 

EarthTronics 25-Watt Emergency Driver for Linear HighbayEarthTronics LED emergency drivers regulate the power supplied to the LED fixture so that it can operate as a light source in the event of a power failure. The purpose of emergency lighting is to ensure that lighting is provided promptly, automatically and for a suitable time when the normal power supply fails.

This insures that people within the building can evacuate safely in the event of an emergency. All EarthTronics emergency drivers meet specific UL, CSA and NFPA requirements. Always consult local code requirements when specifying emergency lighting products.

Read More


 

Peers & Profiles

  • Prev
As of February 2021, Martin Stephenson is the new President and CEO of Signify Canada.   ...
This past July, Kerith Richards, who has worked for Service Wire Company for the last seven years, ...
EngWorks was formed in 2004 as an electrical engineering and consulting firm by Allan Bozek, “After ...
Headquartered in Concord, Ontario, Mercury Lighting services national retail, ...
Among the recipients of the 2021 Clean50 Awards announced last month is Carolina Gallo, Vice ...
Sarah Silverstein is a principal with Liteline along side her two brothers Mark and Daniel. ...
As a 34-year-old female owner of an electrical contracting business, Danielle Gray may be unique. ...
Mark Klein is Co-President of Klein Tools, managing Sales & Marketing activities, alongside ...
Bryan Smith started his now 20-year career at the ground floor, so to speak, as a draftsperson and ...
From small construction to sophisticated industrial projects, House of Electrical Supplies has been ...


EngWorksBy Blake Marchand

EngWorks was formed in 2004 as an electrical engineering and consulting firm by Allan Bozek, “After a short time we realized there was a niche in hazardous locations, in particular in hazardous area classification design requirements for various facilities. And also helping people understand just how the Canadian Electrical Code applies to hazardous locations.”

Given the complexity of hazardous locations, Bozek saw a need for education while working in the field and began developing training courses designed.

Read More


 

 

Eric TordjmanBy Blake Marchand

Headquartered in Concord, Ontario, Mercury Lighting services national retail, multi-residential/commercial property management, energy service companies (ESCO), and auto dealerships. “From design to specifications, we offer turn-key services that go beyond the typical distributor model,” explained Mercury Lighting Vice President, Eric Tordjman. Their value-added approach leverages well-established supplier relations to help clients find a lighting solution that suits their needs.

“How we differentiate ourselves is we’re lighting specific, we do very little in the way of electrical, and really emphasizing our expertise towards solutions selling...

Read More


 

Copper $US Dollar price per pound

Kerrwil Publications Great Place to Work. Certified December 2019 - December 2020

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2021 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil