Test Your Knowledge of the Canadian Electrical Code – Part 1 — The Answers: Fire Alarm Systems

EIN Code Quiz2 400

June 11, 2021

In the last installment, you had the opportunity to answer our questions about the Code and best practices. Here are the answers to those questions.

Fire Alarm Systems, Smoke and Carbon Monoxide Alarms, and Fire Pumps

Q: What rule specifies the requirements for insulated conductors and cables in fire alarm systems and what are the requirements?

A: Rule 32-100 specifies the requirements for insulated conductors and cables in fire alarm systems which include:

  • copper material
  • ampacity
  • use of optical fiber cables
  • use of stranded conductors
  • insulation rated at 300 volts
  • determining wire size for raceways or integral assemblies
  • selection in accordance with rules 12-102(3)or 12-122(1)

Q: What rule requires that no disconnecting means, overcurrent protection or device capable of interrupting the fire pump circuit may be placed between the service box from the normal power supply and the fire pump transfer switch or controller, except?

A: Rule 32-306 requires that no disconnecting means, overcurrent protection or device capable of interrupting the fire pump circuit may be placed between the service box from the normal power supply and the fire pump transfer switch or controller:

  • Except a circuit breaker that is permanently labeled identifying it as a fire pump disconnect.
  • In addition, the circuit breaker must be lockable in the closed position and may be in the separate service box as in Rule 32-304

Q: In the case where this circuit breaker is installed in an emergency power supply circuit between the emergency power source and the fire pump transfer switch, the rating of the circuit breaker shall be?

A: As per rule 28-200:

  • Be set or rated to not less than the rating of the overcurrent protection provided integral with the fire pump transfer switch
  • Indefinitely carry the locked rotor current of the fire pump
  • Where it is installed in a normal supply circuit be rated not less than the overcurrent protection of the fire pump controller
  • Where the circuit breaker is installed in an emergency supply feeder between the emergency generator and the fire pump transfer switch, the feeder must bypass the generator main circuit breaker and be connected directly to the emergency generator.

Go HERE to discuss

Related Articles


Latest Articles


Changing Scene

  • Electrozad Welcomes Jason McFarland as Windsor Branch Account Representative

    Electrozad Welcomes Jason McFarland as Windsor Branch Account Representative

    December 2, 2022 Jason McFarland joins Electrozad as an Account Representative at their #Windsor branch and will be a key point in developing relationships and accounts focused on Industrial Manufacturing/OEM’s. Jason studied advertising at St. Clair College and holds several Sales Certifications. He brings with him several years experience as a marketing coordinator and sales account manager. “My… Read More…

  • Southwire’s Latest Copper Rod Plant in Carrollton, Ga. Nears Completion, Production to Boost by Roughly 10% Annually

    Southwire’s Latest Copper Rod Plant in Carrollton, Ga. Nears Completion, Production to Boost by Roughly 10% Annually

    December 2, 2022 As part of more than a billion-dollar modernization commitment across its footprint, Southwire is nearing the completion of construction on a new, state-of-the art copper rod plant in Carrollton, Ga. The new plant replaces an aging, 40-year-old facility and will increase copper rod production by at least 10 percent annually. “Our goal… Read More…

  • Ontario Finalizes Electrification and Energy Transition Panel

    Ontario Finalizes Electrification and Energy Transition Panel

    December 2, 2022 Ontario is planning for the long-term reliability and affordability of the province’s clean energy supply by appointing the remaining members of the Electrification and Energy Transition Panel. Recently, the province appointed Dr. Monica Gattinger and Chief Emeritus Emily Whetung, former Chief of Curve Lake First Nation, to the Panel, where they join… Read More…

  • Skills Ontario’s Jennifer Green Win’s Apprenticeship Award

    Skills Ontario’s Jennifer Green Win’s Apprenticeship Award

    December 2, 2022 Skills Ontario is pleased to support the Colleges Ontario Premier’s Awards and congratulate Jennifer Green for winning the Apprenticeship Award at the annual Higher Education Summit in Toronto on Monday. There were 126 nominees in total across seven categories. As the only woman in her Industrial Mechanic Millwright program at Conestoga College,… Read More…