Guide to the Canadian Electrical Code, Part I — Instalment 50

Bill Burr

June 5, 2019

By William (Bill) Burr

The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the information you need. This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook** but will hopefully provide some help in navigating, while reading the code. The 24th Edition of the CE-C, Part I, (C22.1-18)* is now available from CSA Group.

Annex J18 is optionally permitted for use in additions, modifications, renovations or operation and maintenance of existing facilities employing the Division system of classification. The rules of Annex J18 are normative (mandatory) where used and amend or supplement other requirements of the Code. Additional informative (non-mandatory) information is contained in Annex JB. Due to the size of this Annex, it is discussed in multiple parts. This is the final Part E – Class III, Division 2 locations.

Class III, Division 2

Rules J18-350 to J18-378 apply to installations in Class III, Division 2 locations in which ignitable fibres or flyings are stored or handled.

Rule J18-350 requires equipment installed in Class III, Division 2 to be in accordance with Table 18.

Rule J18-352 requires that transformers and capacitors installed in these locations conform to Rule J18-252, which states that

• transformers and electrical capacitors containing a flammable liquid be installed in electrical equipment vaults in accordance with Rules 26-350 to 26-356

• transformers and electrical capacitors not containing a flammable liquid be installed in electrical equipment vaults as above, or marked for use in Class II locations

• dry-core transformers be installed in electrical equipment vaults in accordance with Rules 26-350 to 26-356, and have winding and terminal connections enclosed in non-ventilated tight housings and operate at a maximum of 750 volt

Rule J18-354 outlines wiring methods, in Class III, Division 2 locations and requires

• threaded rigid metal conduit

• hazardous location cables

• electrical metal tubing

• armoured cable with overall jacket, such as TECK90, ACWU90, copper-sheathed RC90, or aluminum-sheathed RA90

• control and instrumentation cables with an interlocking metallic armour and a continuous jacket in control circuits (Type ACIC)

• Type TC cable installed in cable tray in accordance with Rule 12-2202

• Type CIC cable (non-armoured control and instrumentation cable) installed in cable tray in accordance with the installation requirements of Rule 12-2202 (2), providing the cable is rated 300V and the circuit voltage is 150 V or less and 5 A or less

• liquid-tight flexible metal conduit and connectors, marked for heavy duty

Rule J18-356 requires that switches, controllers, circuit breakers, and fuses in Class III, Division 2 locations be provided with a Type 5 enclosure or have close-fitting covers to prevent the escape of sparks or burning material.

Rule J18-358 requires that transformers, impedance coils, and resistors used as or in conjunction with control equipment for motors, generators, and appliances in Class III, Division 2 locations comply with Rule J18-308, which states that

• they be provided with enclosures conforming to Rule J18-258, and tight housings without ventilating openings, where not located in the same enclosure

• resistors and resistance devices have dust-tight enclosures marked for use in Class II locations, except when these devices are in the same enclosure with switching devices of the control equipment and are used only for starting or short-time duty, in which case the enclosure may conform to the requirements of Rule J18-306

Rule J18-360 requires that motors and generators and other rotating machinery installed in Class III, Division 2 locations conform to Rule J18-310.

Rule J18-360 applies to motors, generators, and other rotating electrical machinery installed in Class III, Division 2 locations and requires that

• they be totally enclosed non-ventilated, totally enclosed pipe-ventilated, or totally enclosed fan-cooled

• where only moderate accumulations of lint and flyings are likely to collect on, or in the vicinity of, a rotating electrical machine and the machine is readily accessible for routine cleaning and maintenance, be

     o standard open-type machines without sliding contacts or centrifugal or other types of switching mechanisms, including motor overload devices

     o standard open-type machines that have contacts, switching mechanisms, or resistance devices enclosed within tight housings without ventilating or other openings

     o self-cleaning textile motors of the squirrel-cage type

• motors, generators, or other rotating electrical machinery of the partially enclosed or splash-proof not be installed in Class III locations

Rule J18-362 outlines that every vent pipe for a motor, generator, other rotating electrical machine or enclosure for electrical equipment in Class III, Division 2 locations

• be dust-tight throughout its entire length

• lead directly to a source of clean air outside a building

• be metal not less than 0.52 mm (No. 24 MSG) thick or equally substantial noncombustible material

• be screened at the outer end

• have protection against mechanical damage and corrosion

Rule J18-364 requires that fixed or portable utilization equipment be marked for use in Class III locations, motors of motor-driven utilization equipment conform to Rule J18-310, and enclosures for switches, circuit breakers, and fuses conform to Rule J18-306.

Rule J18-366 requires that luminaires in Class III, Division 2 locations conform to Rule J18-316, which states that

• luminaires and portable lighting be complete assemblies marked for use in Class III locations and have the maximum wattage clearly marked

• each luminaire be protected against physical damage by a suitable guard or by location

• pendant luminaires be suspended by and supplied through threaded rigid conduit stems, and threaded joints be provided with set screws or other effective means to prevent loosening, and for stems longer than 300 mm, provided with permanent and effective bracing against lateral displacement at a level not more than 300 mm above the lower end of the stem, or flexibility in the form of a suitable fitting or flexible connector situated not more than 300 mm from the point of attachment

• luminaires be supported by boxes, box assemblies, and fittings marked for use in Class III locations

• starting and control equipment for mercury vapour and fluorescent lamps comply with Rule J18-308

Rule J18-368 requires that flexible cords be extra-hard usage type, contain a bonding conductor and be provided with glands marked minimally for use in Class II, Division 1 locations, where entering a a box or fitting required to be dust-tight.

Rule J18-370 specifies that receptacles and attachment plugs be a polarized type that affords automatic connection to the bonding conductor of the flexible supply cord; and be designed so that the connection to the supply circuit cannot be made or broken while live parts are exposed.

Rule J18-372 requires that

• signal, alarm, remote control, and communication systems, meters, instruments and relays contacts that interrupt other than voice currents be provided with a Type 4 or 5 enclosure or have close-fitting covers to prevent the escape of sparks or burning material

• the windings and terminal connections of transformers and choke coils carrying other than voice currents be provided with tight enclosures without ventilating openings

• resistors, resistance devices, thermionic tubes, and rectifiers carrying other than voice currents and exceeding 120 0 C, be provided with Class II dust-tight enclosures

Rule J18-374 requires that electric cranes, hoists, and similar equipment in Class III, Division 2 locations be installed as prescribed by Rule J18-324, which outlines the installation requirements where installed for operation over combustible fibres or accumulations of flyings, travelling cranes and hoists for material handling, travelling cleaners for textile machinery and similar equipment, and requires they conform to the following:

• the power supply to contact conductors be isolated from all other systems, ungrounded, and equipped with recording ground detection equipment that will give an alarm and will automatically de-energize the contact conductors in case of a fault to ground or provide a visual and audio alarm, maintained until the ground fault is cleared

• contact conductors be located or guarded and inaccessible to other than authorized persons and protected against accidental contact with foreign objects

• current collectors be arranged or guarded to confine normal sparking and prevent escape of sparks or hot particles, provide two or more separate surfaces of contact for each conductor to reduce sparking, and keep contact conductors and current collectors free of lint or flyings

• control equipment comply with Rules J18-306 and J18-308

Rule J18-376 specifies that storage-battery charging equipment for Class III, Division 2 locations be located in separate well ventilated rooms built or lined with non-combustible materials constructed to exclude flyings or lint.

Rule J18-378 outlines that other equipment marked with EPL Da, Db, or Dc protection may be installed in a Class III, Division 2 location with a temperature class not greater than T120 °C for equipment that may be overloaded, and not greater than T165 °C for equipment not subject to overloading.

In the next instalment, we will be discussing Annex J20 – Flammable Liquid and Gasoline Dispensing Service Stations, Garages, Bulk Storage Plants, Finishing Processes and Aircraft Hangers in the Class and Division System of Hazardous Locations Classification.

* The source for this series of articles is the Canadian Electrical Code, Part I, (C22.1-18) published by CSA.

** Note the CEC Handbook is also published by CSA.

William (Bill) Burr is the former Chair of the Canadian Advisory Council on Electrical Safety (CACES), former Director of Electrical and Elevator Safety for the Province of BC, and former Director of Electrical and Gas Standards Development and former Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting billburr@gmail.com.

 

Related Articles


Latest Articles

  • Take the Lesson

    Take the Lesson

    September 2, 2024 By Keith Sones, seasoned utility industry executive “I really don’t want to do this.” “You have to Keith. You have no choice. You can’t leave him hanging” replied my wife. I stared at the phone like a child looks at liver on their plate. They know you have to eat it but also… Read More…

  • Quebec Drives the Growth in Residential Building Construction in June, 2024

    Quebec Drives the Growth in Residential Building Construction in June, 2024

    Investment in building construction grew 2.8% to $21.4 billion in June, after a slight increase of 0.8% in May. These increases partly reflect April’s record high of $13.4 billion in total building permits value, since investment levels for a given period are driven by permits issued in prior months. The June increase in investment in building construction was primarily… Read More…

  • Western Memorial Regional Hospital Sets New Infrastructure Precedent and Receives LEED Silver Certification 

    Western Memorial Regional Hospital Sets New Infrastructure Precedent and Receives LEED Silver Certification 

    August 16, 2024 The new Western Memorial Regional Hospital in Corner Brook is home to Canada’s largest geothermal system, which has set a precedent for modern infrastructure for both Newfoundland and Labrador and North America. The geothermal field is approximately 600 feet below the hospital’s parking lot, and provides 100 per cent of the ground… Read More…

  • Brightening Communities: LED Technology in Action

    Brightening Communities: LED Technology in Action

    August 15, 2024 By Alex Price, Brand & Planning Manager, Current LightingTechnical Contributor: Gary Steinberg, Senior System Manager (Outdoor LED Fixtures), Current Lighting As the landscape of Canadian cities continues to evolve, the importance of outdoor lighting cannot be overstated. From enhancing public safety to promoting economic activity and fostering a sense of community, well-planned… Read More…


Changing Scene

  • Schneider Electric Launches SMART Buildings Division to Drive Sustainable Building Innovation in Canada

    Schneider Electric Launches SMART Buildings Division to Drive Sustainable Building Innovation in Canada

    Schneider Electric is transforming its Digital Buildings business in Canada with the launch of the SMART Buildings Division. This evolution marks a strategic move to deliver comprehensive solutions and services that support building owners and operators in achieving their decarbonization and sustainability goals. The demand for smart buildings is surging, driven by a global shift… Read More…

  • Introducing Alan Bearden as Interim President of Southwire Canada

    Introducing Alan Bearden as Interim President of Southwire Canada

    September 4, 2024 Southwire Canada is pleased to announce that Alan Bearden has been appointed Interim President. In this role, Alan will provide leadership and guidance for Southwire’s Canada-based organization, ensuring continuity and driving growth during this transitional period. Alan Bearden brings a wealth of experience to the position, having joined Southwire in 2008. Over… Read More…

  • A Partnership Between Electromag Graybar Canada and Phoenix Contact

    A Partnership Between Electromag Graybar Canada and Phoenix Contact

    September 3, 2024 Electromag Graybar Canada, a pioneer in industrial automation solutions and pneumatic products, is excited to announce a partnership with Phoenix Contact, a global leader in electrification, networking, and industrial automation. This collaboration, which initially began in the Langley and Ontario branches, is now expanding to Quebec. The alliance aims to provide cutting-edge… Read More…

  • Sonepar Announces the Retirement of William (Bill) C. Smith, Electrozad Director of Transitional Business

    Sonepar Announces the Retirement of William (Bill) C. Smith, Electrozad Director of Transitional Business

    September 2, 2024 William (Bill) C. Smith, Director, Transitional Business of Electrozad Supply Company Limited announced his retirement as of August 30th, 2024 after 49 years of leadership. Bill began his electrical career working part-time at Electrozad Supply while completing a Sales & Marketing Program at St. Clair College.  After his first full-time position in… Read More…