STANDATA: Smoke Detectors in Smoke or Fire/Smoke Damper Installation

October 21, 2024

Purpose:

Clarifies whether the National Building Code – 2023 Alberta Edition (NBC(AE)) requires a smoke detector as part of a smoke or fire/smoke damper operation to be connected to the fire alarm system (FAS).

Discussion

In accordance with Sentence 3.1.8.11.(3) smoke damper and combination smoke/fire dampers must be configured to close automatically upon a signal from an adjacent smoke detector.

The requirements specified in Sentence 3.1.8.11.(3) pertain exclusively to the location of the smoke detector. This provision does not require adhering to any additional fire alarm system requirements. The smoke detector mentioned here is meant to operate as part of the damper system and is not intended to connect to or require the need for a FAS.

As per NBC(AE) Sentence 3.1.8.5.(3) smoke dampers must conform to NFPA 105, Article 6.3.2.4.

Where smoke detectors are used to control smoke dampers or fire/smoke dampers the detectors are required to comply with NFPA 72.

The confusion may stem from the definition of a smoke detector in the NBC(AE) where it is defined as a type of fire detector. A fire detector is defined as a device that sends a signal, to the fire alarm system.

Although the NBC(AE) provides a definition for a fire detector, there are no mandated requirements for a smoke detector serving a smoke damper or combination smoke/fire damper to send a signal to the FAS.

Go HERE for the full Bulletin

Related Articles


Latest Articles


Changing Scene

  • Delta Transformers Appoints New Representative in Ontario

    Delta Transformers Appoints New Representative in Ontario

    October 8, 2026 Delta Transformers, a Canadian manufacturer of dry-type transformers, is pleased to announce the appointment of Spectrum Power Systems as their new representative in Ontario, Canada, effective October 1st, 2026. For over 27 years Spectrum Power Systems has been representing leading electrical manufacturers throughout Ontario. The company has a strong presence in the… Read More…

  • Former Electrical Contractor Principal Arrested Following ESA Referral to Police

    Former Electrical Contractor Principal Arrested Following ESA Referral to Police

    October 8, 2026 Arrest follows ESA licence revocation, $70,000 in previous fines and new electrical safety charges   Peel Regional Police recently arrested Rahyl Hassan, principal of former Licensed Electrical Contractor, Strak Holdings Inc., following an investigation in which the Electrical Safety Authority (ESA) cooperated with police.  ESA referred concerns about potential criminal activity to Peel… Read More…

  • Federal Government Announces $2 billion Investment to Deliver One Million Home Retrofits Across Canada

    Federal Government Announces $2 billion Investment to Deliver One Million Home Retrofits Across Canada

    October 8, 2026 The federal government has announced a $2 billion investment to deliver one million home retrofits across Canada. These energy-efficient retrofits will lower heating costs for Canadians and reduce emissions. First, they are launching a new National Heat Pump Rebate to help up to 820,000 households make the switch to more efficient electric heat pumps: Heat pumps… Read More…

  • FCM and the Government of Canada Announce $66.3 M in 162 Energy Efficient Housing Projects

    FCM and the Government of Canada Announce $66.3 M in 162 Energy Efficient Housing Projects

    September 8, 2026 Funding supports homeowners and affordable housing providers in reducing energy costs and improving quality of life, while adding jobs to communities coast-to-coast  The Government of Canada and the Federation of Canadian Municipalities (FCM) today announced that $66.3 million in funding has been approved for 162 energy efficiency projects across the country. The… Read More…