Guide to the Canadian Electrical Code, Part 1[i], 26th Edition– A Road Map: Section 68 — Pools, Tubs, and Spas

August 10, 2026

By William (Bill) Burr

The Code is a comprehensive document. Sometimes it can seem quite daunting to find the information you need quickly. This series of articles provides a guide to help users find their way through this critical document. These articles do not intend to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook* but hopefully provide help to navigate the Code.

Section 68 — Pools, Tubs, and Spas (The 25th Edition of the CEC, Part I, (C22.1-24) * is now available from CSA Group. This discussion of Section 68 is based on this edition.)

Section 68

Rule 68-000 Scope notes that this is a supplementary or amendatory section of the code and applies to the electrical installation of pools, electrical equipment associated with pools and metal accessories in or within 3 m of a pool, and includes permanently installed and storable swimming pools, hydromassage bathtubs, spas, and hot tubs, wading pools, baptismal pools, decorative pools, and splash pads.

Section 68 is divided into 5 parts – General, Permanently Installed Swimming Pools, Storable Swimming Pools, Hydromassage Bathtubs, and Spas and Hot Tubs.

General

The general requirement Rules 68-050 to 68-070 apply to the installation of all equipment included under this Section.

Rule 68-050 Special terminology contains definitions of several special terms used in this section – conductive pool shell, decorative pool, dry-niche luminaire, forming shell, hydromassage bathtub, leakage current collector, permanently installed swimming pool, spa or hot tub, splash pad, storable swimming pool, and wet-niche luminaire and. Thorough knowledge of these definitions is necessary to follow the correct rules for each type of device.

Rule 68-052 Electrical wiring or equipment in pool walls or water prohibits the installation of any electrical wiring or equipment in the walls or water of a pool except in accordance with the rules of this Section 68.

Rule 68-054 Overhead wiring prohibits locating of a pool under or near overhead wiring and provides requirements for or prohibits the installation of electrical wiring in:

  • pool walls or water,
  • overhead or near the pool including:
    • elevated or adjacent associated diving, slide, swing, observation stand, tower, or platform surfaces, or
    • above the adjacent area extending 5 meters horizontally from the pool edge.

Exceptions are for:

  • insulated communication and antenna distribution cables,
  • neutral supported cables not exceeding 1000 V, provided there is a clearance of 5 m,
  • cables operating up to 50 kV, provided there is a clearance of 7.5 meters (Appendix B has a diagram illustrating these clearances).

Rule 68-056 Underground wiring provides minimum horizontal separations, as per Table 61, of underground cables and insulated conductors in a raceway, except for bonding conductors or Class A GFCI-protected electrical equipment supply conductors.

Rule 68-058 Pool bonding

  • The metal parts of the pool and of other non-electrical equipment associated with the pool, such as piping, pool reinforcing steel, ladders, diving board supports, and conductive infrastructure within 1.5 m of the pool, must be bonded together and to non-current-carrying metal parts of electrical equipment such as decorative-type pool luminaires and lighting equipment not located in a forming shell, forming shells, metal screens of shields for underwater speakers, conduit, junction boxes, and similar electrical equipment by a copper bonding conductor.
  • Bonding conductors for pools must be copper and a minimum of No. 6 AWG.
  • Pool deck and other perimeter surfaces must be bonded by means of
    • bonding the unencapsulated, conductive structural reinforcing steel with a minimum of four connections equally spaced around the perimeter;
    • a copper grid constructed
      • of minimum No. 6 AWG bare copper conductors bonded to each other using suitable connectors at all points of crossing;
      • of conductors in an arranged network of a 300 mm by 300 mm uniformly spaced grid pattern with a tolerance of 100 mm; and
      • such that the grid extends horizontally, 1.5 m from the outside of the pool shell, below grade at a depth of 100 mm to 150 mm to form a continuous 1.5 wide shield around the pool circumference; or
    • for spa or hot tub installations, a copper ring
      • consisting of a bare copper conductor of a minimum No. 6 AWG; and
      • constructed such that securement around the pool is made 450 mm to 600 mm from the outer contour of the pool shell at a depth of 100 mm to 150 mm below grade.
  • Conductive pool shells must be bonded by means of
    • bonding the unencapsulated, conductive structural reinforcing steel with a minimum of four connections equally spaced around the perimeter;
    • a continuous metal pool shell made up of individual panels securely bolted or welded together and bonded in at least one location; or
    • a copper grid constructed
      • of minimum No. 6 AWG bare copper conductors bonded to each other at all points of crossing;
      • of conductors in an arranged network of a 300 mm by 300 mm uniformly spaced grid pattern with a tolerance of 100 mm; and
      • such that securement around and under the pool is made around and under the pool no more than 150 mm from the outer contour of the pool shell.
  • Metal sheaths and raceways must not be relied upon as the bonding medium, and a separate copper bonding conductor must be used, except that a metal conduit between a forming shell and its associated junction box is permitted to be used as the bonding medium, provided that the forming shell and junction box are installed in the same structural section.
  • The bonding conductor must be run to the panelboard supplying pool electrical equipment and, if smaller than No. 6 AWG, must be installed and mechanically protected in the same manner as the insulated circuit conductors or cable.
  • Where none of the bonded parts referred to above are in direct contact with the pool water, a corrosion-resistant conductive surface that exposes not less than 58 cm² of surface area to the pool water at all times must be installed.
  • The corrosion-resistant conductive surface described above must
    • be located where it is not exposed to physical damage or dislodgment during normal pool    use; and
    • be connected to any of the pool infrastructure described above by a No. 6 AWG             copper bonding conductor.

Rule 68-060 Junction and deck boxes provides requirements for the installation of junction and deck boxes and specifies that they:

  • may be submerged in decorative pools, provided they are marked for that usage,
  • may be installed on the supply side of conduits extending to forming shells, if suitable for the purpose,
  • have provisions for independently terminating three bonding conductors inside the box with the external No. 6 AWG that is run to the panelboard,
  • contain only insulated conductors used exclusively to supply the underwater equipment,
  • provide continuity between every metal conduit and bonding terminal with a copper, brass, or similar corrosion-resistant metal integral with the box,
  • be installed above the normal water level of the pool, above the finished level of the pool deck, so that it is not an obstacle, and so that water drains away from the box, and
  • that conduit is water-tight with packing seals around cord entries to prevent water penetration.

Rule 68-062 Transformers and transformer enclosures requires that these

  • be located a minimum of 3 m from the inside wall of a pool or separated by a fence, wall, or another permanent barrier, preventing accessibility to persons in the pool area,
  • have any metal shield between the primary and secondary windings of a transformer bonded to ground,
  • for audio isolation transformers, be:
    • connected between the audio output terminals of each amplifier and any loudspeaker, located within 3 m of the pool wall,
    • located in or adjacent to the amplifier, with which they are used, and
    • have an audio output voltage of not more than 75 V rms.

Rule 68-064 Receptacles requires that receptacles be:

  • located more than 1.5 m from the inside walls of a pool,
  • protected with a Class A type GFCI if located between 1.5 and 3 meters from a pool (measured by the shortest path of a power cord without piercing a floor, wall, or ceiling).

Rule 68-066 Luminaires and lighting equipment specifies that:

  • wet-niche or submersible luminaires:
    • be mounted in forming shells, except within a decorative pool, with provision for a suitable connection to the wiring used,
    • be submersed in the pool water at a depth of not more than 600 mm, unless suitable for submersion at a greater depth,
    • operate with the supply voltage of not more than 150 volts,
  • dry-niche luminaires are installed so that the supply voltage is not more than 300v (starting or operating), and that they are accessible from a walkway, service tunnel outside the pool or a closed, drained recess in the pool, for maintenance,
  • metal parts of luminaires in contact with the pool water be brass or other corrosion-resistant material,
  • luminaires, including standards or supports, installed below, or within 3 m of, the pool surface or walls, must be protected by a Class A type GFCI unless separated from the pool by a fence, wall, or another permanent barrier,
  • forming shells be metal and have provision for a threaded connection to a rigid metal conduit unless operating at less than 30 volts.

Rule 68-068 Ground fault circuit interrupters requires that they

  • be installed to protect:
    • electrical equipment placed in the water in the pool,
    • spas and hot tubs,
    • audio amplifiers connected to loudspeakers in the pool water,
    • electrical equipment located within 3 m of the inside of the pool, unless suitably separated by a fence, wall or permanent barrier,
    • receptacles located in wet areas associated with the pool such as locker and change rooms,
  • be permanently connected,
  • be applied to a feeder, a branch circuit, or an individual device,
  • have a warning sign, located beside the circuit switch, advising that it is protected by a GFCI, that should be tested regularly,
  • be installed:
    • in a location that will facilitate testing,
    • at least 3 meters from the water in a pool, spa, or hot tub, and at least 1.5 meters from a hydromassage tub, unless protected by a Class A GFCI which is an integral part of a factory-built spa, hot tub, or hydromassage bathtub, or
    • behind a barrier that prevents an occupant from contacting the GFCI.
  • Where a Class A type GFCI is not available because of the rating of the equipment, an alternate ground fault protection device may be used providing it will clear a ground fault within the time and current values specified for a Class A type GFCI, and all the above requirements will apply.

Rule 68-070 Other electrical equipment requires that:

  • loudspeakers installed beneath the pool surface be connected to isolating transformers by ungrounded wiring, mounted in a recess in the wall or floor of the pool, and enclosed by a separate, rigid, corrosion-resistant metal screen,
  • communication jacks not be installed within 3 m of the inside walls of the pool,
  • communication equipment
    • is separated from the pool area by a fence, wall, or another permanent barrier,
    • or permanently fixed on the wall if within 3 m of the inside walls of the pool,
    • be located at least 1.5 meters from the walls of the pool, 
    • located so that it can’t be used from the pool unless actuated by a cord with an insulating link.

Rule 68-072 Disconnecting means for pool pumps, spas, and hot tubs specifies that

A disconnecting means rated to interrupt the connected load must be provided for each permanently connected pool pump, spa, and hot tub, and must be

  • located not closer than 1.5 m to the inside walls of a pool, spa and hot tub unless behind a permanent barrier that will prevent the occupant of the pool, spa, or hot tub from contacting the device;
  • located outside when the equipment is located outside at a dwelling unit;
  • readily accessible;
  • lockable when not within sight of the pool pump, spa, and hot tub.

Permanently Installed Swimming Pools

Rule 68-100 Wiring method provides that for permanently installed swimming pools:

  • the wiring method between the junction boxes referred to in Rule 68-060 and the forming shell of luminaires, installed below the pool surface, be rigid copper conduit or other corrosion-resistant metal or rigid PVC conduit, and flexible cord for use in wet locations and supplied as a part of the luminaire, or as specified in Section 12,
  • insulated conductors on the load side of each Class A GFCI must be kept independent of other wiring not GFCI protected, and not enter a luminaire, raceway, box, or cabinet occupied by other wiring, except for panelboards that house the GFCI,
  • conduits in the walls and deck of a swimming pool must be installed so drainage is provided.

Storable swimming pools

Rule 68-200 Electrical equipment requires that any electrical equipment associated with storable swimming poolsnot be installed in the pool water or on the pool wall unless suitable for the purpose.

Rule 68-202 Pumps requires that pumps for storable swimming pools be

  • marked for the purpose;
  • be supplied from a permanently installed receptacle located more than 1.5 meters but not less than 7.5 m from the pool wall; 
  • be protected by a Class A GFCI if located within 3 m of the inside walls of the pool, except where separated from the pool area by a fence, wall, or another permanent barrier.

Hydromassage bathtubs

Rule 68-300 General states that Rules 68-302 to 68-308 apply to the installation of permanently connected and cord-connected hydromassage bathtubs.

Rule 68-302 Protection requires that electrical equipment that is an integral part of a hydromassage bathtub be protected by a Class A type GFCI.

Rule 68-304 Control requires that a hydromassage bathtub be controlled by an on-off device located behind a barrier or located at least 1 m horizontally from the wall of the hydromassage bathtub unless it is an integral part of a factory-built hydromassage bathtub.

Rule 68-306 Receptacles for a cord-connected hydromassage bathtub addresses requirements for receptacles where a cord-connected hydromassage bathtub may have one or more power supply cords:

  • each cord and attachment plug must be:
    •  connected to a receptacle that is supplied by at least one branch circuit supplying only receptacles dedicated to the hydromassage bathtub,
    • located at least 300 mm from the floor,
    • inaccessible to the occupant of the hydromassage bathtub.
  • where more than one receptacle is required for the cord-connected hydromassage bathtub, they must be in proximity, and each receptacle must be protected by a Class A type GFCI unless the hydromassage bathtub has an integral GFCI.
  • a warning label must be affixed to the above-specified receptacles warning against the connection of any equipment not associated with the hydromassage bathtub.

Rule 68-308 Other electric equipment requires that electric equipment, not directlyassociated with a hydromassage bathtub comply with other rules of the code governing the installation of equipment in bathrooms.

Spas and hot tubs

Rule 68-400 General states that Rules 68-402 to 68-408 apply to the installation of spas and hot tubs.

Rule 68-402 Bonding to ground requires the metal parts of spas and hot tubs, except rings or bands securing staves of wooden hot tubs, be bonded together and to ground as per rule 68-058.

Rule 68-404 Controls and other electrical equipment provides requirements for the installation of controls and other electrical equipmentfor a spa or hot tub:

  • controls must be located at least 1 meter horizontally from the tub or hot tub unless located behind a barrier, or unless they are an integral part of a factory-built spa.
  • receptacles and luminaires must be installed in accordance with rules 68-064 and 68-066, respectively.
  • for a spa or hot tub installed other than at a dwelling unit, an emergency shut-off switch is required that disconnects the water circulating pump and:
    • is independent of the other controls.
    • is located at a point readily accessible to users, and within sight of and not more than 15 meters away.
    • is conspicuously and legibly identified as the emergency shut-off switch with a permanent label, and activates an audible, visual trouble-signal device giving an immediate warning.

Rule 68-406 requires that leakage current collectors consisting of corrosion-resistant metal tubing with at least 5 times the diameter in length with a corrosion-resistant lug must be:

  • installed in all water inlets and outlets of a field assembled spa or hot tub, or a device providing equal protection as an integral part of a spa or hot tub factory built for field assembly.
  • electrically insulated from the spa or hot tub and bonded to the control panel or the main service ground with a minimum No. 6 AWG copper bonding conductor, or, as per Table 16 if mechanically protected the same as the insulated circuit conductors or cables.

Note that if the only electrical component is a pump marked as an insulated wet end pump, leakage current collectors are not required.

Rule 68-408 requires that field-assembled spas and hot tubs must be installed in accordance with rules 68-402 to 68-406 with individual electrical components such as pumps, heaters, and blowers suitable for use with spas or hot tubs and a means to prevent water from contacting live parts.

In the next installment, we discuss Section 70 — Electrical requirements for factory-built relocatable structures and non-relocatable structures


[i] Source: CSA C22.1:24, Canadian Electrical Code, Part 1 – Safety Standard for Electrical Installations. © 2024 Canadian Standards Association. Please visit store.csagroup.org. With the permission of CSA Group, material is reproduced from CSA Group standard CSA C22.1:21, Canadian Electrical Code, Part 1 – Safety Standard for Electrical Installations. This material is not the complete and official position of CSA Group on the referenced subject, which is represented solely by the Standard in its entirety. While use of the material has been authorized, CSA Group is not responsible for the manner in which the data are presented, nor for any representations and interpretations. No further reproduction is permitted. For more information or to purchase standard(s) from CSA Group, please visit store.csagroup.org or call 1-800-463-6727.

Related Articles


Latest Articles


Changing Scene

  • The ECABC Jack Funk Scholarship Open Until August 15

    The ECABC Jack Funk Scholarship Open Until August 15

    August 10, 2026 The ECABC Jack Funk Scholarship honours the memory of Jack Funk, a long-time electrical contractor and leader in British Columbia. Jack ran his electrical contracting business for 45 years and served as President of ECABC from 1994 to 1996. These scholarships reflect his commitment to training and supporting future generations of electrical… Read More…

  • Munden Munden Enterprises and Lotus LED Lights Partner in Atlantic Canada

    Munden Munden Enterprises and Lotus LED Lights Partner in Atlantic Canada

    August 10, 2026 Munden Enterprises has announced a partnership with Lotus LED Lights as their representative across Atlantic Canada. “Lotus brings patented innovation, clean architectural design, installer friendly solutions, North American warehouse support, and warranty confidence to a lighting category where consistency, availability, and long-term support matter.” Read More…

  • Elec-Tech Sales Ltd. Announce New Partnership with CMP Products in BC

    Elec-Tech Sales Ltd. Announce New Partnership with CMP Products in BC

    August 10, 2026 Elec-Tech Sales Ltd. is excited to announce is new partnership with CMP Products in British Columbia. “We are looking forward to expanding the CMP footprint throughout the province on their comprehensive portfolio of cable glands & cable cleats. Please reach out to our team with any inquiries,” the company said. Read More…

  • Seacliff Electric Welcomes New Project Manager

    Seacliff Electric Welcomes New Project Manager

    August 10, 2026 Seacliff Electric welcomed Clayton Miller to Seacliff Electric as their newest Project Manager in a LinkedIn post. “With more than 20 years of experience in the electrical industry, Clayton brings a wealth of knowledge spanning project management, estimating, and field operations. His extensive background and industry expertise will be a valuable addition… Read More…