Study Shows Value of Sensor-controlled, Bi-Level Lighting

LRC

Jan 21, 2019

Considerable energy savings can be achieved with sensor-controlled, bi-level corridor lighting, according to results of a field demonstration led by the Lighting Research Center (LRC) at Rensselaer Polytechnic Institute.

The field demonstration looked at sensor-controlled, bi-level corridor lighting in a multi-family apartment building.

“Saving lighting energy in multi-family corridors is becoming more feasible,” says Jennifer Brons, who authored a report on the field demonstration. “LED luminaires can easily dim light output when corridors are vacant, rather than turning off entirely. Most importantly, the occupants had positive comments about safety and comfort with sensor-controlled, bi-level lighting.”

Dimming light output when corridors are vacant, rather than turning off entirely, is referred to as “bi-level” or “adaptive” lighting. Sensors can be mounted in each luminaire, or can be wirelessly linked to multiple luminaires.

Project background

With support from the New York State Energy Research and Development Authority, the LRC and Taitem Engineering collaborated with Albany Housing Authority to upgrade 60 corridor lights on six floors of a below-market-rate apartment building in Albany, New York, known as Lincoln Square Two. Monitoring results from 14 other apartment buildings enabled energy savings calculations comparing market rate vs. below market rate buildings.

Lincoln Square Two is part of a complex of high-rise apartments built in the 1960s. The project involved upgrading 60 corridor lights (6 floors, 10 per floor).

Previous lighting consisted of linear T8 fluorescent lamps4 in surface-mounted luminaires spaced typically 13 feet

(4 m) apart. Although lamps were in good working order, plastic cube louvers had yellowed with age, thus distorting colours and reducing luminaire light output. Before the retrofit, average illuminance on the floor was 106 lux (10 fc).

For this research, each of the previous fluorescent luminaires were replaced one-for-one with LED luminaires controlled by integrated ultrasonic occupancy sensors. Luminaires were rotated to orient parallel to the corridor

to improve light distribution on the walls. Each of the new luminaires was set to operate at 100% output when occupied (average 303 lux at floor level); when vacant, luminaires dimmed independently to 20% of full output. Twenty of the new luminaires were set for each of the three delay time settings: 5, 10, or 15 minutes.

Resident feedback

The LRC administered a questionnaire to compare occupant acceptance to the conventional, fixed-output fluorescent lighting in use before the retrofit. Despite the higher light levels with the new lighting, most occupants did not consider the hallways too bright after retrofit. Over three-quarters (78%) of the occupants approve of the new bi-level lighting. More of the occupants had positive ratings after retrofit than before retrofit.

The occupants also offered positive comments about the retrofit. Multiple people commented that they like how the individually controlled luminaires ramp up light output successively as they walk through the corridor. One person likes that the sensors act as a notification that others are present. Several people simply prefer having more light in the corridors, independent of sensor features. There were no negative comments about the sensors.

Estimated annual energy use

Energy impacts were studied for the three delay time settings. Luminaires programmed with the shortest sensor delay time (5 minutes) operated at high output for less time (22%) compared to those programmed with longer (15 minute) delay times (31%). This resulted in 14% less annual energy use for the short delay time setting compared to the long delay time setting.

Proximity to elevator lobbies increased the amount of time luminaires were at high output, and therefore reduced energy savings in these areas. However, even in busy elevator lobbies, bi-level lighting used about half as much energy as only upgrading to fixed-output LEDs.

The LRC calculated annual energy use for 48 luminaires comparing the previous T8 fluorescent luminaires to two conditions: LED luminaires without sensors, and bi-level lighting programmed with a 5-minute time delay. At this high-rise residential site, use of sensors to create bi-level lighting more than doubled energy savings compared to upgrading to fixed-output LEDs.

Key findings

The Lincoln Square bi-level lighting demonstration showed that

    • over three-quarters (78%) of the occupants approved of the new bi-level lighting
    • 5-minute delay time was not objectionable
    • dimming to 20% light output when vacant was not objectionable
    • use of sensors to create bi-level lighting more than doubled energy savings compared to upgrading to fixed-output LEDs
    • the lower the dim setting when vacant, the greater the energy savings due to bi-level lighting

Read the full study here

Related Articles


Latest Articles

  • How ABB’s Hi-Tech Valiant™ Current Limiting Fuse for Fire Mitigation Impacts Safety & Reliability, Protecting the Environment & Critical Infrastructure

    How ABB’s Hi-Tech Valiant™ Current Limiting Fuse for Fire Mitigation Impacts Safety & Reliability, Protecting the Environment & Critical Infrastructure

    March 13, 2025 By Blake Marchand Discussing the Hi-Tech Valiant™ Fuse for Fire Mitigation with ABB’s Dominique Tardif There has been increased awareness on the impact of forest fires in recent years, as wildfire seasons have intensified in North America. We recently saw devastating fires in California, and in Canada, statistics show that each year wildfire seasons… Read More…

  • EFC Tariff Update Hub

    EFC Tariff Update Hub

    March 13, 2025 EFC’s Tarrif Update Hub provides a centralized location for EFC actions, government advocacy, and key industry resources regarding the ongoing tariff situation between Canada and the United States. Designed to keep EFC members aligned and ahead of developments, check back for updates and insights to help you navigate the evolving landscape. EFC… Read More…

  • International Women’s Day 2025: Advancing Equity in the Skilled Trades

    International Women’s Day 2025: Advancing Equity in the Skilled Trades

    March 13, 2025 On March 8, 2025, CAF-FCA celebrates International Women’s Day (IWD) by reaffirming our commitment to breaking barriers and advancing opportunities for women and equity-priority groups in the skilled trades. This year’s theme, “For ALL Women and Girls: Rights. Equality. Empowerment,” is a powerful call to action—one that aligns with our efforts to… Read More…

  • EFC is Proud to Recognize March 8 as International Women’s Day

    EFC is Proud to Recognize March 8 as International Women’s Day

    March 13, 2025 By Electro-Federation Canada Imagine a gender equal world. A world free of bias, stereotypes, and discrimination. A world that’s diverse, equitable, and inclusive. A world where difference is valued and celebrated. Together we can forge women’s equality. Collectively for #IWD2025 we can all #AccelerateAction. Focusing on the need to Accelerate Action emphasizes the importance of taking swift… Read More…


Changing Scene

  • Canada Invests in Deep Energy Retrofits for Affordable Housing in Hamilton

    Canada Invests in Deep Energy Retrofits for Affordable Housing in Hamilton

    March 13, 2025 There is a need and an opportunity for Canada to strengthen energy security and affordability for all Canadians. Canada’s buildings sector is the third-largest contributor to greenhouse gas emissions across the country. By increasing the scale and pace of building retrofits, we can make homes and buildings more energy-efficient and improve reliability in units.  The federal… Read More…

  • Tesla Products Excluded from BC Hydro Incentive Program

    Tesla Products Excluded from BC Hydro Incentive Program

    March 13, 2025 CBC has reported that BC Hydro is excluding Tesla products from their EV charger incentive program. However, products purchased prior to March 12 will still be eligible. “As of March 12, Tesla chargers, energy storage batteries and inverters are not eligible for rebates, according to B.C. Hydro. Those who have purchased or… Read More…

  • Acuity Rebrands and Introduces New Corporate Identity

    Acuity Rebrands and Introduces New Corporate Identity

    March 13, 2025 Acuity Brands, Inc.’s corporate name is changing from Acuity Brands, Inc. to Acuity Inc. effective March 26, 2025. Acuity will continue to operate through two business segments, Acuity Brands Lighting (ABL) and Acuity Intelligent Spaces (AIS), formerly Intelligent Spaces Group (ISG). They will continue trading on the New York Stock Exchange under the ticker symbol “AYI”. “Acuity is positioned for long term growth…. Read More…

  • IDEAL Electrical™ Unveils Fresh, Modern Brand Identity

    IDEAL Electrical™ Unveils Fresh, Modern Brand Identity

    March 7, 2025 IDEAL Electrical was the first company to obtain a patent to make and sell wire connectors in the United States 96 years ago this month – and today IDEAL® announces a modern look for the brand, which captures the company’s spirit of relentless innovation and the optimistic future of the electrical trade. … Read More…