Guide to the Canadian Electrical Code, Part 1 , 25th Edition – A Road Map: Appendix J – Annex J18 – Part C

September 8, 2023

By William (Bill) Burr[i]

The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the information you need. This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B, or the explanations of individual requirements contained in the CEC Handbook** but will hopefully provide some help in navigating while reading the Code.

Guide to the Canadian Electrical Code, Part 1, 25th Edition– A Road Map: Appendix J - Annex J18 – Part B

Appendix J – Annex J18 – Part C

Annex J18 is optionally permitted for use in additions, modifications, renovations or operation and maintenance of existing facilities employing the Division system of classification. The rules of Annex J18 are normative (mandatory) where used and amend or supplement other requirements of the Code.  Additional informative (non-mandatory) information is contained in Annex JB.  Annex J18 is divided into four parts – General, Class I, Class II and Class III locations. Due to the size of this Annex, it is discussed in four parts. This is Part C Class II locations.

Class II, Division 1 Locations

Rules J18-200 to J18-226 apply to installations in Class II, Division 1 locations where, under normal operating conditions or abnormal operation or failure of equipment, combustible dust may be in suspension continuously, intermittently, or periodically in sufficient quantities to produce explosive or ignitable mixtures or conduct electricity. For additional information reference Appendix E.

Rule J18-200 requires that equipment installed in a Class II, Division 1 location be in accordance with Table 18.

Rule J18-202 requires that:

  • transformers and electrical capacitors containing a flammable liquid be installed in electrical equipment vaults in accordance with Rules 26-350 to 26-356 and have self-closing fire doors on both sides of the wall sealed to minimize dust intrusion, vent openings or ducts and suitable pressure relief openings communicating only with the air outside the building.
  • transformers and electrical capacitors that do not contain a flammable liquid be installed in electrical equipment vaults as above or marked for use in Class II locations.
  • No transformer or capacitor be installed where dust from magnesium, aluminum, aluminum bronze powders, or other metals of similarly hazardous characteristics may be present.

Rule J18-204 outlines wiring methods, in Class II, Division 1 locations and requires:

  • threaded rigid metal conduit or hazardous location cables with associated cable glands complying with Table 18,
  • explosion-proof boxes, fittings, marked for use in Class II locations, and joints threaded for connection to conduit and cable glands,
  • cables installed and supported to avoid tensile stress at the cable glands,
  • explosion-proof type flexible fittings, marked for use in Class II locations be used where necessary for flexible connections at motor terminals and similar places; and be protected by a sheath where subjected to oil or corrosive conditions.

Rule J18-206 specifies the requirements for sealing in Class II, Division 1 locations and requires that communication between a raceway and a dust-tight enclosure be prevented by a permanent seal, a 3 m long horizontal section of raceway, or a vertical 1.5m long section of raceway extending downward from the enclosure.

Rule J18-208 requires that switches, motor controllers, circuit breakers, and fuses including push buttons, relays, and similar devices be provided with a dust-tight enclosure marked for use in Class II locations.

Rule J18-210 requires that transformers, impedance coils, and resistors located in Class I, Division 1, used in conjunction with control equipment for motors, generators, and appliances, and any associated switching mechanism, be provided with a dust-tight enclosure marked for use in Class II locations.

Rule J18-212 requires that motors, generators, and other rotating electrical machines be marked for use in Class II locations.

Rule J18-214 outlines that:

  • Every vent pipe for a motor, generator, other rotating electrical machine, or enclosure for electrical equipment, be:
    • Dust-tight throughout its entire length,
    • lead directly to a source of clean air outside a building,
    • be metal not less than 0.52 mm (No. 24 MSG) thick or equally substantial non-combustible material,
    • be screened at the outer end, and,
    • Have protection against mechanical damage and corrosion.
  • the seams and joints of metal vent pipes be riveted and soldered, bolted and soldered, welded, or rendered dust-tight by some other effective means; and
  • No exhaust pipe discharges inside a building.

Rule J18-216 requires that utilization equipment be marked for use in Class II locations.

Rule J18-218 requires that:

  • Luminaires and portable lighting be complete assemblies marked for use in Class II locations and have the maximum wattage clearly marked,
  • Each luminaire be protected against physical damage by a suitable guard or by location,
  • pendant luminaires be:
    • suspended by and supplied through threaded rigid conduit stems,
    • threaded joints be provided with set screws or other effective means to prevent loosening, and
    • For stems longer than 300 mm, provided with permanent and effective bracing against lateral displacement at a level not more than 300 mm above the lower end of the stem,
    • Flexibility in the form of a suitable fitting or flexible connector situated not more than 300 mm from the point of attachment, and
  • Luminaires be supported by boxes, box assemblies, and fittings marked for use in Class II locations.

Rule J18-220 requires that flexible cords be extra-hard usage type, contain a bonding conductor and be provided with glands marked for use in Class II, Division 1 locations, where entering a box or fitting required to be dust-tight.

Rule J18-222 specifies that receptacles and attachment plugs be marked for use in Class II locations.

Rule J18-224 requires that signal, alarm, remote control, communication systems, meters, instruments, relays, apparatus, and equipment comply with Table 18 and that all wiring comply with Rules J18-204 and J18-206.

Rule J18-226 outlines that equipment marked with EPL Da may be installed in a Class II, Division 1 location with the same explosive dust atmosphere and temperature class.

Class II, Division 2 Locations

Rules J18-250 to J18-276 apply to installations in Class II, Division 2 locations where, under infrequent malfunctioning of handling or processing equipment, combustible dust may:

  • be present in quantities sufficient to produce explosive or ignitable mixtures but only for short periods of time, or
  • Develop combustible dust accumulations on equipment sufficient to interfere with the safe dissipation of heat, or
  • become ignitable by operational failure of equipment.

For additional information reference Appendix E.

Rule J18-250 requires that equipment installed in a Class II, Division 2 location be in accordance with Table 18.

Rule J18-252 requires that:

  • transformers and electrical capacitors containing a flammable liquid be installed in electrical equipment vaults in accordance with Rules 26-350 to 26-356, and
  • transformers and electrical capacitors not containing a flammable liquid be installed in electrical equipment vaults as above or marked for use in Class II locations.
  • Dry-core transformers be installed in electrical equipment vaults in accordance with Rules 26-350 to 26-356 and have winding and terminal connections enclosed in non-ventilated tight housings and operate at a maximum of 750 volts.

Rule J18-254 outlines wiring methods, in Class II, Division 2 locations and requires:

  • Wiring methods of:
    • threaded rigid metal conduit or hazardous location cables complying with Table 18,
    • Type TC cable installed in cable tray in accordance with Rule 12-2202 and enclosed in rigid conduit where it leaves the cable tray,
    • armoured cable with overall non-metallic jacket, such as TECK90, ACWU90, copper-sheathed RC90, or aluminum-sheathed RA90,
    • Control and instrumentation cables with interlocking metallic armour and continuous jacket in control circuits (Type ACIC),
    • type CIC cable (non-armoured control and instrumentation cable) installed in cable tray installed in accordance with Rule 12-2202 (2), where the cable is rated 300 volts and the circuit voltage is 150 volts at 5 amps or less,
    • rigid RTRC conduit Type XW, with associated boxes, fittings, and joints marked with the suffix “–XW” and installed and serviced in industrial establishments, only by qualified persons, or
    • heavy-duty liquid-tight flexible metal conduit and connectors.
  • Boxes and fittings in which taps, joints, or terminal connections are made be either enclosure Type 4 or 5 or have close-fitting covers to prevent the escape of sparks or burning material.
  • cables installed and supported to avoid tensile stress at the cable glands; and
  • compliance with Rule J18-204 (4), (a) and (c), and (5) where flexible connections are necessary.

Rule J18-256 requires raceways in Class II, Division 2 to be sealed in accordance with Rule J18-206.

Rule J18-258 requires that switches, motor controllers, circuit breakers, and fuses including push buttons, relays, and similar devices be provided with a Type 4 or 5, enclosure or have close-fitting covers to prevent the escape of sparks or burning material.

Rule J18-260 requires that:

  • Switching mechanisms, including overcurrent devices, used in conjunction with control transformers, impedance coils, and resistors be provided with enclosures conforming to Rule J18-258, and tight housings without ventilating openings, where not located in the same enclosure; and
  • Resistors and resistance devices have dust-tight enclosures marked for use in Class II locations.

Rule J18-262 requires that motors, generators, and other rotating electrical machines be marked for use in Class II, or Class II, Division 2 locations.

Rule J18-264 outlines that every vent pipe for a motor, generator, other rotating electrical machine, or enclosures for electrical equipment:

  • Comply with Rule J18-214,
  • be sufficiently tight to prevent the entrance of dust into the ventilated equipment or enclosure, and prevent the escape of sparks, flame, or burning material igniting accumulations of dust or combustible material, and
  • permits lock seams, riveted or welded joints and tight-fitting slip joints where flexibility is necessary.

Rule J18-266 requires that:

  • Electrically heated utilization equipment be marked for use in Class II locations,
  • Motors of motor-driven utilization equipment conform to Rule J18-262,
  • Enclosure for switches, circuit breakers, and fuses conform to Rule J18-258.
  • transformers, impedance coils, and resistors forming part of or used in connection with utilization equipment conform to Rule J18-260 (2) and (3).

Rule J18-268 requires that:

  • Luminaires and portable lighting be complete assemblies marked for use in Class II locations and have the maximum wattage clearly marked.
  • Each luminaire be protected against physical damage by a suitable guard or by location and have enclosures for lamps and lampholders designed to minimize the deposit of dust on lamps and prevent the escape of sparks, burning material, or hot metal.
  • pendant luminaires be:
    • suspended by and supplied through threaded rigid conduit stems,
    • threaded joints be provided with set screws or other effective means to prevent loosening, and
    • For stems longer than 300 mm, provided with permanent and effective bracing against lateral displacement at a level not more than 300 mm above the lower end of the stem,
    • Flexibility in the form of a suitable fitting or flexible connector situated not more than 300 mm from the point of attachment, and
  • Luminaires be supported by boxes, box assemblies, and fittings marked for use in Class II locations; and
  • Starting and control equipment for mercury vapour and fluorescent lamps conform to Rule J18-260.

Rule J18-270 requires that flexible cords conform to Rule J18-220.

Rule J18-272 specifies that receptacles and attachment plugs be a polarized type that affords automatic connection to the bonding conductor of the flexible

supply cord: and is designed so that the connection to the supply circuit cannot be made or broken while live parts are exposed.

Rule J18-274 requires that:

  • Signal, alarm, remote control, and communication systems, meters, instruments, relays, and contacts that interrupt other than voice currents be enclosed as per Rule J18-258.
  • The windings and terminal connections of transformers and choke coils carrying other than voice currents be provided with tight enclosures without ventilating openings; and
  • Resistors, resistance devices, thermionic tubes, and rectifiers carrying other than voice currents and exceeding 120 0 C, be provided with Class II dust-tight enclosures,

Rule J18-276 outlines that equipment marked with EPL Da, Db, or Dc may be installed in a Class II, Division 2 location with the same explosive dust atmosphere and temperature class.

In the next instalment, we will be discussing Part Dof Annex J18of Appendix J, Class III locations.

[1] Source: CSA C22.1:21, Canadian Electrical Code, Part 1 – Safety Standard for Electrical Installations. © 2021 Canadian Standards Association. Please visit Store – CSA Group or call 1-800-463-6727. With the permission of CSA Group, the material is reproduced from CSA Group standard CSA C22.1:21, Canadian Electrical Code, Part 1 – Safety Standard for Electrical Installations. This material is not the complete and official position of CSA Group on the referenced subject, which is represented solely by the Standard in its entirety. While use of the material has been authorized, CSA Group is not responsible for the manner in which the data are presented, nor for any representations and interpretations. No further reproduction is permitted. For more information or to purchase standard(s) from CSA Group, please visit Store – CSA Group or call 1-800-463-6727.


[i] William (Bill) Burr is an associate member of the Canadian Electrical Code, Part 1, Technical Committee and formerly Chair of the Canadian Advisory Council on Electrical Safety (CACES), Chief Electrical and Elevator Inspector for the Province of BC & the Northwest Territories, Director of Electrical and Gas Standards Development and Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting billburr@gmail.com..

Related Articles


Latest Articles

  • Winnipeg Information Bulletin: Low-Risk Voice, Data, Video & Security System Installations

    Winnipeg Information Bulletin: Low-Risk Voice, Data, Video & Security System Installations

    September 17, 2026 Certain types of installations may qualify for a low-risk voice, data, video (VDV) and security system electrical permit. For information related to regular VDV/security system installations, see winnipeg.ca/vdvsystems. Applications must be submitted through Permits Online. Electrical permits and inspections are needed for certain installations of security and similar alarm systems. This makes… Read More…

  • What Type of Outdoor Light Do I Need for My Application?

    What Type of Outdoor Light Do I Need for My Application?

    September 17, 2026 By Stanpro The right outdoor light starts with the space you need to illuminate and how that space is used. For commercial projects, parking lots and large exterior areas point toward area lights; entrances and building perimeters toward wall-mounted or security lighting; signs, facades and targeted areas toward flood lights; pathways toward… Read More…

  • Alberta Employers and Tradespeople Share their Perspectives

    Alberta Employers and Tradespeople Share their Perspectives

    September 16, 2026 In Alberta’s skilled trades labour market employers and tradespeople are facing growing pressure from tariffs, rising costs, hiring challenges and labour mobility barriers. CAF-FCA’s new report, Hiring, Mobility and Needed Supports: Alberta Employers and Tradespeople Share Their Perspectives, takes a closer look at what’s happening on the ground. Based on surveys of… Read More…

  • Goal Zero YETI 3000X Power Stations Recalled due to Fire and Burn Hazards

    Goal Zero YETI 3000X Power Stations Recalled due to Fire and Burn Hazards

    September 16, 2026 This recall involves Goal Zero YETI 3000X power stations. The silver and black portable power stations measure about 62 centimetres (24.4 inches) high, 47 centimetres (18.5 inches) wide, 57 centimetres (22.3 inches) deep and weigh approximately 42 kilograms (92 pounds). The power stations have yellow handles and a digital display at the… Read More…


Changing Scene

  • LEDVANCE Canada Marks 10 Years of Innovation and Growth and Looks Ahead to Its Next Chapter in the Canadian Market

    LEDVANCE Canada Marks 10 Years of Innovation and Growth and Looks Ahead to Its Next Chapter in the Canadian Market

    September 25, 2026 From legacy lighting leader to solutions partner, LEDVANCE is entering its next decade with a clear focus on Canadian customers, communities, and market needs LEDVANCE Canada is marking the 10th anniversary of LEDVANCE as an independent brand by celebrating a decade of growth, customer partnerships, and continued investment in solutions designed around… Read More…

  • EFC Welcomes Patrick McManus as Incoming President & CEO

    EFC Welcomes Patrick McManus as Incoming President & CEO

    September 25, 2026 Electro-Federation Canada (EFC) is pleased to announce the appointment of Patrick McManus as President & CEO, effective October 13, 2026. McManus will succeed Carol McGlogan, who is retiring following 10 years with EFC. McGlogan will remain with the organization through the end of 2026 to support a smooth leadership transition. McManus is… Read More…

  • Innovair Solutions Acquires TRM Heating Cables

    Innovair Solutions Acquires TRM Heating Cables

    September 18, 2026 Innovair Solutions has announced the acquisition of TRM Heating Cables, a Toronto-based Canadian company specializing in heating cables for commercial and industrial applications. Founded in 2001, TRM has built strong technical expertise in the sale and installation of specialized products, including self-regulating cables, mineral-insulated cables and electric floor heating systems. The company… Read More…

  • Electrical Safety Authority Honours Leaders Helping Build a Safer, More Electrified Future

    Electrical Safety Authority Honours Leaders Helping Build a Safer, More Electrified Future

    September 17, 2026 From preparing the next generation of skilled workers to supporting one of the world’s largest sporting events, this year’s recipients demonstrate how electrical safety supports Ontario’s future As Ontario electrifies homes, transportation and industry, the Electrical Safety Authority (ESA) has recognized the organizations and individuals helping ensure safety keeps pace with that… Read More…