The Importance of Trip-Free Operation and Its Characteristics

Trip-free circuit breakers

 

Anthony T. Ricciuti

One of the many often desirable characteristics in the specifications and marketing literature for medium voltage circuit breakers is “trip-free.” Unfortunately, there are many misconceptions about this characteristic.
Definitions

For IEEET rated products, there are several related definitions of “trip-free”:

•    In the most general definition of “trip-free,” the contacts of the circuit breaker must return tothe open position and remain there when an opening operation follows a closing operation,regardless of whether the closing signal, force,or action is maintained.

•    A common variant is called “electrically trip-free.” For a medium voltage circuit breaker tobe considered electrically trip-free, the circuit breaker must be able to receive and respond to an electrical opening signal regardless of whether an electrical closing signal is energized.

•    “Mechanically trip-free” operations refer to a mechanical release mechanism that can open the medium voltage circuit breaker regardless of whether any closing release device operated by any means is activated or maintained.Medium voltage circuit breakers can also be hydraulically trip-free or pneumatically trip-free if they contain a hydraulic or pneumatic opening release device, respectively,that are capable of opening the circuit breaker regardless of whether any closing release device operated by any means is activated or maintained.

Any of these variants of trip-free operation may include a trip-free relay, in which its operation alters a closing release circuit, permitting an opening release to operate unimpeded by a closing release operation in any state. For IEC rated products, although the standard recommends that the suitability for trip-free operations should be provided to customers that are specifying medium voltage circuit breakers,no specific definition is provided for this function.

Physical requirements

For IEEE rated products, if a mechanical opening release operation is maintained on a medium voltage circuit breaker, then any closing release operation signal must not result in contact movement that reduces the open gap between the contacts by more than 10%. This characteristic is often confused with the definition of trip-free.However, if any opening release operation isinitiated simultaneously with any closing release operation signal, contact movement up to and including a momentary touching of the main circuit breaker contacts is acceptable before the circuit breaker completes the opening operation.

Additionally, because electrical opening release operation circuits typically employ auxiliary switch contacts internal to the circuit breaker, and therefore the electrical release operation circuit remains open until the main contacts of the circuit breaker have closed, when an electrical opening release operation circuit is maintained, the momentary touching of the main contacts is acceptable before the circuit breaker completes the opening operation.

Figure 1: Eaton medium voltage circuit breaker operation

Eaton Circuit breaker


Anthony T. Ricciuti is a Specialist Engineer at Eaton, a power management company with 2014 sales of US$22.6 billion. Anthony has a Bachelor’s degree in Mechanical Engineering and more than 20 years of experience in the design, testing, and analysis of circuit breakers. This article first appeared as an Eaton white paper, www.eaton.com/Eaton/OurCompany/WhitePapers/FeaturedWhitePapers/index.htm.

Related Articles


Latest Articles


Changing Scene

  • Mac’s II Agencies Re-Envisions EV Charging Solutions with Two Leading Brands

    Mac’s II Agencies Re-Envisions EV Charging Solutions with Two Leading Brands

    April 9, 2026 Mac’s II Agencies has announced a strategic revision of its electric vehicle charging portfolio with the addition of Wallbox, and an expanded partnership with RVE. These partnerships position Mac’s II Agencies to deliver end-to-end EV charging solutions for residential developments and commercial applications throughout British Columbia and Yukon in a whole new way. Since Read More…

  • EB Horsman Introduces New Lower Mainland District Manager

    EB Horsman Introduces New Lower Mainland District Manager

    April 9, 2026 EB Horsman is pleased to announce the appointment of Shane Smith as Lower Mainland District Manager, effective April 1, 2026. With nearly two decades of experience at EB Horsman & Son, Shane has built a strong foundation across multiple areas of the business. Since joining the company in 2007, he has progressed Read More…

  • Nominations are Open for NETCO 2026 Leadership Excellence Award

    Nominations are Open for NETCO 2026 Leadership Excellence Award

    April 9, 2026 NETCO is pleased to announce that nominations are now open for the 2026 Leadership Excellence Award. Established in 2016, this national award recognizes an individual who has made outstanding contributions to apprenticeship training and continuing electrical training across Canada. The recipient is honoured annually at the NETCO National Training Conference. NETCO are seeking nominations for Read More…

  • Bartle & Gibson Announces New Partnership with Eaton

    Bartle & Gibson Announces New Partnership with Eaton

    April 9, 2026 Bartle & Gibson Co. Ltd., an Alberta-based premier distributor of plumbing, heating, and electrical products, and Eaton Industries (Canada) Company have announced a new regional partnership that expands access to Eaton’s electrical solutions across Western Canada. This agreement enables customers throughout the Western provinces to procure a broad range of Eaton products, Read More…