Guide to the Canadian Electrical Code, Part I — Instalment 51

Bill Burr

Aug 8, 2019

By William (Bill) Burr

This discussion of Appendix J -Annex J20 is based on the 24th edition. The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the information you need. This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook** but will hopefully provide some help in navigating, while reading the code. The 24th Edition of the CE-C, Part I, (C22.1-18)* is now available from CSA Group.

Annex J20 is optionally permitted for use in additions, modifications, renovations or operation and maintenance of existing facilities that employ the Division system of classification. The rules of Annex J20 are normative (mandatory) where used and amend or supplement other requirements of the Code. Additional informative (non-mandatory) information is contained in Appendix G and Annex JB.

Due to the size of this annex, it is discussed in multiple parts. This is Part A – Flammable Liquid and Gasoline Dispensing Service Stations and Garages.

Rule J20-000 states that the scope of Annex J20 applies to existing flammable liquid and gasoline dispensing, service stations, garages, bulk storage plants, finishing processes, and aircraft hangars that employ the Division system of classification.

The definitions in Rule J18-002 provide special terminology definitions for terms used in that section that are supplementary to the definitions in Section 0 and also apply in Annex J20.

Gasoline dispensing stations and service stations

Rule J20-002 points out that Rules J20-004 to J20-014 apply to electrical equipment and wiring installed in gasoline dispensing stations, and other locations where gasoline or volatile flammable liquids are dispensed or transferred to the fuel tanks of vehicles. Note that lubritoriums, service rooms, repair rooms, offices, salesrooms, compressor rooms, and similar locations are excluded and are covered by Rules J20-100 to J20-112.

Rule J20-004 defines the limits of Class I, Division 1, and Division 2 hazardous areas of gasoline and other flammable liquids dispensing stations.

Rule J20-006 requires that wiring and equipment within hazardous areas, as defined in J20-004, comply with the wiring and equipment rules of Annex J18. In addition, where dispensers are supplied by rigid metal conduit, a union and a flexible fitting must be installed between the conduit and the dispenser junction box, in addition to any sealing fittings, that must be maintained if a flexible cable is used.

Rule J20-008 outlines that wiring and equipment installed above hazardous areas conform to rules J20-106 and J20-110 outlined below.

Rule J20-010 requires that a switch, that disconnects all ungrounded conductors simultaneously, be provided on each circuit leading to or through a dispensing pump.

Rule J20-012 specifies that seals, as required by Annex J18, be installed in each conduit run, both entering or leaving a dispenser, as well as cavities or enclosures communicating with a dispenser.

Rule J20-014 reiterates that all non-current-carrying metal parts of dispensing pumps, metal raceways, and other electrical equipment must be bonded to ground, in accordance with Section 10.

Propane dispensing, container filling, and storage

Rule J20-030 points out that Rules J20-032 to J20-042 apply to locations where propane is dispensed to vehicles, portable containers, or to storage containers.

Rule J20-032 contains special terminology that applies to this subsection.

Rule J20-034 outlines the Class I, Division 1, and Division 2 hazardous areas in this subsection, as listed in Table JT-63

Rule J20-036 specifies that wiring and equipment in hazardous areas, defined in Table JT63, conform to the requirements of Annex J18, and that rigid metal conduit, supplying dispensers, conform to Rules J20-006 (2) and (3).

Rule J20-038 requires seals to be installed as required by Annex J18, and seals for propane dispensers be provided as per Rule J20-012.

Rule J20-040 requires that a switch, that disconnects all ungrounded conductors simultaneously, be provided on each circuit leading to or through a propane dispensing device.

Rule J20-042 reiterates that all non-current-carrying metal parts of propane dispensing equipment and raceways must be bonded to ground, in accordance with Section 10.

Compressed natural gas refueling stations, compressors, and storage facilities

Rule J20-060 points out that Rules J20-062 to J20-070 apply to locations where compressed natural gas is dispensed to the fuel tanks of self-propelled vehicles, and to associated compressors and storage facilities, but does not apply to vehicle refuelling appliances installed in accordance with CSA B149.1 that do not have storage facilities.

Rule 20-062 outlines the Class I, Division 1, and Division 2 hazardous areas in this subsection, as listed in Table 64.

Rule J20-064 requires that wiring and equipment within hazardous areas, as defined in J20-062 above, comply with the wiring and equipment rules of Annex J18. In addition, Rule J20-006 (2) and (3) apply where dispensers are supplied by rigid metal conduit,

Rule J20-066 requires seals be installed as required by Annex J18, and seals for dispensers be provided as per Rule J20-012.

Rule J20-068 requires that a switch, that disconnects all ungrounded conductors simultaneously, be provided on each circuit leading to a compressor or dispensing device.

Rule J20-070 reiterates that all non-current-carrying metal parts of dispensing pumps, metal raceways, and other electrical equipment must be bonded to ground, in accordance with Section 10.

Commercial repair garages

Rule J20-100 points out that Rules J20-102 to J20-112 apply to commercial garages where vehicles powered by gasoline, propane, or other flammable fuels are serviced or repaired. Table JB-4 outlines the flashpoints of flammable liquids.

Rule J20-102 outlines the Class I, Division 2 hazardous areas in commercial repair garages.

Rule J20-104 requires that wiring and equipment within hazardous areas as defined in J20-102 comply with the wiring and equipment rules of Annex J18.

Rule J20-106 requires that fixed wiring, above hazardous areas in commercial repair garages, be installed in accordance with Section 12. Flexible cord of the hard-usage type is to be used for pendants, portable lamps, portable motors and other portable equipment.

Rule J20-108 requires seals installed in commercial repair garages as required by Annex J18 and that raceways buried below, or embedded in a masonry floor that lead to or through a hazardous area above the floor, be considered within the hazardous area.

Rule J20-110 requires that in a commercial repair garage

• fixed equipment above hazardous areas but less than 3.6 m above floor level, that may produce arcs, sparks, or particles of hot metal, be of the totally enclosed type or constructed to prevent escape of sparks or hot metal particles;

• permanently installed luminaires located over lanes through which vehicles are commonly driven may be suitable for non-hazardous locations and may be located a minimum of 3.6 m above the floor or be protected by a guard or by location;

• portable lamps must:

◦ be the totally enclosed gasketted type
◦ be equipped with a handle, lampholder, hook, and substantial guard attached to the lampholder or handle, and
◦ have all exterior surfaces that may contact battery terminals, wiring terminals, or other objects be of non-conducting materials or be effectively protected with an insulating jacket
◦ be of the unswitched type, and
◦ not be provided with receptacles for attachment plugs

Rule J20-112 requires that battery charging equipment and batteries being charged, not be located within the hazardous areas of commercial repair garages, as classified in Rule J20-102.

In the next instalment, we will be discussing Annex J20 – Part B – Bulk Storage Plants, Finishing Processes and Aircraft Hangars in the Class and Division System of Hazardous Locations Classification

* The source for this series of articles is the Canadian Electrical Code, Part I, (C22.1-18) published by CSA.

** Note the CEC Handbook is also published by CSA.

William (Bill) Burr is the former Chair of the Canadian Advisory Council on Electrical Safety (CACES), former Director of Electrical and Elevator Safety for the Province of BC, and former Director of Electrical and Gas Standards Development and former Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting billburr@gmail.com.

 

Related Articles


Latest Articles

  • ESA has Identified Increasing Safety Concern Surrounding Meter Base Installations

    ESA has Identified Increasing Safety Concern Surrounding Meter Base Installations

    April 18, 2025 ESA and EFC are raising awareness on an increasing safety concern the ESA has identified surrounding meter base installations. ESA identified an increase of installed meter bases where the neutral block is isolated from the enclosure. According to OESC Rule 10-210 a bonding conductor must be installed between the meter base and… Read More…

  • Non-residential Construction Investment Continues to Reach Record Highs in January 2025

    Non-residential Construction Investment Continues to Reach Record Highs in January 2025

    April 18, 2025 Overall, investment in building construction rose 1.8% (+$393.7 million) to $22.1 billion in January. The residential sector increased 2.3% to $15.4 billion, while the non-residential sector was up 0.8% to $6.7 billion. Year over year, investment in building construction grew 5.7% in January. On a constant dollar basis (2017=100), investment in building construction increased 1.5% from the previous month to $13.2 billion… Read More…

  • BC Non-Residential Drives Growth, Multi-Family Component Drives Residential Decline in February Building Permits

    BC Non-Residential Drives Growth, Multi-Family Component Drives Residential Decline in February Building Permits

    April 18, 2025 In February, the total value of building permits issued in Canada increased by $371.3 million (+2.9%) to $13.1 billion. Gains in construction intentions were led by British Columbia’s non-residential sector. On a constant dollar basis (2017=100), the total value of building permits issued in February grew 3.2% from the previous month and was up 5.6% on… Read More…

  • Navigating Tariffs: Practical Strategies for ECABC Members

    Navigating Tariffs: Practical Strategies for ECABC Members

    April 18, 2025 Canadian businesses are facing uncertain and unprecedented risks created by tariffs on Canadian goods from the United States. The combination of the economic impact to BC’s economy from these tariffs, and the potential increase in the cost of construction materials and equipment as Canada is forced to respond with retaliatory tariffs, has… Read More…


Changing Scene

  • Ontario Introduces Legistlation to Unlock Trade and Labour Mobility Within Canada

    Ontario Introduces Legistlation to Unlock Trade and Labour Mobility Within Canada

    April 18, 2025 As a next step in its plan to protect Ontario by unleashing the province’s economy, the Ontario government is introducing the Protect Ontario through Free Trade within Canada Act to unlock free trade and labour mobility within Canada. This legislation will, if passed, create new opportunities for job creation and investment attraction, supporting economic… Read More…

  • Ontario, P.E.I. Join Nova Scotia With Legislation to Remove Internal Trade Barriers

    Ontario, P.E.I. Join Nova Scotia With Legislation to Remove Internal Trade Barriers

    April 18, 2025 Prince Edward Island and Ontario have joined the Nova Scotia by introducing reciprocal legislation that will help foster an environment of mutual recognition of goods, services and labour mobility between these provinces. “Leaders across the country are expressing interest in removing trade barriers, and I’m very pleased that P.E.I. and Ontario have… Read More…

  • New Brunswick Signs MOU with Ontario to Reduce Trade and Labour Mobility Barriers

    New Brunswick Signs MOU with Ontario to Reduce Trade and Labour Mobility Barriers

    April 18, 2025 The governments of New Brunswick and Ontario have signed a memorandum of understanding on free trade and labour mobility. “Ontario is New Brunswick’s second-biggest trading partner, and we are excited to be building on the positive momentum to reduce internal trade barriers across Canada,” said Premier Susan Holt. “Today’s signing of this… Read More…

  • EFC Welcomes New Manufacturer Member: MegaResistors Corp.

    EFC Welcomes New Manufacturer Member: MegaResistors Corp.

    April 18, 2025 Founded in 2008, MegaResistors is a proudly Canadian company specializing in the design and production of high-quality power resistors, including grounding resistors, braking resistors and resistive load banks, tailored for demanding industry and mission critical applications. Their extensive line of products helps them meet the needs of the industry, from crane control… Read More…