High Voltage Is Not High Risk!

EIN author TerryBecker 400

Feb 16, 2021

By Terry Becker, P.Eng., CESCP, IEEE Senior Member

It is interesting that these two words “High Voltage” have been used throughout the history of our use of electricity to use fear as a tactic to keep people away from electrical equipment located indoors or outdoors and in turn has also been considered “high risk.”  Would you believe me if I told you that actually working on low voltage electrical equipment may be a higher inherent risk level or the same inherent risk level as working on or near high voltage electrical equipment?  With the application of expected and appropriate hierarchy risk controls methods low voltage and high voltage energized electrical work tasks would both be low risk.

In the CSA Z462 Workplace electrical safety Standard it doesn’t use the voltage level of electrical equipment to define low risk, medium risk, high risk or extreme risk/danger.   CSA Z462 Clause 4.1.7.8 Risk assessment procedure outlines three requirements in completing a risk assessment: identify hazards; assess risks; and implement risk control according to the hierarchy of risk control methods to eliminate exposure or reduce risk to as low as reasonably practicable.  In implementing this process, it is clear that “High Voltage Is Not High Risk!”  For specific details on completing a risk assessment you can also refer to CSA Z1002 and CSA Z45001.

In Clause 3 Definitions of the CSA Z462 Standard two definitions are provided to further clarify risk and risk assessment.

“Risk – a combination of the likelihood of occurrence of injury or damage to health and the potential severity of injury or damage to health that results from a hazard.

Risk Assessment – an overall process that identifies hazards, estimates the likelihood of occurrence of injury or damage to health, estimates the potential severity of injury or damage to health, and determines if protective measures are required.

Note: As used in this Standard, “arc flash risk assessment” and “shock risk assessment” are types of risk assessments.(1)

The CSA Z462 Standard is a Job and discrete work task(s) based Standard and this is the starting point and basis for the implementation of the employers defined Risk Assessment Procedure in their Electrical Safety Program.  The starting point is the work task description, CSA Z462 provides Table 2 Estimate of the likelihood of occurrence of an arc flash incident for ac and dc systems, which can be used. It provides thirty-one (31) discrete energized electrical work tasks.  The voltage of the electrical equipment that will be worked on is secondary and is used to define if an abnormal arcing fault can be sustained and lead to an arc flash occurring and the voltage also determines if a shock hazard exposure can occur.   The third consideration in completing the risk assessment procedure is the actual electrical equipment that the energized electrical work task will be performed on.  Following this sequence, a qualitative risk assessment for the Job and discrete work task(s) will be used to determine the residual risk level based on the energized electrical work task description first.  Figure 1 below visually represents the risk assessment process.

Figure 1 – Risk Assessment Process

F1 RiskAsses

As noted above risk assessment takes into consideration the likelihood of occurrence and the potential severity of injury or damage to health.  These two elements are considered together to determine a discrete work task’s residual risk level as low, medium, high or extreme risk/danger.

CSA Z462 also defines two independent risk assessments required to be completed as components of the overall Risk Assessment Procedure.  CSA Z462 Clauses 4.2.4 Shock risk assessment and Clause 4.2.5 Arc flash risk assessment require that the Qualified Electrical Worker completes and documents these two risk assessments in the field before executing the Job assigned to them and executing the energized electrical work task(s) related to a Job.  

In completing both the Shock Risk Assessment and the Arc Flash Risk Assessment for an energized electrical work task, the process is the same as the overall Risk Assessment Procedure: identify if the shock or arc flash hazard exists, estimate the likelihood or occurrence of injury or damage to health and the potential severity of injury or damage to health; and determine if additional protective measures are required, including the use of PPE.

CSA Z462 also notes that the estimate of likelihood or occurrence and potential severity of injury or damage to health for both the shock and arc flash risk assessments shall take into consideration:

Shock:            The electrical equipment design shall be considered, including but not limited to, the suitability of the guarding of exposed energized electrical conductors or circuit parts.

Arc Flash:      The design of the electrical equipment, including its overcurrent protective device and its operating time.

Both the shock risk assessment and arc flash risk assessment need to consider the electrical equipment operating condition and the condition of maintenance.  Specific to the arc flash risk assessment, it needs to consider the design of the electrical equipment, including its overcurrent protective device upstream of the work task location on the electrical equipment and its operating time.

When completing the risk assessment procedure for an energized electrical work task, low voltage work tasks are performed more frequently, and lower voltages will result in higher available fault currents which can lead to higher incident energy levels depending on the maximum fault clearing times associated with the low voltage electrical equipment.   Low voltage work tasks performed on low voltage electrical equipment will be the same risk level or a higher risk level than work tasks performed on high voltage electrical equipment.

You can and should develop, implement and document a formal risk assessment process with associated electrical hazard risk assessment matrix and work task risk register table as a key component of your company’s Electrical Safety Program.  As I outline above, use it to confirm for a Job that requires individual energized electrical work tasks, low or high voltage, with the application of the expected hierarchy or risk control methods are residual low risk.

High Voltage Is Not High Risk!

If you are interested in discussing the CSA Z462 Standard, 2021 Edition or have any questions or comments you may have regarding this article please contact Terry Becker, P.Eng., CESCP, IEEE Senior Member via phone 1-587-433-3777, or email terry.becker@twbesc.ca or for additional information see his website www.twbesc.ca.

Terry Becker, P.Eng., CESCP, IEEE Senior Member is the first past Vice-Chair of the CSA Z462 Workplace electrical safety Standard Technical Committee and currently a Voting Member and Working Group Leader for Clause 4.1 and the Annexes.  Terry is also a Voting Member on the CSA Z463 Maintenance of electrical systems Standard and a Voting Member of the IEEE 1584 Guide for Performing Arc-Flash Hazard Calculations.  Terry has presented at Conferences and Workshops on electrical safety in Canada, the USA, India, and Australia.  Terry is a Professional Engineer in AB, BC, SK, MN and ON.  Terry is an Electrical Safety Specialist, Management Consultant at TW Becker Electrical Safety Consulting Inc..

(1) CSA Z462 Workplace electrical safety Standard, 5th Edition, 2021.

Related Articles


Latest Articles

  • Stephanie Medeiros on EV Infrastructure in Canada, Innovative Technologies, Well-Planned Charging Networks, & Commercial Fleets

    Stephanie Medeiros on EV Infrastructure in Canada, Innovative Technologies, Well-Planned Charging Networks, & Commercial Fleets

    September 3, 2026 By Blake Marchand In this Q&A with Stephanie Medeiros, the Head of Mobility at Schneider Electric Canada provides insight into her perspective on EV charging infrastructure in Canada, factors that will contribute to growing EV adoption, grid modernization for commercial fleets, the role of Vehicle-to-Grid and other innovative approaches to electrification. The focus of… Read More…

  • LEDVANCE: Understanding Light Beam Angles

    LEDVANCE: Understanding Light Beam Angles

    September 3, 2026 Light Beam Angles: How It Affects Different Types of Lighting, Where It Is Applied & What to Consider When Choosing the Right One Beam angle is important in lighting design. It determines how light spreads within a space and influences both functionality and atmosphere. By understanding beam angles, you can achieve both… Read More…

  • ITC 101 Series: Why Certifications (UL, CSA) Matter in Industrial Components

    ITC 101 Series: Why Certifications (UL, CSA) Matter in Industrial Components

    September 2, 2026 By ITC Electrical Components When selecting industrial electrical components, certification is more than a logo on a datasheet. A certification mark indicates that a product or component has been independently evaluated against specified requirements for its intended market. In North America, selecting products with the appropriate certification can affect regulatory acceptance, equipment… Read More…

  • Project Spotlight: Leigh Square Fountain

    Project Spotlight: Leigh Square Fountain

    September 2, 2026 In spring 2025, the City of Port Coquitlam unveiled a transformed Leigh Square, reimagined as a vibrant, accessible, and welcoming gathering place in the heart of downtown. At the heart of the renewed plaza, a Bellagio-style programmable dancing fountain is integrated directly into the paving—three interlocking rings where jets rise, fall, and… Read More…


Changing Scene

  • 2026 Ontario Apprenticeship Awards Call for Nominations

    2026 Ontario Apprenticeship Awards Call for Nominations

    September 3, 2026 Skilled Trades Ontario is proud to open nominations for the 2026 Ontario Apprenticeship Awards, recognizing outstanding apprentices, journeypersons, organizations and skilled trades leaders who are helping strengthen Ontario’s apprenticeship system. Award recipients will be announced at the Ontario Apprenticeship Summit on November 4, 2026, at the Toronto Congress Centre. Nominations must be submitted… Read More…

  • Bartle & Gibson Announces New Partnership with Hubbell Canada

    Bartle & Gibson Announces New Partnership with Hubbell Canada

    September 3, 2026 Bartle & Gibson Co. Ltd., an Alberta-based premier plumbing, heating and electrical distributor and Hubbell Canada have announced a new regional partnership enabling increased access to Hubbell Canada’s end-to-end electrical product portfolio across Western Canada. “With our strong presence in the west through 31 branches and counting located in Alberta, Saskatchewan, British… Read More…

  • Bartle & Gibson Opens Salmon Arm Location

    Bartle & Gibson Opens Salmon Arm Location

    September 3, 2026 Bartle & Gibson opened their new Salmon Arm location on July 20th. The Salmon Arm location features: This site is strategically positioned in the city of Salmon Arm, located near to the busy Picadilly Mall.  Salmon Arm branch is located at: 621- 10 Street SW Salmon ARM, BC V1E 1T1 Photo Source Read More…

  • MacKinnon Magnetics Announces Partnership with Resilient Sales Corporation in Northeastern Ontario

    MacKinnon Magnetics Announces Partnership with Resilient Sales Corporation in Northeastern Ontario

    September 3, 2026 MacKinnon Magnetics is pleased to welcome Resilient Sales Corporation as their newest sales agency partner. Resilient Sales will represent MacKinnon Magnetics across Northeastern Ontario, including the Districts of Muskoka and Parry Sound. Key markets include Sudbury, North Bay, Timmins, Kirkland Lake, Sault Ste. Marie, Huntsville, Bracebridge and Parry Sound. “This partnership expands… Read More…