Test Your Knowledge of the Canadian Electrical Code – Part 1 — The Answers: Fire Alarm Systems

EIN Code Quiz2 400

June 11, 2021

In the last installment, you had the opportunity to answer our questions about the Code and best practices. Here are the answers to those questions.

Fire Alarm Systems, Smoke and Carbon Monoxide Alarms, and Fire Pumps

Q: What rule specifies the requirements for insulated conductors and cables in fire alarm systems and what are the requirements?

A: Rule 32-100 specifies the requirements for insulated conductors and cables in fire alarm systems which include:

  • copper material
  • ampacity
  • use of optical fiber cables
  • use of stranded conductors
  • insulation rated at 300 volts
  • determining wire size for raceways or integral assemblies
  • selection in accordance with rules 12-102(3)or 12-122(1)

Q: What rule requires that no disconnecting means, overcurrent protection or device capable of interrupting the fire pump circuit may be placed between the service box from the normal power supply and the fire pump transfer switch or controller, except?

A: Rule 32-306 requires that no disconnecting means, overcurrent protection or device capable of interrupting the fire pump circuit may be placed between the service box from the normal power supply and the fire pump transfer switch or controller:

  • Except a circuit breaker that is permanently labeled identifying it as a fire pump disconnect.
  • In addition, the circuit breaker must be lockable in the closed position and may be in the separate service box as in Rule 32-304

Q: In the case where this circuit breaker is installed in an emergency power supply circuit between the emergency power source and the fire pump transfer switch, the rating of the circuit breaker shall be?

A: As per rule 28-200:

  • Be set or rated to not less than the rating of the overcurrent protection provided integral with the fire pump transfer switch
  • Indefinitely carry the locked rotor current of the fire pump
  • Where it is installed in a normal supply circuit be rated not less than the overcurrent protection of the fire pump controller
  • Where the circuit breaker is installed in an emergency supply feeder between the emergency generator and the fire pump transfer switch, the feeder must bypass the generator main circuit breaker and be connected directly to the emergency generator.

Go HERE to discuss

Related Articles


Latest Articles

  • STANDATA Bulletin Section 6 – Services and Service Equipment

    STANDATA Bulletin Section 6 – Services and Service Equipment

    July 27, 2026 The purpose of this STANDATA bulletin is to clarify Section 6 of the 2024 Canadian Electrical Code (CE Code), Part 1, which outlines the installation requirements for services, service equipment, and metering equipment. View the Bulletin: Read More…

  • Behind the Glow: How Neonview Helped Shape Vancouver’s Newest Landmark Roof

    Behind the Glow: How Neonview Helped Shape Vancouver’s Newest Landmark Roof

    July 27, 2026 Some projects are exciting because they’re new. Others are exciting because you can feel how many people had to be exceptionally good at their craft to make them look effortless. The PNE Amphitheatre (Freedom Mobile Arch) is the latter. The notable largest free-span wood roof in North American is the headline, but the lighting is the… Read More…

  • Canada Light Expo: Energy Efficient Lighting Solutions for Modern Businesses

    Canada Light Expo: Energy Efficient Lighting Solutions for Modern Businesses

    July 27, 2026 How Energy Efficient Lighting Can Help Modern Businesses Balance Profitability with Environmental Responsibility In today’s competitive business landscape, organizations are constantly seeking ways to reduce operational costs, improve sustainability, and foster productive work environments. Among the most impactful yet often overlooked areas of optimization is lighting. As businesses strive to balance profitability… Read More…

  • Stelpro Baseboard Heating: Reliable Comfort for Commercial & Residential Spaces

    Stelpro Baseboard Heating: Reliable Comfort for Commercial & Residential Spaces

    July 27, 2026 By EB Horsman & Son As temperatures rise and winter fades into the background, heating systems might not be top of mind. However, spring and summer are actually the ideal time to plan ahead. Installing or upgrading your heating system now can save time, reduce stress, and ensure you are fully prepared… Read More…


Changing Scene