Transformer Short Circuit Considerations

March 9 2016

Short circuits or faults can and do occur on electric power and distribution systems. When a fault occurs on the load side of a transformer, the fault current will pass through the transformer. As components on these systems, transformers need to be able to withstand these fault currents.

Fault currents flowing through transformers are significantly higher than the rated currents of the transformers. In a worst case scenario, the current would be as high as the current that would flow if system voltage was applied to the primary terminals while the secondary terminals are shorted — limited by the transformer impedance only. These currents produce both mechanical and thermal stresses in the transformers.

Photo credit: Hammond Power Solutions

Forces resulting from the currents passing through the transformer act on the conductors. The forces are a function of the peak asymmetrical current (the highest peak value of any cycle of the current), which is usually at its highest during the first half cycle of the fault. The duration of the fault is not normally a concern for mechanical withstand because the peak value of each cycle of the current reduces as the fault persists. The transformer manufacturer needs to ensure these forces do not damage the transformer.

The thermal stress is caused by the high current causing heating in the transformer. Both the RMS symmetrical current magnitude and duration of the fault contribute to the heating of the transformer. The transformer manufacturer needs to ensure the components of the transformer do not become hot enough to be damaged.

General purpose dry type transformers are typically designed to withstand the mechanical and thermal stresses caused by a short circuit occurring on the secondary terminals of the transformer with rated voltage applied to the primary terminals for a maximum of 2 seconds, provided the current does not exceed 25 times rated current. The fault current magnitude is a function of the transformer impedance. The table below shows the fault current for selected impedances and applies to both line currents and phase currents.

 

Transformer Impedance  Fault Current (times rated)
4.0% 25.0
5.0% 20.0
6.0% 16.7
7.0% 14.3
8.0% 12.5

 

The maximum of 25 times rated current is listed so that transformers with an impedance below 4% need only be able to withstand 25 times rated current, although the fault current could be higher than this. It does not mean that all transformers are able to handle a fault current up to 25 times rated current. With rated voltage applied to the primary a transformer impedance above 4% will not allow 25 times rated current to flow.

Many specifications indicate a fault level at the primary terminals of the transformer. Some customers will ask for a transformer to be braced for the primary fault level. A general purpose transformer is suitable to be connected to a system with the specified fault level, but the transformer impedance will limit the fault current through it to well below the available fault level. As an example, the customer requests a 2500 kVA transformer, 13.8 kV delta to 480Y/277 V, 5.75% impedance to be braced for 750 MVA fault level at 13.8 kV. In this case, the available fault current at the primary terminals is 31.4 kA. For a fault on the secondary side of the transformer, the transformer impedance will limit the fault current that flows in the primary to 1.8 kA in the lines and 1.1 kA in the coils — significantly lower than the available fault level. There is no need for the transformer primary conductors to be sized and braced to handle a 31.4 kA fault current.

Some operating conditions need special attention. Some customers specify the transformer to operate continuously with load at higher than rated voltage. If a fault occurs when the transformer is operating at higher than rated voltage, the resulting fault current would be higher than a typical transformer is designed for. This will increase both the forces in the transformer and the heating of the transformer. Some customers specify a fault duration longer than 2 seconds without specifying a higher voltage. This does not affect the forces but does increase the heating in the transformer. In these cases, a special design may be required.

One case in particular requires special attention: transformers directly connected to a generator. When a generator is supplying a load and the load is suddenly disconnected, the output voltage of the generator rises significantly for a short time until the excitation system decreases the voltage. If a fault occurs on the secondary of a transformer at this time, the fault current can be significantly higher than a typical transformer is designed for. Some applications may not have any overcurrent protection between the generator and the transformer primary winding, resulting in an increased duration. In such cases, it is recommended that IEEE C57.116 IEEE Guide for Transformers Directly Connected to Generators be reviewed to determine the short circuit withstand requirement for the transformer.

General purpose transformers have short circuit withstand capabilities that are sufficient for many applications. The transformer manufacturer needs to be informed of cases where a fault could occur on the secondary of the transformer when the transformer is supplied above rated voltage or the fault duration is longer than two seconds to ensure the transformer is suitably designed to withstand the possible secondary faults.


This document was first published as a white paper by Hammond Power Solutions, the largest manufacturer of dry-type transformers in North America. Hammond Power Solutions engineers and manufactures a wider range of custom transformers that are exported globally in electrical equipment and systems. The firm supports solid industries such as oil and gas, mining, steel, waste and water treatment, and wind power-generation.

 

 

Related Articles


Latest Articles

  • Hazardous Environment vs. Intrinsically Safe Sensors: Understanding the Differences

    Hazardous Environment vs. Intrinsically Safe Sensors: Understanding the Differences

    May 5, 2025 Sensors designed for industrial applications often face harsh conditions, including extreme temperatures, high humidity, exposure to chemicals, and the presence of combustible gases or dust. Two common classifications for sensors used in such environments are hazardous environment sensors and intrinsically safe sensors. While they share some overlap, they serve different purposes and… Read More…

  • The Wild and Wonderful of Thermal by FLIR – How Thermal Imaging is Augmenting More Than Just Cameras

    The Wild and Wonderful of Thermal by FLIR – How Thermal Imaging is Augmenting More Than Just Cameras

    May 5, 2025 By Krystie Johnston Teledyne FLIR OEM launched their Thermal by FLIR about six years ago, to expand support for original equipment manufacturers (OEMs) who integrate FLIR thermal camera technology into their products. Since then, these collaborations have taken thermal into completely new spaces. Mike Walters, Vice President of Emerging Product Management at FLIR… Read More…

  • Ontario Leads Residential Sector Increase in February Construction Investment

    Ontario Leads Residential Sector Increase in February Construction Investment

    May 5, 2025 Overall, investment in building construction rose 1.5% (+$331.7 million) to $22.4 billion in February, with gains being recorded across all components. The residential sector increased 1.8% to $15.7 billion, while the non-residential sector was up 0.8% to $6.8 billion. Year over year, investment in building construction grew 8.9% in February. On a constant dollar basis (2017=100), investment in building construction… Read More…

  • MCEE 2025 Marks Big Return to the Palais des congrès

    MCEE 2025 Marks Big Return to the Palais des congrès

    May 4, 2025 By Electro-Federation Canada Canada’s largest Mechanical, Plumbing, Hydronics, HVAC, Electrical and Lighting Expo did not disappoint. On April 24-25, more than 6,000 attendees flocked to the Palais des congrès in the heart of Montreal to attend the Mechanical, Conditioning, Electrical, and Equipment (MCEE) trade show to see the latest products, learn about… Read More…


Changing Scene

  • City Electric Supply Bids Farewell to Vickey Mackay and Brian Doucette

    City Electric Supply Bids Farewell to Vickey Mackay and Brian Doucette

    May 5, 2025 After decades of leadership, City Electric Supply bid a warm farewell to two incredible branch managers in their Ottawa District — Vicky Mackay (Ottawa Central & Kemptville) and Brian Doucette (Pembroke). “Their dedication, leadership, and lasting impact will be felt for years to come,” said City Electric Supply on LinkedIn. City Electric Supply are also introducing… Read More…

  • 2025 Skills Ontario Competition & Career Exploration Showcase Highlights the Future Skilled Trade and Technology Workforce

    2025 Skills Ontario Competition & Career Exploration Showcase Highlights the Future Skilled Trade and Technology Workforce

    May 5, 2025 Canada’s largest skilled trades and technology conference, the Skills Ontario Competition, is back at the Toronto Congress Centre May 5th – May 6th. Ian Howcroft, CEO of Skills Ontario, said Skills Ontario is changing lives and inspiring leaders through skilled trades and technologies through events like the Skills Ontario Competition. “We look forward… Read More…

  • Manitoba Government Honours Highest Achieving New Journeypersons

    Manitoba Government Honours Highest Achieving New Journeypersons

    May 4, 2025 The Manitoba government is proud to acknowledge the outstanding work and commitment of newly certified journeypersons, as well as recognize employers and their contributions to Manitoba’s skilled trades, Business, Mining, Trade and Job Creation Minister Jamie Moses announced last night at the Legislative Building during the 33rd annual Apprenticeship Highest Achievement Awards… Read More…

  • Acuity Acquires Sports Lighting Startup M3 Innovation

    Acuity Acquires Sports Lighting Startup M3 Innovation

    May 4, 2025  Acuity Inc. has acquired the business assets of M3 Innovation, LLC, a sports lighting startup that uses innovative technology to lower the overall cost of the installation and operation of sports lighting solutions.   The acquisition has already closed, and the solution is now part of the Acuity Brands Lighting (ABL) business portfolio. M3 Innovation’s products and innovative technology will be available through Acuity’s independent sales network as part of their Lithonia Lighting® brand and through direct sales and utility channels as part of their Holophane® brand.   “We are excited to welcome M3 Innovation to ABL. The founders are thought… Read More…