Fixed Electrical HeatingPierre McDonald

Users of the Canadian Electrical Code, 23rd edition will see a completely re-written Section 62 covering fixed electric heating systems. Advances in new heating technologies as well as increases in electric heating efficiency at the point of use have seen growth in industrial, commercial and residential applications. Changes to Section 62 include these new applications as well as a complete re-organizing of existing requirements. Rules that duplicated requirements or were repeated for different installations have been combined.Significant entries have also been included within Appendix B to assist with clarification.This article will attempt to simplify the requirements and illustrate the total overall change within Section 62.

Heating technology

Fixed electric space heating refers to the application of providing heat to an enclosed space or room for the comfort of persons or animals, or simply to maintain a specific temperature required by products stored within that room.Electric heaters provide heat in a room by radiation, conduction or convection.Understanding these heating methods helps to understand installation requirements, including clearances.

Radiant heating is heat energy transferred in the form of electro magnetic radiation. A common example is the warmth of the sun.Fixtures generating radiant heat will have very specific clearances from combustible and non-combustible materials.

Convection heating is simply the movement of heat by air. This is also known as forced air. However, not all convection heating is forced air. The natural movement of air over a heating element causes hot air to rise within a room. The heated or hot air will eventually cool and fall back down to the floor, circulating through the heater and repeating this cycle.Fixtures producing convection heat will also have specific clearances from combustible and non-combustible materials.

Conduction heating is the transfer of heat energy between objects that are in physical contact with each other.This type of heating is common in industrial applications where tanks, piping and vessels must be heated to ensure their contents do not freeze.These heating technologies will have virtually no clearance requirements from the surfaces they are designed to heat. However, clearances from other adjacent surfaces may need to be observed.Additionally, a maximum temperature limit will come in to play with some applications.

Section 62: scope

Revisions to the scope of Section 62 now include all fixed heaters, including fixed electric space heating systems for rooms and similar areas, fixed surface heating systems, and fixed heating that is not considered as space heating or surface heating.Examples of these three heating systems have been tabulated and are listed in the Appendix B note to Rule 62-000 and include:

• central heating units
• baseboard heaters
• radiant heaters
• wall and ceiling heaters
• floor warming heaters
• pipe heating
• storage tank or vessel heating
• snow and/or ice melting
• Skin effect heating
• pipe internal heaters, often referred to as “gut” heating
• immersion heaters
• hot water tanks

General (100 Series) Rules

Several changes have been made to the General Rules (100 Series) of Section 62.Rules of a general nature that were scattered throughout the section have all been consolidated.Additionally, several rules that repeated themselves in the previous edition CE Code have been rewritten once for clarity.This simplifies the meaning and lets code users know that the rules specified under the General Rules apply to all heating installations except where otherwise specified.The following is a summary of the changes to the General Rules, 62-102 to 62-128.

• Heating devices shall be assembled and installed “following manufacturer instructions.”This is stated just once as opposed to several times as in previous editions of the code, Rule 62-102(1).
• CE Code Part ll standards require electrically conductive coverings, braids, etc. on all heaters. Rule 62-102(2) requires that these coverings be bonded to ground.
• Special Terminology (62-104 Definitions) includes standardized cable and panel definitions, and has changed “Fixture” to “Heating fixture.”The generic term “Heating device” includes all heaters and has added definitions forbare element water heater, dielectric heating, impedance heating, induction heating, and skin effect trace heating.
• Wet conditions are stated in AppendixB Note to Rule 62-106 as concrete slabs or masonry in direct contact with earth or drains, e.g., showers,but not where isolation measures are installed, e.g., a membrane.
• One requirement has been set for maximum temperature adjacent to combustible materials: 90oC, Rule 62-112.
• The previous requirement not allowing a flammable fluid to be heated above its flash point (62-118(3)) has been deleted.
• All ground fault protection requirements were consolidated into one general rule, (62-116), with exemptions for industrial establishments under certain conditions. Additional exemptions apply to heaters on Class 1 extra-low-voltage power circuits with an ungrounded secondary isolating transformer.
• A demand factor relaxation was added for cyclic loads.
• Updates were made to field repair, modification or assembly of series heating cable sets(62-126).

Space heating (200 Series)

These rules (62-200 to 62-222) have also seen several changes with edits tobetter match the topic area. The rules cover fixed electric space heating systems for heating rooms and similar areas, and now recognize surface heaters and wall heating. One of the significant changes includes the addition of Table 67, which identifies clearance requirements of installed heating systems. Temperature limits shown in Table 67 were derived from the Maximum Temperature Table in C22.2 No. 130, reproduced in Appendix B. Additionally, five diagrams (B62-1 to B62-5) were added to Appendix B,illustrating examples of clearances in residential applications. The maximum temperatures for heater contact with materials are

• 150oC for masonry, concrete, etc., 62-210(2)
• 90oC for combustible material, 62-112

The requirements for sauna heaters have also been included within the 200 Series (62-222) with a few changes.

Surface heating (300 Series)

The 300 series of rules (62-300 to 62-314) covers fixed surface heating systems for pipe heating, melting of snow or ice on roofs or concrete or asphalt surfaces, soil heating, and similar applications other than space heating. Substantial changes were made to applications of heating systems under sidewalks, driveways, and similar areas whereby the non-safety requirements (clearances, separations, wattages, etc.) associated with these installations were moved to the informative Appendix B, leaving the rules to address the safety related requirements. Other notable changes include:

• The 90oC Max Temp. requirement changed, applyingonly to adjacent combustible materials and now in the General (100) section.
• 750 V limit for parallel cables has been deleted (this is covered in the product standard).
• The requirement for marking has been changed to requirements for caution labels, with subrules added to define the frequency of these labels.
• Requirements for skin effect trace heating systemshave been added (62-314), including an Appendix Bnote and diagram (B62.6)

Other heating (400 Series)

Lastly, the 400 Series (62-400 to 62-410)was revised to bring the requirements for heating cable sets and heating panel set installed within pipes, ducts or vessels up to date. Pipeline resistance heating is now referred to as pipeline impedance heating, and several rules have been moved from Section 26 for infrared drying lamps, water storage tanks, dielectric and induction heating, and bare element water heaters.

Additional changes and the re-organization of Section 62 rules will continue to take place. Requirements are in the works for heating within hazardous locations as well as Induction heating. Advances will also take place with skin effect heating and impedance heating systems. With the changes to this 2015 CE Code, Section 62 is posed to accept new heating technologies and any new safety requirements. While this article covers a very general view of section 62, it is incumbent on the Code user to review all the changes and apply the rules accordingly. It should also be noted that while this 2015 CE Code is published and available, to date it has yet to be recognized by anyprovincial or territorial authority having jurisdiction (AHJ). Code users should contact their Inspection authority to determine when this code becomes law within you jurisdiction.

More from Pierre McDonald:
- Conductor Ampacities and Their Temperature Rating
- Code and Public Safety
- Establishing When the CE Code Becomes Mandatory
- UL Code Link
- CAN/ULC-S576-14, Standard for Mass Notification System Equipment and Accessories
- Canadian CE Code Changes: Section 20 and More
- Meeting National Building Code of Canada Requirements


 

Pierre McDonald, CET, is Senior Regulatory Affairs Representative/Répresentant Principal, Affaires Réglementaires, Underwriters Laboratories of Canada Inc. Based in St. Albert, AB, Pierre has been a member of the Canadian Electrical Code Part 1 technical committee as well as several subcommittees including serving as Chair of Sections 6 and 76 and as a member representing regulators on several other CSA committees. Pierre is still active with code development and interpretation.

 

Changing Scene

  • Prev
A New Brunswick provincial program aimed at supporting and mentoring women in apprenticeable trades ...
Government Relations Minister Lori Carr announced the transfer of gas and electrical licensing ...
IDEAL continues to recognize the essential work electricians are doing during this global crisis. ...
Total investment in building construction increased 60.1% to $13.4 billion in May, ...
IDEAL Industries recently put together a new supply catalogue focused on panel builders and ...
ECAO is piloting a young leaders group, named Future Leaders Advisory Council (FLAC).   ...
Cooper Lighting extends its commitment to education and support of its customers and specifiers. ...
Stay Wired to Win is a monthly at-home challenge designed to keep your competitive spark going ...
Join the Electrical Contractors Association of Ontario (ECAO) for a live webinar on July 7 at 2:00 ...
Following the latest COVID-19 announcements from the Ontario Government, ESA has decided to ...


 

LDS Aug Products Eaton AL Series Dimmers 400Eaton's Wiring Devices AL series dimmers offer a versatile option for any dimming application - fine tune the dimming performance to match your exact needs and change colors as needed to suit any décor.

Color change kits come with three color faceplates, offering design flexibility within one product. Select models are available in 4 different color combination packs.

 

 


Read More

 

ESAAs the government continues a gradual, staged approach to reopen Ontario, ESA is assessing how they can safely resume in-person classroom training while adhering to Ontario Public Health guidelines. ESA is continuing to monitor key public health indicators and Stage 3 restrictions as efforts begin to reschedule previously postponed in-person classroom courses.

If you are registered in a postponed ESA course, they will notify you in the next couple of weeks of the rescheduled date. Please note that online courses are continuing as scheduled.

 

Read More

 


 



Case Study: EikoPro Electric LLC had a customer that had just constructed a new horse barn and was looking to light it quickly. The barn was designed to be lit with ten high bay lights for maximum efficacy and efficiency. Together with EiKO’s distributor partner, Platt Electric Redmond located in Redmond, Oregon, Pro Electric selected the EiKO 200W BAY-C high bay fixture, which puts out an impressive 30,000+ lumens at a 5000K color temperature. This high lumen output and the long life of the fixture – 72,000 hours – made it an ideal choice for the application.

Obviously, when lighting a barn, the security and safety of the animals, riders, and care givers is paramount. EiKO’s LED high bay products fill the space with light, eliminating shadows and blind spots.

Read More

Product News

  • Prev
The SlimLED you know and love is now available with a 5-position CCT selectable switch.   ...
Intense Lighting, a Leviton company, today announced the launch of the highly anticipated V-Rail ...
Beluce has developed a line of social distancing signs and “face covering required” signs to remind ...
Eaton's Wiring Devices AL series dimmers offer a versatile option for any dimming application - ...
The YDD-L is an energy-efficient dusk to dawn yard light. It was designed for barns and ...
Arani's single-sided LED plastic running man sign comes in 2 versions: with battery, and without ...
With three shapes and 14 sizes available, Lumewerx’s latest addition to the Pop family comes in ...
Midwest’s Metallic RV power centers are a cost-effective favorite among campground owners ...
The IDEAL SLK® Disconnect Fuse Kit is a waterproof breakaway safety device that ...
The LED Edge-Lit ceiling luminaire has a very slim design for a modern and minimalist ...


 

Yard LightThe YDD-L is an energy-efficient dusk to dawn yard light. It was designed for barns and farms. It is a versatile and economic light source that is good on the environment and uses long-life LED’s. The YDD-L comes standard with photo control which helps to provide significant power savings.

Lens
Polycarbonate diffused lens encloses high performance LEDs.

 

 

 

Read More

 


 

Peers & Profiles

  • Prev
At 14, Tom Miguel was sitting in the counselor’s office of Silverthorn Collegiate Institute in ...
Meredith Halfpenny is a Wind Site Technician with Boralex where she inspects, maintains, and ...
Rutul Bhavsar is a final year Electrical Engineering student at Mohawk College. He recently ...
Shannon Tymosko is a first-year apprentice with IBEW (International Brotherhood of Electrical ...
ELG Electric is an electrical contractor based out of Goderich, Ontario serving the area’s ...
Founded by Warren Osak, Electromate specializes in Robotic and Mechatronic Solutions, distributing ...
 Will West is a first-year apprentice working in the solar industry with Hakai Energy ...
“It’s definitely the Olympics of our trade,” said Lance Giesbrecht of the Ideal National ...
Tommy Carducci is a 14-year industry veteran working with Seneca Electrical and was one of 18 ...
Legend Power Systems is an innovative Canadian company headquartered out of Vancouver, B.C. Their ...


Tom MiguelBy Sarah PickardTom Miguel

At 14, Tom Miguel was sitting in the counselor’s office of Silverthorn Collegiate Institute in Etobicoke with his entire life ahead of him. In 1981, the world was changing, and like so many young men and women, he was faced with a world of choices that would go on to define both his career and his life.

It was in this office that some counsellor suggested becoming an electrician, and Tom’s interest was piqued. “I knew from that point on what field of studies I needed to focus on to become an electrician,” Tom said.

 

Read More

 


Rutul Bhavsar 1 400By Blake Marchand

Rutul Bhavsar is a final year Electrical Engineering student at Mohawk College. He recently co-authored a whitepaper on Mohawk College’s Joyce Centre for Partnership & Innovation discussing the technologies utilized in the state-of-the-art zero-carbon/carbon-neutral facility. Rutul was the lead author on the project, supported by Dr. Mariano Arriaga, General Manager of Mohawk’s Energy and Power Innovation Centre (EPIC) and Dr. Tony Cupido Research Chair, Sustainability at Mohawk College. Rutul’s interests lie in the more progressive areas of the industry, automation, control, and energy efficient technologies.

Read More


 

Copper $US Dollar price per pound

Kerrwil Publications Great Place to Work. Certified December 2019 - December 2020

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2020 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil