How to Use the Fluke T6 Electrical Testers with FieldSense Technology

Fluke

September 28, 2017

This is the second of a two-part article on Fluke’s new TC electrical tester. Part 1 explored features in benefits. Here in Part 2: putting Fluke T6 to work.

Anyone who uses electrical testers to capture measurements such as voltage and current knows that the process is traditionally time-consuming and carries the potential for risk. The Fluke T6 electrical tester with FieldSense Technology provides a faster and safer method for taking electrical readings on distribution panels and junction boxes, among other applications. This tool senses an electrical field in the open fork, allowing you to take the measurement with ease.

Typically, electricians encounter junction boxes crowded with wires, so finding the right connec­tion point poses a challenge. T6 electrical testers go beyond simple detec­tion. They actually measure AC voltage, current and frequency without test leads. With the use of the provided test leads, the tools are also able to measure AC/DC voltage, resistance and conti­nuity.

The FieldSense technology measures the voltage through the cable’s insula­tion, reducing user hazard to exposed metallic conductors and reducing the likelihood for errors or accidentally contacting the wrong conduc­tors. The technology injects a known signal to accurately derive the unknown AC voltage. This allows for an actual AC voltage measurement, versus simply sensing a magnetic field found in traditional non-contact voltage detectors.

Taking stable readings

The optimal position for a hot or neutral conduc­tor when taking FieldSense measurements is centred at the bottom of the open fork. When positioning the fork, with one hand, simply slide the open fork over the conductor. For the T6-1000, the LCD display simultaneously shows the voltage and current measurements while the frequency can be manually selected with the press of a button. There’s no need to reconfigure the tool or search for metallic test points.

The display screen will turn green to indicate that FieldSense has a reliable electrical signal. The triangle-shaped voltage indicator light, marked with the lightning bolt icon, turns red if the voltage present is greater than 30 V.

Be aware that the reading may not be as accu­rate when the user is wearing insulated gloves, highly insulated boots or standing on an insu­lated ladder. These scenarios will require an external grounded lead to be connected in order to confirm a reliable reading. This is accom­plished by simply touching the attached black lead to a grounded conductor, such as a conduit or a junction box.

Measuring AC voltage and AC current

Follow these four easy steps:

  1. Turn the dial knob to the second position, or “FieldSense” function. The tester measures and simultaneously displays both AC voltage and AC amps on the T6-1000 while the T6-600 will default to AC amps and must be toggled to AC voltage using the yellow toggle button.
  2. When using the touch pad to complete the ground, insert the black test probe into the storage dock on the back of the unit. If using insulated gloves, standing on an insulated ladder or otherwise insulated from ground, place the black test lead on a ground conductor or attach it to ground with an alligator clip.
  3. View the reading, making note of the units of measurement.
  4. Press the HOLD button to momentarily freeze the reading for a quick snapshot of the screen readout.

Remember, the attached test leads must be used when measuring AC/dc voltage through the tradi­tional metallic contact method and when making phase to phase voltage measurements. Touch the probe tips to the circuit across the load or power source in parallel to the circuit.

The T6-600 is rated 600 V CAT III and the T6-1000 is dual rated 1000 V CAT III/600 V CAT IV.

Measuring resistance and continuity

The T6-1000 measures resistance 1Ω to 100 kΩ, while the T6-600 measures 1Ω to 2000 Ω. To take a measurement:

  1. Turn off power in the circuit to be tested.
  2. Turn the selector to Ω.
  3. Touch the probe tips across the designated component or portion of the circuit.
  4. View the reading.
  5. If the reading is less than 40 ohms, you will obtain an audible continuity alert.

Non-operating circuitry

With an energized circuit not under load, you can measure the hot leg of an AC circuit. T6 electrical testers help you troubleshoot, as they empower you to find out which wires are hot, even while the circuit — whether for a light, motor, or lamp — is non-operational. This gives electricians the ability to test wires with voltage potential and troubleshoot where the circuit is open. 3 Fluke Corporation How to use Fluke T6 electrical testers to take accurate measurements

Staying protected

Notwithstanding the T6 electrical testers’ improvements to safely taking electrical measurements, workers should still wear appropriate personal protective equipment (PPE). This means electricians should still wear arc-rated clothing and protective equipment including gloves, safety glasses or goggles, hearing protection and leather foot­wear. In lower voltage areas, measurements can be taken wearing minimal PPE, includ­ing gloves and protective eyewear. However, measuring without test leads does not mean you can skip wearing the required PPE.

Find out more: www.fluke.com/t6

Read Part 1 here: http://www.electricalindustry.ca/latest-news/3485-troubleshoot-electrical-systems-safer-and-faster-with-new-tester-part-1

Related Articles


Latest Articles


Changing Scene

  • Hammond Power Solutions Appoints Linda Nadeau Sanford as Western Regional Sales Manager

    Hammond Power Solutions Appoints Linda Nadeau Sanford as Western Regional Sales Manager

    May 12, 2025 Hammond Power Solutions (HPS), a leader in dry-type transformers and power quality solutions, is pleased to announce the appointment of Linda Nadeau Sanford as the new Western Regional Sales Manager. Linda will play a key part in driving sales and revenue across the Western Canada region. She will oversee territory management, advance… Read More…

  • Susanna Zagar, Ontario Energy Board CEO, Named EHRC’s 2025 Agent of Change

    Susanna Zagar, Ontario Energy Board CEO, Named EHRC’s 2025 Agent of Change

    May 12, 2025 Electricity Human Resources Canada (EHRC) is proud to announce Susanna Zagar (she/her), Chief Executive Officer of the Ontario Energy Board (OEB), as the recipient of the 2025 Agent of Change Award. This recognition celebrates Ms. Zagar’s remarkable leadership and commitment to diversity, equity and inclusion (DEI) in the electricity sector. Since stepping… Read More…

  • AD Reports Huge Jump in Member Sales Through Three Months of 2025

    AD Reports Huge Jump in Member Sales Through Three Months of 2025

    May 12, 2025 AD reports that member sales in the first three months of 2025 increased 23% to a record $24 billion across the group’s 14 divisions and three countries. AD welcomed over 550 new members in the first quarter through both organic growth and the IMARK Electrical merger. AD members also acquired another 10… Read More…

  • Legrand Introduces Wattstopper i3 Building Management Platform

    Legrand Introduces Wattstopper i3 Building Management Platform

    May 12, 2025 Legrand® has announced the launch of the Wattstopper i3 Platform, a next-generation lighting and building intelligence solution powered by KODE Labs, a global leader of advanced smart building technology.  The partnership positions Legrand to lead the lighting controls industry into a new era of unified experiences, seamless integrations, and data-driven control, making it easier… Read More…