Guide to the Canadian Electrical Code, Part 1[i], 26th Edition– A Road Map: Section 34

May 12, 2025

by William (Bill) Burr

The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the information you need. This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook but will hopefully provide some help in navigating the Code.

Section 34

Section 34 – Signs

Rule 34-000 Scope, this is a supplementary or amendatory section of the code and applies to incandescent lamps, fluorescent lamps, high-voltage luminous discharge (cold-cathode or neon) tubes, high-intensity discharge lamps and other light-emitting sources such as LEDs. The CEC Handbook has a good diagram of a typical sign installation.

Rule 34-002 denotes some special terminology that applies to this section –GTO sleeving, Neon supply and Sign.

General Requirements

Rule 34-100 requires that each sign and outline lighting system must have disconnecting means integral with it and located within sight and within 9 meters of it or be capable of being locked in the open position.

Rule 34-102 requires that the disconnecting means and other control devices for transformers and ballasts must be approved for the purpose, or have a current rating not less than twice the rating of the neon supply, transformer or ballast.

Rule 34-104 specifies that thermally protected ballasts are required for all signs, and outline lighting with fluorescent lamps except for simple reactance type ballasts.

Rule 34-106 requires that signs, outline lighting and supports be located so that there is no contact, or interference or proximity that can cause a hazard with overhead conductors and electrical and communications utility lines. In addition, a sign or outline lighting system, except for the support, must be a minimum of 2.2 meters above grade. This does not apply to free-standing signs, indoor signs and outline lighting installed in show windows and similar locations, providing they are approved for the location or have mechanical protection.

Rule 34-108 requires that poles, masts standards or other devices used as electrical raceways must be approved for the purpose except when used for mechanical support only.

Rule 34-110 requires that all conductive non-current-carrying parts of a sign or outline lighting installation, except for small metal parts, metal wire ties securing neon tubing and systems supplied by a class 2 power supply, must be bonded to ground in accordance with Section 10 – Bonding and Grounding.

Rule 34-112 requires that sign leads that pass through the surfaces or partitions must be protected by non-combustible bushings.

Rule 34-114 specifies that fuseholders and flashers be enclosed and accessible without removing obstructions or dismantling the sign.

Enclosures

Rule 34-200 requires that neon supplies, switches, timers, relays, sequencing units and similar devices must be in suitable electrical enclosures (information on the construction of enclosures is contained in Appendix B).

Rule 34-202 requires that uninsulated parts that are accessible to authorized persons be protected by doors or covers with interlocks or require non-ordinary tools to open.

Neon supplies

Rule 34-300 limits the rated secondary open-circuit voltage of a neon supply to 15000 v and 7500 volts-to-ground.

Rule 34-302 requires secondary-circuit ground fault protection on neon supplies, except for:

  1. transformers with isolated secondaries and maximum open-circuit voltage of 6000v between leads or terminals, and
  2. integral glass or porcelain secondary tube housing with no secondary circuit field wiring.

Rule 34-304 limits open-type and core-and-coil type transformers to dry locations only.

Rule 34-306 requires that neon supplies used or installed in damp or wet locations as defined in Section 0 – Definitions must be wet or damp type as per 2-024 and 2-400.

Rule 34-308 governs the installation of neon supplies and requires that they are installed in locations that are accessible, capable of being removed or replaced, and rigidly secured. In an attic, bulkhead or similar location, an access door measuring not less than 900mm high by 600mm wide, and a 300mm wide permanent walkway to each component, must be provided.

Rule 34-310 specifies that the rating of overcurrent devices protecting neon supplies be a maximum of 30 amps or as per Rule 8-104 for two or more supplies, and must be of the weatherproof type if exposed to the weather.  Any additional overcurrent devices may be placed inside or outside the sign structure.

Rule 34-312 notes that high-voltage outputs of neon supplies may not be connected in parallel or series with the output of any other neon supply.

Wiring Methods

Rule 34-400 provides extensive detailed requirements for the installation of high-voltage cables in accordance with the rules of Section 12 and Table 15 and include:

  1. type and minimum sizes of raceways and cables, and
  2. minimum separation from combustible material.

Rule 34-402 requires that high-voltage cables in show windows and similar locations must be:

  1. enclosed in approved GTO sleeving,
  2. have a minimum separation of 38mm form combustible and conducting material,
  3. be located so as not subject to mechanical damage and
  4. not used to support the sign.

Rule 34-404 specifies that the length of high voltage cable from neon supplies shall be as short as practicable except not more than 6meters installed in metal raceway, and 16 meters installed in non-metallic raceway.

Rule 34-406 requires that the connection of high-voltage cables to neon tubing must be:

  • inaccessible to unauthorized persons,
  • made by an electrode receptacle or a connection in an enclosure, approved for the location,
  • with minimum conductor insulation extensions of
    • 100 mm for damp or wet locations and
    • 65mm for dry locations.

Rule 34-408 allows flexible metal and liquid-tight flexible metal conduit enclosing high-voltage cables between electrode receptacle assemblies and neon supplies:

  • to serve as the bonding means (conductor) for the metal electrode receptacle assembly, provided it terminates in a secure bonding connection (Rule 10-610).
  • Where non-metallic conduit is used to enclose high-voltage cable, the bonding conductor must be installed exterior to the conduit and a minimum distance from conduits of
    • 38 mm on installations operating at 100 Hz or less,
    • 44 mm on installations operating at more than 100 Hz and not smaller than no. 12 AWG.

The CEC Handbook has a good diagram of bonding for enclosures of high-voltage cable in non-metallic conduit for metal electrode assembly housing.


[i] Source: CSA C22.1:24, Canadian Electrical Code, Part 1 – Safety Standard for Electrical Installations. © 2021 Canadian Standards Association. Please visit Store – CSA Group or call 1-800-463-6727. With the permission of CSA Group, the material is reproduced from CSA Group standard CSA C22.1:21, Canadian Electrical Code, Part 1 – Safety Standard for Electrical Installations. This material is not the complete and official position of CSA Group on the referenced subject, which is represented solely by the Standard in its entirety. While use of the material has been authorized, CSA Group is not responsible for the manner in which the data are presented, nor for any representations and interpretations. No further reproduction is permitted. For more information or to purchase standard(s) from CSA Group, please visit Store – CSA Group or call 1-800-463-6727.

Related Articles


Latest Articles

  • EHRC Destination Trade Program for Third and Fourth-Year Apprentices

    EHRC Destination Trade Program for Third and Fourth-Year Apprentices

    May 14, 2026 Providing financial incentives of up to $5,000 to employers who create new Work-Integrated Learning (WIL) opportunities for third and fourth-year apprentices. Electricity Human Resources Canada’s (EHRC) Destination Trade program is Canada’s third- or fourth-year apprentice work placement initiative for the electricity industry, providing wage subsidies of up to $5,000 to small to Read More…

  • Record Attendance Marks Strong Return for MEET 2026

    Record Attendance Marks Strong Return for MEET 2026

    May 14, 2026 By Electro Federation Canada The Mechanical Electrical Electronic Technology (MEET) show saw a powerful return to Moncton, NB on May 6-7, setting a new attendance record with 7,532 participants attending the two-day event. The biennial show, now in its 26th edition, is touted as the premier industry trade show in the region Read More…

  • LLM Cybersecurity Is Now a Construction Cybersecurity Problem

    LLM Cybersecurity Is Now a Construction Cybersecurity Problem

    May 14, 2026 By Melvin Newman, PataBid CEO In a previous article, we covered how to write effective AI prompts and the real productivity benefits LLMs (large language models) can bring to construction estimating and operations. If you haven’t read it yet, it’s worth starting there. This article picks up where that one left off, Read More…

  • Smart Planning and Innovation Drive Success in Winnipeg Retrofit

    Smart Planning and Innovation Drive Success in Winnipeg Retrofit

    May 14, 2026 The Darling Ingredients retrofit project recently wrapped in Winnipeg—and it’s already being hailed as a model for future upgrades across the company’s North American facilities. Black & McDonald’s electrical division was tasked with replacing the motor control centres (MCCs) at the rendering plant, a high-stakes environment where downtime simply isn’t an option. Read More…


Changing Scene

  • Luminis Wins Red Dot Award for Ellington

    Luminis Wins Red Dot Award for Ellington

    May 14, 2026 Luminis, an established innovator and manufacturer of specification-grade, interior and exterior lighting solutions, today announced its Ellington and Trilo families have each received a Red Dot Design Award for Product Design. Dating back to 1955, the Red Dot Design Award is one of the world’s largest design competitions. Every year, the Red Read More…

  • Quarter Century Platinum Status for PCL Construction

    Quarter Century Platinum Status for PCL Construction

    May 14, 2026 PCL Construction is proud to announce it has once again been recognized as a Platinum Club member of Canada’s Best Managed Companies, earning the distinction for 2026 and reaffirming its place among the country’s most respected and well-managed private enterprises. The recognition extends PCL’s long-standing record of excellence, marking 25 consecutive years as Read More…

  • Landscape Ontario, Electrical Safety Authority Partner to Promote Electrical Safety in Landscape Trades

    Landscape Ontario, Electrical Safety Authority Partner to Promote Electrical Safety in Landscape Trades

    May 14, 2026 Landscape Ontario Horticultural Trades Association (Landscape Ontario) and the Electrical Safety Authority (ESA) have partnered to improve electrical safety awareness and compliance across Ontario’s landscape and horticultural industry. The partnership focuses on supporting safe work around electrical infrastructure, including overhead powerlines and underground systems, and providing clarity and guidance on the application of the Ontario Read More…

  • Register Now for EFC’s Annual Conference: June 2-4, 2026

    Register Now for EFC’s Annual Conference: June 2-4, 2026

    May 14, 2026 Bringing together professionals from across Canada’s electrical industry, EFC’s annual conference offers a dynamic platform for learning, networking, and business growth. Attendees will gain valuable insights from expert speakers in the business program while also being able to take advantage of dedicated B2B Head Office meeting spaces and the ever popular Electro-Lounge Read More…