The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the information you need. This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook** but will hopefully provide some help in navigating, while reading the code. The 24th Edition of the CE-C, Part I, (C22.1-18)* is now available from CSA Group.

Annex J18 is optionally permitted for use in additions, modifications, renovations or operation and maintenance of existing facilities employing the Division system of classification. The rules of Annex J18 are normative (mandatory) where used and amend or supplement other requirements of the Code. Additional informative (non-mandatory) information is contained in Annex JB. Due to the size of this Annex, it is discussed in multiple parts. This is the final Part E - Class III, Division 2 locations.

Class III, Division 2

Rules J18-350 to J18-378 apply to installations in Class III, Division 2 locations in which ignitable fibres or flyings are stored or handled.

Rule J18-350 requires equipment installed in Class III, Division 2 to be in accordance with Table 18.

Rule J18-352 requires that transformers and capacitors installed in these locations conform to Rule J18-252, which states that


• transformers and electrical capacitors containing a flammable liquid be installed in electrical equipment vaults in accordance with Rules 26-350 to 26-356

• transformers and electrical capacitors not containing a flammable liquid be installed in electrical equipment vaults as above, or marked for use in Class II locations


• dry-core transformers be installed in electrical equipment vaults in accordance with Rules 26-350 to 26-356, and have winding and terminal connections enclosed in non-ventilated tight housings and operate at a maximum of 750 volt

Rule J18-354 outlines wiring methods, in Class III, Division 2 locations and requires

• threaded rigid metal conduit

• hazardous location cables

• electrical metal tubing

• armoured cable with overall jacket, such as TECK90, ACWU90, copper-sheathed RC90, or aluminum-sheathed RA90

• control and instrumentation cables with an interlocking metallic armour and a continuous jacket in control circuits (Type ACIC)

• Type TC cable installed in cable tray in accordance with Rule 12-2202

• Type CIC cable (non-armoured control and instrumentation cable) installed in cable tray in accordance with the installation requirements of Rule 12-2202 (2), providing the cable is rated 300V and the circuit voltage is 150 V or less and 5 A or less

• liquid-tight flexible metal conduit and connectors, marked for heavy duty

Rule J18-356 requires that switches, controllers, circuit breakers, and fuses in Class III, Division 2 locations be provided with a Type 5 enclosure or have close-fitting covers to prevent the escape of sparks or burning material.

Rule J18-358 requires that transformers, impedance coils, and resistors used as or in conjunction with control equipment for motors, generators, and appliances in Class III, Division 2 locations comply with Rule J18-308, which states that

• they be provided with enclosures conforming to Rule J18-258, and tight housings without ventilating openings, where not located in the same enclosure

• resistors and resistance devices have dust-tight enclosures marked for use in Class II locations, except when these devices are in the same enclosure with switching devices of the control equipment and are used only for starting or short-time duty, in which case the enclosure may conform to the requirements of Rule J18-306

Rule J18-360 requires that motors and generators and other rotating machinery installed in Class III, Division 2 locations conform to Rule J18-310.

Rule J18-360 applies to motors, generators, and other rotating electrical machinery installed in Class III, Division 2 locations and requires that

• they be totally enclosed non-ventilated, totally enclosed pipe-ventilated, or totally enclosed fan-cooled

• where only moderate accumulations of lint and flyings are likely to collect on, or in the vicinity of, a rotating electrical machine and the machine is readily accessible for routine cleaning and maintenance, be

     o standard open-type machines without sliding contacts or centrifugal or other types of switching mechanisms, including motor overload devices

     o standard open-type machines that have contacts, switching mechanisms, or resistance devices enclosed within tight housings without ventilating or other openings

     o self-cleaning textile motors of the squirrel-cage type

• motors, generators, or other rotating electrical machinery of the partially enclosed or splash-proof not be installed in Class III locations

Rule J18-362 outlines that every vent pipe for a motor, generator, other rotating electrical machine or enclosure for electrical equipment in Class III, Division 2 locations

• be dust-tight throughout its entire length

• lead directly to a source of clean air outside a building

• be metal not less than 0.52 mm (No. 24 MSG) thick or equally substantial noncombustible material

• be screened at the outer end

• have protection against mechanical damage and corrosion

Rule J18-364 requires that fixed or portable utilization equipment be marked for use in Class III locations, motors of motor-driven utilization equipment conform to Rule J18-310, and enclosures for switches, circuit breakers, and fuses conform to Rule J18-306.

Rule J18-366 requires that luminaires in Class III, Division 2 locations conform to Rule J18-316, which states that

• luminaires and portable lighting be complete assemblies marked for use in Class III locations and have the maximum wattage clearly marked

• each luminaire be protected against physical damage by a suitable guard or by location

• pendant luminaires be suspended by and supplied through threaded rigid conduit stems, and threaded joints be provided with set screws or other effective means to prevent loosening, and for stems longer than 300 mm, provided with permanent and effective bracing against lateral displacement at a level not more than 300 mm above the lower end of the stem, or flexibility in the form of a suitable fitting or flexible connector situated not more than 300 mm from the point of attachment

• luminaires be supported by boxes, box assemblies, and fittings marked for use in Class III locations

• starting and control equipment for mercury vapour and fluorescent lamps comply with Rule J18-308

Rule J18-368 requires that flexible cords be extra-hard usage type, contain a bonding conductor and be provided with glands marked minimally for use in Class II, Division 1 locations, where entering a a box or fitting required to be dust-tight.

Rule J18-370 specifies that receptacles and attachment plugs be a polarized type that affords automatic connection to the bonding conductor of the flexible supply cord; and be designed so that the connection to the supply circuit cannot be made or broken while live parts are exposed.

Rule J18-372 requires that

• signal, alarm, remote control, and communication systems, meters, instruments and relays contacts that interrupt other than voice currents be provided with a Type 4 or 5 enclosure or have close-fitting covers to prevent the escape of sparks or burning material

• the windings and terminal connections of transformers and choke coils carrying other than voice currents be provided with tight enclosures without ventilating openings

• resistors, resistance devices, thermionic tubes, and rectifiers carrying other than voice currents and exceeding 120 0 C, be provided with Class II dust-tight enclosures

Rule J18-374 requires that electric cranes, hoists, and similar equipment in Class III, Division 2 locations be installed as prescribed by Rule J18-324, which outlines the installation requirements where installed for operation over combustible fibres or accumulations of flyings, travelling cranes and hoists for material handling, travelling cleaners for textile machinery and similar equipment, and requires they conform to the following:

• the power supply to contact conductors be isolated from all other systems, ungrounded, and equipped with recording ground detection equipment that will give an alarm and will automatically de-energize the contact conductors in case of a fault to ground or provide a visual and audio alarm, maintained until the ground fault is cleared

• contact conductors be located or guarded and inaccessible to other than authorized persons and protected against accidental contact with foreign objects

• current collectors be arranged or guarded to confine normal sparking and prevent escape of sparks or hot particles, provide two or more separate surfaces of contact for each conductor to reduce sparking, and keep contact conductors and current collectors free of lint or flyings

• control equipment comply with Rules J18-306 and J18-308

Rule J18-376 specifies that storage-battery charging equipment for Class III, Division 2 locations be located in separate well ventilated rooms built or lined with non-combustible materials constructed to exclude flyings or lint.

Rule J18-378 outlines that other equipment marked with EPL Da, Db, or Dc protection may be installed in a Class III, Division 2 location with a temperature class not greater than T120 °C for equipment that may be overloaded, and not greater than T165 °C for equipment not subject to overloading.

In the next instalment, we will be discussing Annex J20 – Flammable Liquid and Gasoline Dispensing Service Stations, Garages, Bulk Storage Plants, Finishing Processes and Aircraft Hangers in the Class and Division System of Hazardous Locations Classification.

* The source for this series of articles is the Canadian Electrical Code, Part I, (C22.1-18) published by CSA.

** Note the CEC Handbook is also published by CSA.

William (Bill) Burr is the former Chair of the Canadian Advisory Council on Electrical Safety (CACES), former Director of Electrical and Elevator Safety for the Province of BC, and former Director of Electrical and Gas Standards Development and former Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting billburr@gmail.com.

 

Changing Scene

  • Prev
The Ontario government is introducing new measures to help tradespeople get their certification ...
This ECAA Annual Training Day & AGM hybrid event will take place May 27th – May 29th. ...
Technical Safety BC has reviewed the 2021 Canadian Electrical Code (CE Code) to assess the impacts ...
The Government of Canada is providing close to $5 million, over five years, to the National ...
Applications are now open online for the Increased Employment Incentive (IEI), which ...
As a non-profit organization, Skills Ontario relies on the support of partners to continue ...
Ideal Supply is proud to announce that as of January 1, 2021 they have appointed a new Sales ...
The energy storage ecosystem and the regulatory environment in which it operates are evolving ...
It's April, which means it's time for you to ignite your competitive spark with the a new challenge ...
MP Scott Duvall has introduced an amendment to the Income Tax Act regarding travel expenses for ...


 

www.liteline.com

 

 

 

 


 

Canadian Electrical Contractor Discussion Group: Can You Count the Deficiencies?

EIN CECD 400Have you ever been called to fix the work of a 'handyman'?

"Was supposedly done by a"certified ' electrician....told the homeowner that he got a $266 permit....no record at TSBC. Can you count the deficiencies?"

"There is a second panel change in the triplex also.......even more deficiencies. Think the guy was a glorified handyman. Ones not obvious: 240 BB heat hooked up 120....drier on 2p20....range on 2p50....water heater fed with 2c14 Bx on 2p15."

Go HERE to join the discussion

 


 

Ideal's Stay Wired to WinIt's April, which means it's time for you to ignite your competitive spark with the a new challenge from IDEAL Nationals Canada. This month, IDEAL is asking you to show off your electrical knowledge with the most correct answers.

Five professionals and five apprentice winners will each take home a $100 VISA gift card and forged wire stripper from IDEAL.

 

 

 

 

Read More


 



William (Bill) BurrBy William (Bill) Burr

Section 32 – Fire Alarm Systems, Smoke and Carbon Monoxide Alarms, and Fire Pumps, as outlined in Rule 32-000 Scope, is a supplementary or amendatory section of the code and provides additional and specific requirements for the location, installation, wiring, and protection, of

• local fire alarm systems

• permanently connected smoke and carbon monoxide alarms...

Read More


 

LumenpulseBy Matthew Payette

A lighting programming and control narrative is a document that is essential to coordinate the design/construction process with a fully realized final architectural product. It defines how lighting will integrate into the space and ultimately how humans will interact with that same space.

Sometimes there is a gap between the initial visions of the designers and the final product. Other times, the final product and operation of the lighting systems is achieved but after much project management distress...

Read More


 

Product News

  • Prev
MaxLite introduces the next generation of WallMax Open Face LED Wall Packs with field-selectable ...
Gotham has released its Incito™ 4” Direct-Indirect Wall Mount Cylinder luminaire. The new cylinder ...
Arlington's low cot MC cable fittings in a variety of sizes, are super convenient and ...
The Boca Flasher’s NanoLume has a streamline profile. It is a line voltage fixture perfect for Cove ...
120V AC Model, 24V DC Model, Model LB4R, cULus Listed. Type IC Rated – Approved for Direct Contact ...
 Available in Visual Comfort or Discrete optics configurations. Lumen packages from 1,600 to ...
For direct wire applications only. Consult factory for junction box sold separately. Aluminum cast ...
INFINA® DL-AC-FLEX2 is the next generation of high lumen output, specification grade, a flexible ...
Traditional in appearance, not in innovation. From below the ceiling, the Juno Podz take ...
The SLM is an ultra-slim, modern LED panel featuring edge-lit design for impressive visual comfort ...

 

11 Piece Insulated TorqueVario-S and SlimLine Blade Set• Individually tested to 10,000 volts AC and rated to 1,000 volts AC for safety and peace of mind.

• Meets VDE testing standards for protection against arc flash explosion.

• Torque accuracy of +/- 6% for confidence in precise tolerances.

• 33% narrower blade shafts for reaching deep set terminal block fasteners.

• Direct-molded insulation for protection against electrical shock and arc flash explosion.

Read More


 

 

FLIR TZ20 Dual Thermal Camera Drone PayloadPlug-and-Play Gimbal System for the DJI Matrice 200 Series and Matrice 300 Offers High-Definition FLIR Thermal Imaging with Zoom Capabilities to Improve Situational Awareness.

The FLIR Vue® TZ20, the first high resolution, dual thermal sensor gimbal purpose-built for the DJI®Matrice 200 Series and Matrice 300 airframes is now available in Canada. Featuring both a narrow-field-of-view and a wide-field-of-view 640x512 resolution FLIR Boson®thermal camera module, the Vue TZ20 offers greater situational awareness with a 20-times digital thermal zoom capability to complete public safety and industrial inspection missions both near and far. 

Read More


 

 

Autodesk TakeoffAutodesk, Inc. has announced the worldwide availability of Autodesk Takeoff, a new product that empowers estimators to perform 2D and 3D quantification workflows from a common data environment to increase collaboration, speed and accuracy during the estimation process.

Originally announced at Autodesk University in November 2020, Autodesk Takeoff will join Autodesk Build and Autodesk BIM Collaborate as part of the Autodesk Construction Cloud unified platform. The announcement comes one month after Autodesk Build and Autodesk BIM Collaborate were made available globally for Autodesk Construction Cloud customers. 

Read More


 

Peers & Profiles

  • Prev
Kyle Manfredi is the owner of ARK Electrical alongside his wife, Shannon. Operating out of ...
Like most major events over the last year, the COVID-19 pandemic put serious restrictions on the ...
This past December Jennifer Green was honoured with Canada’s Most Powerful Women Top 100 Award for ...
“It was quite surprising,” said Stephanie Smith of being named EHRC’s Leader of the Year. ...
As an advanced networked lighting controls company serving the industrial and large commercial ...
Trilliant, an international provider of utility solutions for advanced metering and smart grid ...
For more than a century, ABB has been investing in Canadian technologies and products to support ...
Mackenzie Gillan, a bright young lady from Baysville, Ontario, tells us about how she learned ...
Energy Efficient Lighting is a LED lighting manufacturer with nearly 30 years of industry ...
Dee Durant is an industrial electrician apprentice attending Conestoga College and an Ambassador ...


EIN Green 100 400

By Blake Marchand

This past December Jennifer Green was honoured with Canada’s Most Powerful Women Top 100 Award for the Skilled Trades category by WXN (Women’s Executive Network).

“It is truly an honour to be recognized by WXN and to be among this group of amazing women,” said Green of earning the distinction. “Throughout my career, I’ve worked with many great mentors and team members – to them, I say thank you for always inspiring me. I am absolutely thrilled.” Green is an industrial mechanic millwright by trade and works with Skills Ontario as Director of Competitions and Young Women’s Initiatives. 

Read More


 

Jo Istanbul Four Seasons ABy Owen Hurst

Recently, Electrical Industry Canada has developed a relationship with Women in Renewable Energy (WiRE), a non-for-profit group developing resources and networking potential for women and all working or planning to work within the renewable energy sector. Aside from being the WiRE President & CEO, Joanna Osawe is the Global Business Development Manager of Major Projects for DMC Power Inc.

EIN sat down with Osawe to learn more about WiRE and the substantial benefits it provides. Joanna is very personable and open regarding her career and her ambition, as well as the opportunities she is developing for women nationally and globally. 

Read More


 

Copper $US Dollar price per pound

Kerrwil Publications Great Place to Work. Certified December 2019 - December 2020

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2021 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil