Section 32 – Fire Alarm Systems, Smoke and Carbon Monoxide Alarms, and Fire Pumps, as outlined in Rule 32-000 Scope, is a supplementary or amendatory section of the code and provides additional and specific requirements for the location, installation, wiring, and protection, of

• local fire alarm systems

• permanently connected smoke and carbon monoxide alarms

• fire pumps required by the National Building Code of Canada as referenced in Appendix G

For further information, reference should also be made to Canadian Standard CAN/ULC – S524 Standard for the Installation of Fire Alarm Systems published by https://canada.ul.com/. Appendix B contains important additional helpful notes and the CEC Handbook also contains helpful information.

Fire alarm systems

Rule 32-100 specifies the requirements for insulated conductors and cables in fire alarm systems which include:

• copper material

• ampacity

• use of optical fiber cables

• use of stranded conductors

• insulation rated at 300 volts

• determining wire size for raceways or integral assemblies

• selection in accordance with rules 12-102(3) or 12-122(1)

Rule 32-102 outlines wiring methods for installation of insulated conductors:

• either in metal, non-metallic raceway, or having a metal armour or sheath

• where installed in buildings of combustible construction, conductors must be installed in accordance with Section 12

• conductors need to be installed independent of any other wiring except for point of supply, signal, ancillary device, or communication circuits and must be insulated for the highest voltage rated conductor

• communication circuits must conform to Section 60

Rule 32-104 requires that all exposed non-current-carrying parts of electrical equipment must be bonded to ground in accordance with Section 10, and that non-metallic fire alarm wiring systems must incorporate a bonding conductor. sized in accordance with Rule 10-616.

Rule 32-106 denotes that for electrical supervision, each circuit conductor terminal shall be independently terminated.

Rule 32-108 specifies that the fire alarm system power supply, except for included additional control units or transponders, be on a separate circuit and that the overcurrent devices and disconnecting means be permanently identified as a fire alarm system, be coloured red, and lockable in the on position.

Rule 32-200 provides installation requirements for permanently connected smoke alarms and carbon monoxide alarms in dwelling units that are required by the National Building Code of Canada (see Appendix G). The rule requires that

• smoke and carbon monoxide alarms be supplied from a circuit, such as a lighting only or mixed lighting and receptacle circuit

• that will provide an indication if shut off

• have no disconnect between the alarms and the branch circuit overcurrent device

• have no GFCI or AFCI device between the alarms and the branch circuit overcurrent device, except where a smoke, carbon monoxide or a combination smoke and carbon monoxide alarm has an integral battery as a secondary supply source

As an exception to the requirements of Rules 32-100 and 32-102, where a smoke alarm, carbon monoxide alarm and associated equipment circuit utilizes a Class 2 power supply for interconnection, Class 2 wiring methods may be used for buildings of combustible construction, in accordance with Rules 12-506 to 12-524.

Fire pumps

Rule 32-300 requires that insulated conductors for the supply of a fire pump supplied from the emergency power source have an ampacity not less than 125% of the full load current rating of the motor or sum of multiple motors and auxiliary motors, and be protected from fire exposure to provide continuing operation during a fire as required by the National Building Code of Canada (see Appendix G).

Rule 32-302 outlines the requirements for insulated conductors of fire pumps to be installed in metal raceways, in armour or metal sheathed cable, selected in accordance with Rule 12-102 (3) in rigid non-metallic conduit embedded in concrete, or electrical non-metallic tubing embedded in concrete.

Rule 32-304 provides that a separate service box for a fire pump and equipment may be installed in conformance with rule 32-306 below and, notwithstanding rule 6-102(2), may be located remote from other service boxes.

Rule 32-306 requires that no disconnecting means, overcurrent protection or device capable of interrupting the fire pump circuit may be placed between the service box from the normal power supply and the fire pump transfer switch or controller:

• except a circuit breaker that is permanently labeled identifying it as a fire pump disconnect.

• In addition, the circuit breaker must be lockable in the closed position and may be in the separate service box as in Rule 32-304 above.

• In the case where this circuit breaker is installed in an emergency power supply circuit between the emergency power source and the fire pump transfer switch, the rating of the circuit breaker shall be

◦ as per rule 28-200

◦ be set or rated to not less than the rating of the overcurrent protection provided integral with the fire pump transfer switch

◦ indefinitely carry the locked rotor current of the fire pump

◦ where it is installed in a normal supply circuit be rated not less than the overcurrent protection of the fire pump controller

• where the circuit breaker is installed in an emergency supply feeder between the emergency generator and the fire pump transfer switch, the feeder must bypass the generator main circuit breaker and be connected directly to the emergency generator.

Rule 32-308 requires that where an on-site electrical transfer switch is used to provide emergency power supply to a fire pump, it must be provided solely for the fire pump, located in a barriered or separate compartment or enclosure, permanently labeled as the fire pump power transfer switch, and suitable and marked for fire pump service. Where more than one fire pump is provided, a transfer switch is required for each fire pump.

Rule 32-310 provides that overload and overheating protection for branch circuit, control or equipment conductors shall not be required but shall be protected by the motor branch circuit overcurrent device.

Rule 32-210 specifies that ground fault protection shall not be installed in a fire pump circuit.


In the next installment, we will be discussing Section 34 – Signs and Outline Lighting.

William (Bill) Burr is the former Chair of the Canadian Advisory Council on Electrical Safety (CACES), former Director of Electrical and Elevator Safety for the Province of BC, and former Director of Electrical and Gas Standards Development and former Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting billburr@gmail.com.

* Source: CSA C22.1:21, Canadian Electrical Code, Part 1 - Safety Standard for Electrical Installations. © 2021 Canadian Standards Association. Please visit store.csagroup.org. With the permission of CSA Group, material is reproduced from CSA Group standard CSA C22.1:21, Canadian Electrical Code, Part 1 - Safety Standard for Electrical Installations. This material is not the complete and official position of CSA Group on the referenced subject, which is represented solely by the Standard in its entirety. While use of the material has been authorized, CSA Group is not responsible for the manner in which the data are presented, nor for any representations and interpretations. No further reproduction is permitted. For more information or to purchase standard(s) from CSA Group, please visit store.csagroup.org or call 1-800-463-6727.

Changing Scene

  • Prev
The Ontario government is introducing new measures to help tradespeople get their certification ...
This ECAA Annual Training Day & AGM hybrid event will take place May 27th – May 29th. ...
Technical Safety BC has reviewed the 2021 Canadian Electrical Code (CE Code) to assess the impacts ...
The Government of Canada is providing close to $5 million, over five years, to the National ...
Applications are now open online for the Increased Employment Incentive (IEI), which ...
As a non-profit organization, Skills Ontario relies on the support of partners to continue ...
Ideal Supply is proud to announce that as of January 1, 2021 they have appointed a new Sales ...
The energy storage ecosystem and the regulatory environment in which it operates are evolving ...
It's April, which means it's time for you to ignite your competitive spark with the a new challenge ...
MP Scott Duvall has introduced an amendment to the Income Tax Act regarding travel expenses for ...


 

www.liteline.com

 

 

 

 


 

Canadian Electrical Contractor Discussion Group: Can You Count the Deficiencies?

EIN CECD 400Have you ever been called to fix the work of a 'handyman'?

"Was supposedly done by a"certified ' electrician....told the homeowner that he got a $266 permit....no record at TSBC. Can you count the deficiencies?"

"There is a second panel change in the triplex also.......even more deficiencies. Think the guy was a glorified handyman. Ones not obvious: 240 BB heat hooked up 120....drier on 2p20....range on 2p50....water heater fed with 2c14 Bx on 2p15."

Go HERE to join the discussion

 


 

Ideal's Stay Wired to WinIt's April, which means it's time for you to ignite your competitive spark with the a new challenge from IDEAL Nationals Canada. This month, IDEAL is asking you to show off your electrical knowledge with the most correct answers.

Five professionals and five apprentice winners will each take home a $100 VISA gift card and forged wire stripper from IDEAL.

 

 

 

 

Read More


 



William (Bill) BurrBy William (Bill) Burr

Section 32 – Fire Alarm Systems, Smoke and Carbon Monoxide Alarms, and Fire Pumps, as outlined in Rule 32-000 Scope, is a supplementary or amendatory section of the code and provides additional and specific requirements for the location, installation, wiring, and protection, of

• local fire alarm systems

• permanently connected smoke and carbon monoxide alarms...

Read More


 

LumenpulseBy Matthew Payette

A lighting programming and control narrative is a document that is essential to coordinate the design/construction process with a fully realized final architectural product. It defines how lighting will integrate into the space and ultimately how humans will interact with that same space.

Sometimes there is a gap between the initial visions of the designers and the final product. Other times, the final product and operation of the lighting systems is achieved but after much project management distress...

Read More


 

Product News

  • Prev
MaxLite introduces the next generation of WallMax Open Face LED Wall Packs with field-selectable ...
Gotham has released its Incito™ 4” Direct-Indirect Wall Mount Cylinder luminaire. The new cylinder ...
Arlington's low cot MC cable fittings in a variety of sizes, are super convenient and ...
The Boca Flasher’s NanoLume has a streamline profile. It is a line voltage fixture perfect for Cove ...
120V AC Model, 24V DC Model, Model LB4R, cULus Listed. Type IC Rated – Approved for Direct Contact ...
 Available in Visual Comfort or Discrete optics configurations. Lumen packages from 1,600 to ...
For direct wire applications only. Consult factory for junction box sold separately. Aluminum cast ...
INFINA® DL-AC-FLEX2 is the next generation of high lumen output, specification grade, a flexible ...
Traditional in appearance, not in innovation. From below the ceiling, the Juno Podz take ...
The SLM is an ultra-slim, modern LED panel featuring edge-lit design for impressive visual comfort ...

 

11 Piece Insulated TorqueVario-S and SlimLine Blade Set• Individually tested to 10,000 volts AC and rated to 1,000 volts AC for safety and peace of mind.

• Meets VDE testing standards for protection against arc flash explosion.

• Torque accuracy of +/- 6% for confidence in precise tolerances.

• 33% narrower blade shafts for reaching deep set terminal block fasteners.

• Direct-molded insulation for protection against electrical shock and arc flash explosion.

Read More


 

 

FLIR TZ20 Dual Thermal Camera Drone PayloadPlug-and-Play Gimbal System for the DJI Matrice 200 Series and Matrice 300 Offers High-Definition FLIR Thermal Imaging with Zoom Capabilities to Improve Situational Awareness.

The FLIR Vue® TZ20, the first high resolution, dual thermal sensor gimbal purpose-built for the DJI®Matrice 200 Series and Matrice 300 airframes is now available in Canada. Featuring both a narrow-field-of-view and a wide-field-of-view 640x512 resolution FLIR Boson®thermal camera module, the Vue TZ20 offers greater situational awareness with a 20-times digital thermal zoom capability to complete public safety and industrial inspection missions both near and far. 

Read More


 

 

Autodesk TakeoffAutodesk, Inc. has announced the worldwide availability of Autodesk Takeoff, a new product that empowers estimators to perform 2D and 3D quantification workflows from a common data environment to increase collaboration, speed and accuracy during the estimation process.

Originally announced at Autodesk University in November 2020, Autodesk Takeoff will join Autodesk Build and Autodesk BIM Collaborate as part of the Autodesk Construction Cloud unified platform. The announcement comes one month after Autodesk Build and Autodesk BIM Collaborate were made available globally for Autodesk Construction Cloud customers. 

Read More


 

Peers & Profiles

  • Prev
Kyle Manfredi is the owner of ARK Electrical alongside his wife, Shannon. Operating out of ...
Like most major events over the last year, the COVID-19 pandemic put serious restrictions on the ...
This past December Jennifer Green was honoured with Canada’s Most Powerful Women Top 100 Award for ...
“It was quite surprising,” said Stephanie Smith of being named EHRC’s Leader of the Year. ...
As an advanced networked lighting controls company serving the industrial and large commercial ...
Trilliant, an international provider of utility solutions for advanced metering and smart grid ...
For more than a century, ABB has been investing in Canadian technologies and products to support ...
Mackenzie Gillan, a bright young lady from Baysville, Ontario, tells us about how she learned ...
Energy Efficient Lighting is a LED lighting manufacturer with nearly 30 years of industry ...
Dee Durant is an industrial electrician apprentice attending Conestoga College and an Ambassador ...


EIN Green 100 400

By Blake Marchand

This past December Jennifer Green was honoured with Canada’s Most Powerful Women Top 100 Award for the Skilled Trades category by WXN (Women’s Executive Network).

“It is truly an honour to be recognized by WXN and to be among this group of amazing women,” said Green of earning the distinction. “Throughout my career, I’ve worked with many great mentors and team members – to them, I say thank you for always inspiring me. I am absolutely thrilled.” Green is an industrial mechanic millwright by trade and works with Skills Ontario as Director of Competitions and Young Women’s Initiatives. 

Read More


 

Jo Istanbul Four Seasons ABy Owen Hurst

Recently, Electrical Industry Canada has developed a relationship with Women in Renewable Energy (WiRE), a non-for-profit group developing resources and networking potential for women and all working or planning to work within the renewable energy sector. Aside from being the WiRE President & CEO, Joanna Osawe is the Global Business Development Manager of Major Projects for DMC Power Inc.

EIN sat down with Osawe to learn more about WiRE and the substantial benefits it provides. Joanna is very personable and open regarding her career and her ambition, as well as the opportunities she is developing for women nationally and globally. 

Read More


 

Copper $US Dollar price per pound

Kerrwil Publications Great Place to Work. Certified December 2019 - December 2020

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2021 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil