Section 46 — Emergency Power Supply, Unit Equipment, Exit Signs, and Life Safety Systems

The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the information you need. This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendices B and G or the explanations of individual requirements contained in the CEC Handbook, but will hopefully provide some help in navigating the Code. These notes are based on the 25th edition.

Rule 46-000 Scope – states that Section 46 is a supplementary or amendatory section of the code and applies to the installation, operation, and maintenance of emergency power supply and unit equipment intended to provide power to life safety systems, exit signs, and illumination of exit signs in the event of failure of the normal power supply in cooperation with the requirements of the National Building Code of Canada. Appendices B, G and the CSA CEC Handbook provide additional explanations and diagrams.

Rule 46-002 – provides some special terminology for this section and defines emergency power supply, life safety systems and unit equipment in accordance with the terms in the National Building Code of Canada.

The Section is divided into 4 parts:

  • general rules, which applies to all emergency power supplies and unit equipment,
  • emergency power supplies,
  • unit equipment, and
  • exit signs.

General

Rule 46-100 specifies that an emergency power supply, including unit equipment must have adequate capacity for all the equipment that is connected to it in case of a normal power failure.

Rule 46-102 requires that complete instructions for operation, care and monthly testing be posted, under glass, and on the premises, in conformance with the National Building Code of Canada.

Rule 46-104 states that, where batteries are used as the emergency power supply, they must be maintained in proper condition and fully charged.

Rule 46-106 specifies that emergency lights must be on a dedicated emergency circuit, with no other lamps connected to it, and need to be arranged so that the area covered is illuminated even if any one lamp fails.

Rule 46-108 outlines the wiring method for all insulated conductors, with a few exceptions as noted below, required for life safety systems, emergency power supplies, exit signs and between unit equipment and remote lamps. In addition to the methods outlined in this rule, the National Building Code of Canada or Provincial Building Codes must be referenced for additional requirements for fire protection of insulated conductors and cables that may apply. For additional information see Appendices B and G. These methods include:

  • metal raceway of the totally enclosed type,
  • cable having a metal armour or sheath,
  • rigid non-metallic conduit, and,
  • electrical non-metallic tubing imbedded in at least 50mm of poured concrete or masonry.

Exceptions to this rule include:

  • insulated conductors and cables installed in buildings of combustible construction where rules 12-506 to 12-520 apply and may be run as NMSC or in totally enclosed non-metallic raceway, and
  • use of flexible cord and attachment plug for unit equipment in accordance with Rule 46-304(3).

In addition, the above noted insulated conductors and cables must be kept separate from all other insulated conductors and equipment, except for transfer switches and exit and emergency lights with two sources of supply. Also, the supply for any other electrical equipment that is not part of the “life safety system” must not enter any busway, splitter, or other enclosure that is part of the emergency power supply as per rule 46-208.

Emergency power supply

Rule 46-200 notes that Rules 46-202 to 46-212 only apply to central standby power sourced emergency power supplies.

Rule 46-202 outlines that emergency power supplies, in conformance with the National Building Code of Canada, must consist of:

  • an automatically rechargeable storage battery with sufficient capacity to maintain at least 91% of full load voltage for a minimum of 30 minutes; or
  • an automatically and failure-free starting and transferring generator conforming to CSA C282 with sufficient capacity to carry the full load of the emergency power supply.

Note that where storage batteries are used they should not be automobile or lead acid batteries unless of the totally enclosed glass-jar type, except by special permission granted under rule 2-030.

Rule 46-204 reaffirms that all insulated power, control, and communication conductors and cables required for emergency power supply, and installed outside the generator room, must, as per the requirements of the National Building Code of Canada, be protected against fire exposure to maintain continued operation.

Rule 46-206 specifies that an automatic transfer switch, solely accessible to authorized persons, that actuates upon failure of the normal power supply, must control the emergency power supply. Where an area is adequately illuminated by daylight and artificial light is only needed at night, an automatic light-actuated device may be used to control emergency illumination separately in this area.

Rule 46-208 requires that the overcurrent protection for an emergency power supply needs to be coordinated with OC devices ,for feeders and circuits supplying life safety and other emergency power supply equipment, to provide selective operation in the event of a fault.  These overcurrent devices must be accessible to authorized persons only.

An exception to this is where, in accordance with CSA C282:19

Emergency Electrical Power Supply for Buildings, or Rule 32-306 (6), the overcurrent protective devices are connected upstream of the main disconnecting means and overcurrent device connecting the generator to the emergency electrical power system, selective coordination between the overcurrent protective devices is not required.

Rule 46-210 outlines that all emergency power supplies need to be equipped with audible and visual trouble signal devices that:

  • warn of the normal source current failure,
  • indicate exit signs or life safety systems are supplied from the emergency power supply,
  • are connected so that they can be silenced, but continually show a red warning or trouble light, and
  • when the system is returned to normal, continue to audibly indicate the need to restore, or automatically reset, the silencing switch to normal. 

Rule 46-212 specifies that remote lamps, located some distance from the power supply, must have a voltage drop limited to 5% of applied voltage.

Unit equipment

Rule 46-300 outlines that Rules 46-302 to 46-306 apply to unit equipment for emergency lighting only, as defined in Appendix B. 

Rule 46-302 requires the bottom enclosure of unit equipment to be mounted at least 2 meters above the floor where practicable. Note that the definition of practicable includes the synonym “feasible”.

Rule 46-304 specifies the requirements that the supply connections for unit equipment include:

  • permanent connection, if the voltage exceeds 250 volts or 24 amps,
  • flexible cord and attachment plug located 2.5 meters above the floor and within 1.5 meters of the unit equipment, where the ratings above are not exceeded, and
  • automatic actuation upon failure of the normal lighting power supply to the area covered.

Rule 46-306 provides the requirements for remote lamps to unit equipment and requires that:

  • the voltage drop of insulated conductors be limited to 5% of the marked output voltage of the unit equipment,
  • remote lamps be included in the list of lamps provided for that unit, and
  • the number of lamps connected to a single unit does not exceed the power output rating of the unit for the duration of the emergency period.

Exit signs

Rule 46-400 requires that exit signs be:

  • connected to a dedicated circuit, except where connected to a circuit supplying emergency lighting in the same area,
  • illuminated by an emergency power supply, where emergency lighting is required by the National Building Code of Canada. Note that the NBC requires that exit signs be illuminated continuously, so no switch, time clock, or other disconnecting means, may be inserted in the circuit.

In the next installment, we will be discussing Section 50 — Diagnostic Imaging Installations. (Note: Sections 48 and 50 were deleted in the 23rd Edition)

[1] Source: CSA C22.1:21, Canadian Electrical Code, Part 1 - Safety Standard for Electrical Installations. © 2021 Canadian Standards Association. Please visit store.csagroup.org. With the permission of CSA Group, material is reproduced from CSA Group standard CSA C22.1:21, Canadian Electrical Code, Part 1 - Safety Standard for Electrical Installations. This material is not the complete and official position of CSA Group on the referenced subject, which is represented solely by the Standard in its entirety. While use of the material has been authorized, CSA Group is not responsible for the manner in which the data are presented, nor for any representations and interpretations. No further reproduction is permitted. For more information or to purchase standard(s) from CSA Group, please visit store.csagroup.org or call 1-800-463-6727.

[1] William (Bill) Burr is an associate member of the Canadian Electrical Code, Part 1, Technical Committee and formerly Chair of the Canadian Advisory Council on Electrical Safety (CACES), Chief Electrical and Elevator Inspector for the Province of BC & the Northwest Territories, Director of Electrical and Gas Standards Development and Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting billburr@gmail.com.

Changing Scene

  • Prev
Last week's disastrous floods have left many B.C. residents homeless, stranded or in desperate need ...
The Canadian Apprenticeship Forum (CAF-FCA) will launch a new program to empower skilled trades ...
Sean Dunnigan, President of Techspan Industries Inc., is pleased to announce the appointment of ...
The Electrical Safety Authority (ESA) would like to advise that the Minister of Government and ...
LabTest Certification Inc. is proud to announce its most recent recognition by OSHA as a Nationally ...
On November 13th, the Universal Women’s Network virtually hosted the 2021 Women of ...
Soussanna Karas, Director of Licensing at ESA, breaks down the risks of the underground economy ...
BCEA U40 group invites you to their Professional Development virtual series...     ...
Three accomplished women with diverse backgrounds are the newest members of Ontario Power ...


 

EIN ABB logo 400ABB is an international company with a large global presence, but did you know that a significant percentage of the products sold in Canada are also designed and manufactured locally?

ABB’s Installation Products division, formerly known as Thomas & Betts, operates seven manufacturing facilities in Canada, six of them in Quebec and one in Alberta.

Many of their most well-known brands, including IBERVILLE®️️, Marrette®️️, Microlectric®️️, and Star Teck®️️, are products that started in Canada and are still manufactured locally to meet Canadian standards.

 

 


 

Canadian Electrical Contractor Discussion Group: Can You Count the Deficiencies?

EIN CECD 400Have you ever been called to fix the work of a 'handyman'?

"Was supposedly done by a"certified ' electrician....told the homeowner that he got a $266 permit....no record at TSBC. Can you count the deficiencies?"

"There is a second panel change in the triplex also.......even more deficiencies. Think the guy was a glorified handyman. Ones not obvious: 240 BB heat hooked up 120....drier on 2p20....range on 2p50....water heater fed with 2c14 Bx on 2p15."

Go HERE to join the discussion

 


 



 

 Siemens Built In Isolation Products 400By Alyssa Kerslake

Life safety today is top of mind for nearly everyone. There is a certain level of trust that fire alarm systems continue to work within a fire incident. With system survivability being a key concern to regulators, building managers, and the public, Siemens has developed systems that are designed to meet and exceed regulations that protect people, property, and assets. 

One of the most significant concerns, particularly in a large multi-story building, is implementing a secure and fully functional fire alarm system. Today, it is not uncommon to have power and data for hundreds of fire alarm devices connected over a single pair of wires. The concern is, if a fault occurs somewhere between the devices, the zone and location of the device may no longer be known, or the operation of that circuit reduced or possibly impaired. These scenarios could allow an undetected catastrophic event to develop within the space due to inoperable life safety devices. 

 

Read More


 

 

David Gordon

By Terry Becker, P.Eng., CESCP, IEEE Senior Member

The CSA Z462 Workplace electrical safety Standard published its 2021 Edition in January.  A mandatory requirement for an employer is developing, implementing, and auditing an Electrical Safety Program.  If you have an Electrical Safety Program, is it up to date in its policies, practices and procedural requirements, is it performing as expected?  Workers do not necessarily do what you expect, they do what you inspect!  Management of change is required.

I have been involved in supporting industry with respect to shock and arc flash hazards in the workplace and in understanding what needs to be done to ensure worker safety, that effective defendable due diligence is established, and evidence of compliance is available related to occupational health & safety regulations both Provincial, Territorially or Federally.  I am in Ontario this week completing a detailed Electrical Safety Audit at multiple enterprise facilities.


Read More


 

Product News

  • Prev
On the hottest days of the summer and the coldest of the winter, the Napoleon NS18 heat pump and ...
Lumenwerx is pleased to launch Aera, an innovative lighting family that marks a new era in recessed ...
Eaton’s humidity sensor and fan control (HDFS3P1) device is a single pole humidity sensor for ...
With an EC motor and smart control, ORA-EC40 series air curtains are ideal for commercial and ...
Klein Tools expands its line of insulated screwdrivers with new lengths and tips, as well as a new ...
EarthTronics LED High Lumen Wattage & Color Selectable Series to provide flexibility and full ...
Eaton’s astronomic programmable timer (AT18HM) device reduces energy consumption by automating ...
The HomeGuard LED family of residential security lights, with rugged die cast aluminum ...
This preassembled constant wattage heating cable from Ouellet is specialized for roof and gutter ...


 

Milwaukee M12 Cable Stripper

Connect plug-in lamps, holiday lighting, and small appliances to the top “Controlled” outlet, while the bottom “Powered” outlet remains always on. The DW15R features tamper resistant receptacles with built-in shutters to prevent the insertion of unintended foreign objects. As well, the integrated button with vanishing feedback LED provides manual push-button on/off control and clear indiciation at any time.

Simplify control of the residence - schedule lamps and connected loads to turn on/off at specific times or based on sunrise/sunset, easily group smart devices into rooms, and create scenes to activate multiple loads at once. Utilize the auto-shutoff feature as a countdown timer in closets, hallways and bathrooms.

Read More


 

 

Incoplas Hybrid

Now available for Siemens Class 52 Actuators and Indicator Lights are the new Class 1, Div. 2 contact blocks. Suitable for use in Hazardous Location, Class 1, Div. 2 applications when used in a suitable enclosure. No matter which style actuator you use, the common base provided attaches to the hazardous location contact blocks easily.

Hazardous Location (HL) Series Contact Blocks are good for Hazardous Location CL1, DIV2 Applications using a Standard Enclosure NEMA 1, 12, 13, 4, 4X.

HL Series Contact Blocks are rated for switching high inrush loads like Tungsten Lamps.

 

Read More


 

 

EarthTronics 25-Watt Emergency Driver for Linear Highbay

The 20A Outlet and 15A Outlet have the ability to allow function specific Inserts to be installed/removed/swapped making this platform an optimal choice for renovations and new construction. The Swidget Outlet is installed using the same wiring as a standard wall receptacle and when paired with a Swidget Insert turns into a powerful and flexible Smart Home device. The swapability of the Inserts ensures that this will work with Smart Home wireless systems now and in the future.

The Swidget product line targets the Home Automation and Smart Home markets with a unique future-proof solution. Swidget currently offers eight smart Inserts with different functionalities including Wi-Fi control, indoor air quality sensor, temperature, humidity, and motion sensors, as well as a USB charger guide light, and emergency lighting. They can all be controlled from anywhere with the Swidget App for iOS/Android or Alexa and Google Home.

Read More


 

Peers & Profiles

  • Prev
Allana Kellett-Jamieson loves working in the electrical sector and is proud of the great focus ...
As the head of ABB Canada's electrification business unit, Éric Deschênes is no newcomer to the ...
Karen Pullen knows what it’s like to be the only woman on a construction site, and as a proud ...
As of February 2021, Martin Stephenson is the new President and CEO of Signify Canada.   ...
This past July, Kerith Richards, who has worked for Service Wire Company for the last seven years, ...
EngWorks was formed in 2004 as an electrical engineering and consulting firm by Allan Bozek, “After ...
Headquartered in Concord, Ontario, Mercury Lighting services national retail, ...
Among the recipients of the 2021 Clean50 Awards announced last month is Carolina Gallo, Vice ...
Sarah Silverstein is a principal with Liteline along side her two brothers Mark and Daniel. ...
As a 34-year-old female owner of an electrical contracting business, Danielle Gray may be unique. ...


EngWorksBy Blake Marchand

EngWorks was formed in 2004 as an electrical engineering and consulting firm by Allan Bozek, “After a short time we realized there was a niche in hazardous locations, in particular in hazardous area classification design requirements for various facilities. And also helping people understand just how the Canadian Electrical Code applies to hazardous locations.”

Given the complexity of hazardous locations, Bozek saw a need for education while working in the field and began developing training courses designed.

Read More


 

Éric DeschênesBy Line Goyette

As the head of ABB Canada's electrification business unit, Éric Deschênes is no newcomer to the electrical industry. He has a long track record and a passion for finding practical solutions to optimize technology adoption. Deschênes took on his current role with ABB January of 2020, he joined ABB in 2017 as Executive VP of the Electrification business after 15 years with Schneider Electric.

We met with him recently to discuss his new role at the helm of ABB Canada and his plans moving forward. He began by pointing out that the recent change to ABB Canada's structure, as elsewhere in the world, was made to make customer relations more straightforward. 

Read More


 

Copper $US Dollar price per pound

Kerrwil Publications Great Place to Work. Certified December 2019 - December 2020

538 Elizabeth Street, Midland,Ontario, Canada L4R2A3 +1 705 527 7666
©2021 All rights reserved

Use of this Site constitutes acceptance of our Privacy Policy (effective 1.1.2016)
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of Kerrwil