Faulty Wiring Energizes Houseboat, Exposes Swimmers to Electric Shock

Faulty

Sept 24, 2018

Two young swimmers became incapacitated due to electric shock while swimming in BC’s Lake Cowichan, but were saved by bystanders.

According to an alert published by Technical Safety BC, it appears that the houseboat became energized due to faulty wiring, a situation exacerbated by a lack of GFCI protection. This in turn energized the water and leaked current to a steel cable situated on a nearby dock. When the swimmers jumped into the lake from the houseboat, they inadvertently jumped directly into the path of the leaking current and sustained a debilitating shock.

The houseboat wiring had been altered and an alternating current (AC) circuit was added. Non-metallic sheathed cable (NMD90) fed receptacles and fridge. The fridge was capable of running on either 12V DC or 120V AC.

Testing revealed damaged non-metallic sheathed cable shorted out to a metal device box that housed a receptacle located at the forward part of the cabin. The short to ground was able to make a path back to its source through a 12V/120V fridge that was bonded to the aluminum hull of the boat via the 12V system.

The neighbour’s dock had a galvanized steel cable run along it, the cable ran up the bank between the two properties to where it was connected to a power pole guy line. The guy line anchor was located approximately seven feet from the neighbour’s service ground electrode. The steel cable was in the water directly across from where the swimmers jumped into the water. The steel cable through the guy line anchor and the neighbours service ground electrode was a good return path to the common transformer feeding both properties.

The facts and evidence strongly suggest that the houseboat became energized by faulty wiring. This was exacerbated by the lack of GFCI protection and possibly a poor bonding connection and or voltage drop that prevented the breaker from tripping. This in turn energized the water and leaked current to the steel cable on the neighbour’s dock. The swimmers jumped directly into the path of the leaking current.

The Canadian Electrical Code requires that all 15- and 20-amp receptacles feeding marinas, wharfs and similar structures be protected by Class A ground fault circuit interrupters (GFCI) which trip at 4-6 amps.

Photo source: Technical Safety BC. See more photos at www.technicalsafetybc.ca/alerts/faulty-wiring-energizes-houseboat-exposes-swimmers-electric-shock

Related Articles


Latest Articles


Changing Scene

  • Rexel Canada Welcomes Rexel USA Agreement to acquire Genuine Cable Group

    Rexel Canada Welcomes Rexel USA Agreement to acquire Genuine Cable Group

    October 19, 2026 “Rexel Canada welcomes Rexel USA agreement to acquire GCG (Genuine Cable Group)—a transformational step that will strengthen our capabilities, expand our reach and support continued growth across Canada, North America and global markets,” Rexel Canada CEO, Jeffrey Moyle announced on LinkedIn. GCG is a leading specialty infrastructure platform providing wire and cable,… Read More…

  • Ontario Announces Additional Funding for Training Seats for In-Demand Careers

    Ontario Announces Additional Funding for Training Seats for In-Demand Careers

    October 19, 2026  The Ontario government has allocated 40,000 new funded seats at publicly assisted colleges and universities to connect more students to good-paying, in-demand careers. This allocation, which is part of a broader $1.7 billion investment to support a total of 70,000 new seats, supports the province’s plan to protect Ontario and build a… Read More…

  • QEII Halifax Infirmary Tower Project Reaches Milestone, Wins Collaboration Award

    QEII Halifax Infirmary Tower Project Reaches Milestone, Wins Collaboration Award

    October 19, 2026 Construction of the new acute care tower at the QEII Halifax Infirmary has reached another milestone, with the Level 8 podium structure now in place. The podium is the lower, wider portion of the building that forms the base of the 14-storey acute care tower. It will house a range of hospital… Read More…

  • Ontario Starts Major Construction on Grimsby GO Station

    Ontario Starts Major Construction on Grimsby GO Station

    October 19, 2026 The Ontario government has awarded a contract for major construction on Grimsby GO Station, marking another milestone in its plan to protect Ontario by building the transportation infrastructure needed to reduce gridlock, shorten travel times and support economic growth across the province. Expected to be completed in the second half of 2027,… Read More…