Improve Test & Measurement Safety and Efficiency by Matching Thermal Imaging-Enabled Devices with the Appropriate CAT Rating

Flir

May 3, 2021

By Rob Milner, Global Business Development Manager, Condition Monitoring, FLIR Systems

When you think of test and measurement tools, you are most likely not thinking about thermal imaging. You might first think of traditional tools like non-contact voltage detectors, multi meters, clamp meters and videoscopes. Today, you can find electrical tools like clamp meters and multimeters integrated with thermal imaging capabilities. A primary benefit of this matchup is that users can now quickly and safely “visualize” potential electrical issues using thermal then verify volt and amp measurements, all with one tool. You can even find videoscopes with thermal imaging, enabling temperature readings on electrical equipment in hard-to-access places, such as underground utility vaults.

Thermal imaging captures relative temperature based off the target’s “emitted energy”. This is ideal for professionals that must do inspections with their target under full load conditions. Thermal allows the user to safety inspect for common issues like loose connections, load imbalances, and abnormal temp measurements from cables from 3 to 5 feet away from the given target. This allows the user to avoid approaching a potentially dangerous situation. Most electricians are not looking for precise temperature measurement, they are looking to see if there are any differences in temperature that are not typical with that target’s load or normal working conditions. Given this, the lower IR resolution capabilities embedded in test and measurement tools are sufficient if the arc-flash limit of approach allows. For applications where absolute temperature measurements are needed or the target is located at a greater distance, higher resolution thermal cameras may be required.

Users need to be aware that when using a test tool with integrated thermal imaging to perform electrical scans, there are several effects that can create false readings, specifically low emissivity surfaces, like shiny metals, reflections, forced convectional cooling such as wind, solar loading or low or no load targets. Given these situations, it is very important that users understand the basics around thermal imaging. It is highly recommended to take, at minimum, a basic thermography course to understand how to take and interpret a thermal image.

Simply put, when using a test tool with thermal imaging users can quickly and safety pinpoint potential issues allowing them to work more efficiently and to also be able to clearly verify the issue was properly fixed.

Understanding CAT Ratings

While thermal imaging is an ideal first step in visually identifying potential issues, now we need to consider when the test instrument is being used to collect voltage/amp data. This leads us to understanding the CAT rating of a test tool. Make sure all meters, test leads and probes have an adequate category (CAT) safety rating. Sometimes, the only thing standing between an electrical worker and an unexpected spike is their meter and test leads. If you use the wrong equipment with the wrong voltage, you could be putting yourself and others at risk. So, before conducting any test, make sure your choice of instrument is correct. Professionals should determine the proper category (CAT) rating required, based on the highest hazard exposure throughout their day.

The CAT rating method of classification, divided into four parts, known individually as category (CAT) ratings: CAT I, CAT II, CAT III and CAT IV, provide a quick and simple guide to match the right tools for the job. Understanding what each of these categories means is vital to avoid exposure to unnecessary risk, including significant injury or death. 

In the CAT ratings system, the roman numerals, (i.e., I through IV) refer to the location of a circuit in relation to the power source, defined in terms of the total potential transient voltage danger.   

• CAT I describes secondary circuits not intended to be connected to the mains electricity supply, such as personal electronics, and circuits powered by regulated low voltage sources. 

• CAT II is defined as local-level electrical distribution, such as a standard mains socket and plug-in loads. This category includes household appliances, such as washing machines, and portable plug-in power tools.  

• CAT III references a building’s electrical installations, including circuit-breakers, wiring, switches and industrial equipment.  

• CAT IV involves the source of the low-voltage power installation, essentially the power grid infrastructure, such as underground utility vaults or outdoor power lines.  
Figure 1

However, determining the appropriate voltage category is only half the story. Simply matching the presumed voltage to the test and measurement device will not provide adequate safety assurance. Failed electrical units can experience impulse or transient voltages on the order of many times a particular electrical tool’s rating. For example, a line may normally have a voltage of 120 or 240, but the transient voltage from a lightning strike can generate several thousand volts, causing a short circuit and arcing that may severely injure personnel working with inadequate equipment.  

IEC supplies a quick-reference chart to determine whether or not a given electrical tool is appropriate for the task at hand.

Rated Voltage

IEC 61010-1

2nd Edition

UL 61010B-1
(UL 31111-1)

 

CAT IV

CATIII

CAT II

CATIII

CAT II

CAT I

150V

4000V

2500V

1500V

2500V

1500V

800V

300V

6000V

4000V

2500V

4000V

2500V

1500V

600V

8000V

6000V

4000V

6000V

4000V

2500V

1,000V

12kV

8000V

6000V

8000V

6000V

4000V

Resistance

2-ohms

 2-ohms

12-ohms

 2-ohms

12-ohms

30-ohms

 

 

 

 

 

 

 

 

 

 

Matching the Right Electrical Tools for the Job

Included below are some test and measurement examples where thermal imaging and CAT ratings play a crucial role in the user’s safety and efficiency.

Multimeters
Thermal imaging-enhanced multimeters can help guide electrical professionals to the precise location of temperature anomalies and potential problems. For instance, when facing a maze of wires or scanning complex electrical panels for issues, that visibility is invaluable to pinpoint likely issues without requiring any direct contact with the test site. Once an issue is observed, leveraging a properly CAT rated multimeter’s current, voltage and other advanced functions will allow the user to accurately diagnose the equipment problem.

Clamp Meters
Clamp meters with built-in thermal imaging can eliminate guess work to quickly identify issues while keeping a safe distance from contact with panels, cabinets, or cluttered wires and cables that may present a safety hazard. For a situation where the issue appears to be a failing motor or compressor, a thermal camera-enabled clamp meter can help quickly verify the source—is it the power supply, or something else? For clamping around electrical conductors, ensuring the device has the right CAT rating for the job becomes crucial to maintaining an appropriate safety environment, no matter what additional precautions are taken.

Videoscopes
An industrial thermal and visual videoscope with a properly CAT rated probe tip can help professionals quickly and safely find hidden dangers in difficult-to-access locations, especially underground electrical distribution vaults. Crews can safely, efficiently, and effectively inspect vented manholes and identify potential problems without having to remove the cover or even having to enter the structure. This reduces the physical effort required, the time it takes to complete an inspection and enhances data collection activities to support regular infrastructure planning and maintenance.

Keeping Safety and Efficiency Top of Mind
Thanks to advances in test and measurement equipment with integrated thermal imaging technology electricians and service technicians have the ability to diagnose and solve electrical system problems quickly and safely. Another advantage is they can then go back with the thermal camera and take an image to verify that the work done has actually solved the problem. However, it is important to remember that although CAT ratings and thermal imaging provide an additional layer of safety, they are not a complete replacement of the other tried-and-true safety protocols, including wearing appropriate personal protective equipment (PPE) for the job and following all local and national safety codes, and ensuring that where jobs require extreme caution, the operator never works alone.

Related Articles


Latest Articles

  • Electrical Permit Requirements for Alarm System and Voice, Data, Video Installations

    Electrical Permit Requirements for Alarm System and Voice, Data, Video Installations

    January 19, 2026 Other than the exceptions listed below, electrical permits and inspections are required for all electrical work involved in the installation of intrusion and similar alarm systems in all structures. Electrical permits and inspections ensure that low -voltage systems are installed safely and in compliance with Code requirements. A permit and inspections must Read More…

  • The Role of Lighting in the AI-Powered Home

    The Role of Lighting in the AI-Powered Home

    January 14, 2026 Elizabeth Parks, President and CMO of Parks Associates, joins Derek Richardson, Founder and CEO of Deako, for a wide-ranging conversation on how lighting is becoming a core layer of the intelligent home. The discussion explores how Deako’s plug-and-play lighting approach is removing long-standing barriers to adoption by simplifying installation, reducing costs, and Read More…

  • What Canada’s Lighting Pulse Means for Contractors and Plant Buyers in 2026

    What Canada’s Lighting Pulse Means for Contractors and Plant Buyers in 2026

    January 14, 2025 By John Kerr From the ground, many contractors and plant teams are experiencing the same thing: jobs are there, but they are smaller, more price‑sensitive, and slower to release compared to past years. The Canadian Pulse of Lighting confirms that impression and offers some clear signals about how contractors and plant electrical Read More…

  • Guide to the Canadian Electrical Code, Part 1 – 26th Edition[i] – A Road Map: Section 54

    Guide to the Canadian Electrical Code, Part 1 – 26th Edition[i] – A Road Map: Section 54

    January 12, 2026 By Bill Burr The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the information you need. This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B or the Read More…


Changing Scene

  • Leviton Canada Partners with The Titan Group to Strengthen Midwest Presence

    Leviton Canada Partners with The Titan Group to Strengthen Midwest Presence

    January 19, 2026 Leviton Canada is proud to announce its partnership with The Titan Group, who will now represent Leviton’s Residential and Commercial & Industrial product lines across the Midwest provinces, effective January 1, 2026. “We’re excited to begin our partnership with Titan,” said Bill Tischner, Western Sales Director. “Their industry expertise, commitment to service, Read More…

  • Hammond Power Solutions Appoints Xavier Biot as Vice President, Strategic Accounts

    Hammond Power Solutions Appoints Xavier Biot as Vice President, Strategic Accounts

    January 19, 2026 Hammond Power Solutions is pleased to announce the appointment of Xavier Biot as Vice President, Strategic Accounts. In this role, he will lead HPS’s strategic account teams. He will partner with customers to align transformer and power quality solutions with evolving electrification, sustainability, and operational needs. His focus will be on helping Read More…

  • Hammond Manufacturing Expands to Western Canada

    Hammond Manufacturing Expands to Western Canada

    January 13, 2026 Hammond Manufacturing have announced that they are opening a new distribution facility in the Southeast of Calgary, Alberta. The new facility includes over 50,000 sq ft of warehouse space. “This addition will better serve our customers in Western Canada and stock volume and larger products to ensure our distributors have an improve stock Read More…

  • ABB Chosen to Supply Technology for BC Ferries’ New Major Vessels

    ABB Chosen to Supply Technology for BC Ferries’ New Major Vessels

    January 12, 2026 ABB will supply a complete package of power, propulsion and control technology for four new double-ended passenger and car ferries operated by British Columbia Ferry Services (BC Ferries). One of the largest ferry operators in the world, BC Ferries provides year-round vehicle and passenger service on 25 routes to 47 terminals, carrying Read More…