Guide to the Canadian Electrical Code, Part 1, 25th Edition– A Road Map: Section 84

February 28, 2023

By William (Bill) Burr


[i] Source: CSA C22.1:21, Canadian Electrical Code, Part 1 – Safety Standard for Electrical Installations. © 2021 Canadian Standards Association. Please visit store.csagroup.org. With the permission of CSA Group, material is reproduced from CSA Group standard CSA C22.1:21, Canadian Electrical Code, Part 1 – Safety Standard for Electrical Installations. This material is not the complete and official position of CSA Group on the referenced subject, which is represented solely by the Standard in its entirety. While use of the material has been authorized, CSA Group is not responsible for the manner in which the data are presented, nor for any representations and interpretations. No further reproduction is permitted. For more information or to purchase standard(s) from CSA Group, please visit store.csagroup.org or call 1-800-463-6727.

Section 84 — Interconnection of Electric Power Production Sources

(Note that Section 82 has been deleted from the Code) (The 25th Edition of the CE-C, Part I, (C22.1-21) * is available from CSA Group. This discussion of Section 84 is based on this edition).

Rule 84-000 notes that this is a supplementary or amendatory section of the code and applies only to the installation of power production sources interconnected with a supply authority system. These power production sources normally consist of consumer-owned electrical power generation equipment such as generators, photovoltaic systems, fuel cells, and micro-turbines that supply power to a local load and optionally to the supply authority system; and provide requirements for the electrical installation of consumer-owned electric power generation equipment that may operate in parallel with the supply authority system. Appendix B and the CEC Handbook have additional information and descriptions of these installations.

Section 84

Rule 84-002 states that arrangements for interconnection must be in accordance and compatible with the requirements of the supply authority. They must be no hazard to personnel or the public from a fault on either the supply authority system or the consumer-owned installation.

Rule 84-004 requires the provision of protection against backfeed into a supply authority system fault on all interconnected electric power sources. This type of electrical problem requires the supply authority system to be de-energized as soon as possible. The outputs of interconnected electric power production sources must provide protection against backfeed.

Rule 84-006 requires that electric power production sources be equipped with the means and equipment to establish and maintain a synchronous condition with the interconnected supply system and prevent any adverse effect. To ensure proper synchronization. Designers and installers need to pay attention to the phase relationship of the two sources if there is a voltage transformation between the two. The synchronization must be maintained once it is established with the use of voltage regulation.

Rule 84-008 requires that where there is a loss of voltage in one or more phases of the supply authority system, the interconnected electric power production source must be automatically disconnected and not be reconnected until the normal voltage of the supply authority system is restored. This is often referred to as anti-islanding protection. The supply authority may approve an alternate procedure where an inverter, designed to also serve as a disconnection device, that is suitable for interconnection with electric power production sources, may be used.

Rule 84-010 requires that where conductors and equipment are energized from both directions, overcurrent protection must be provided from each supply source.

Rule 84-012 requires that the rating of overcurrent protection for a transformer that is energized from both directions is determined under Section 26, by considering first one side of the transformer and then the other side, as the primary.

Rule 84-014 requires that each interconnected electric power production source installation must have additional devices as necessary for system stability and equipment protection. Other types of protection such as loss-of-excitation protection and over-excitation protection are also sometimes required to ensure system stability in the interest of public safety and equipment protection.

Rule 84-016 requires that ground fault protection per Rule 14-102 be provided.

Rule 84-018 requires that a consumer-owned power production system must monitor and automatically disconnect all phases from the interconnected system when there is a loss of power in any one phase.

Rule 84-020 requires that all ungrounded conductors of any electric power production source of an interconnected system, be provided with a disconnecting means that simultaneously disconnects all circuits supplied by the electric power production source equipment.

Rule 84-022 requires that all ungrounded conductors of any supply authority system electric power production source of an interconnected system, be provided with a disconnecting means that simultaneously disconnects all ungrounded conductors, avoiding imbalanced system voltages and false trips by protection devices and provides safety to personnel servicing the equipment. This gives the supply authority a single point of access to isolate one or more power production sources.

Rule 84-024 provides the general requirements for all disconnecting means used in an interconnected consumer-owned electric power production source installation so that personnel working on the electrical installation must be able to simultaneously disconnect all ungrounded conductors of the circuit, verify visually that the contact of the disconnecting means is open, and lock the disconnecting means in the open position. Additionally, the disconnecting means must:

  • be capable of being energized from both sides.
  • have contact operation verifiable by direct visible means if required by the supply authority (in accordance with Rule 84-002, to provide added assurance to supply authority workers that the circuit is open before work is initiated).
  • conform to Sections 14, 28, and 36 if it includes an overcurrent device.
  • be capable of being opened at rated load.
  • be capable of being closed with safety to the operator with a fault on the system.
  • disconnect all ungrounded conductors of the circuit simultaneously.
  • bear a warning to the effect that inside parts can be energized when the disconnecting means is open.
  • be readily accessible, and
  • where a main fusible disconnecting means is used, an isolating switch must be provided to allow the fuses to be dead during handling.

Rule 84-026 requires that isolating means be provided to isolate equipment that is energized from both directions from all ungrounded conductors of each source of supply. Electrical equipment (e.g., transformers, distribution equipment, fusible switches, and circuit breakers) energized from both directions cannot be serviced safely if there is no isolating switch to isolate it from both sources. The disconnecting means often acts as an isolating switch.

Rule 84-028 specifies that the grounding means at the service entrance may serve as the grounding means for the electric power production source in accordance with Sections 10 and 36. For renewable energy consumer-owned systems, the Rules in Section 64 apply.  In the case of a dc power source connected through a solid-state inverter, the inverter must not be grounded unless the inverter ac power is separated from the supply authority system by means of an isolating transformer.

Rule 84-030 requires that a warning notice and a single-line, permanent, legible diagram of the interconnected system be installed in a conspicuous place at the supply authority disconnecting means specified in Rule 84-022 and at the supply authority meter location.

In the next installment, we will be discussing Section 86 – Electrical Vehicle Charging Systems.

You can find the previous installment of Bill Burr’s Code series HERE.

Source: CSA C22.1:21, Canadian Electrical Code, Part 1 – Safety Standard for Electrical Installations. © 2021 Canadian Standards Association. Please visit store.csagroup.org. With the permission of CSA Group, material is reproduced from CSA Group standard CSA C22.1:21, Canadian Electrical Code, Part 1 – Safety Standard for Electrical Installations. This material is not the complete and official position of CSA Group on the referenced subject, which is represented solely by the Standard in its entirety. While use of the material has been authorized, CSA Group is not responsible for the manner in which the data are presented, nor for any representations and interpretations. No further reproduction is permitted. For more information or to purchase standard(s) from CSA Group, please visit store.csagroup.org or call 1-800-463-6727.

William (Bill) Burr is an associate member of the Canadian Electrical Code, Part 1, Technical Committee and formerly Chair of the Canadian Advisory Council on Electrical Safety (CACES), Chief Electrical and Elevator Inspector for the Province of BC & the Northwest Territories, Director of Electrical and Gas Standards Development and Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting billburr@gmail.com.

Related Articles


Latest Articles

  • Stephanie Medeiros on EV Infrastructure in Canada, Innovative Technologies, Well-Planned Charging Networks, & Commercial Fleets

    Stephanie Medeiros on EV Infrastructure in Canada, Innovative Technologies, Well-Planned Charging Networks, & Commercial Fleets

    September 3, 2026 By Blake Marchand In this Q&A with Stephanie Medeiros, the Head of Mobility at Schneider Electric Canada provides insight into her perspective on EV charging infrastructure in Canada, factors that will contribute to growing EV adoption, grid modernization for commercial fleets, the role of Vehicle-to-Grid and other innovative approaches to electrification. The focus of… Read More…

  • LEDVANCE: Understanding Light Beam Angles

    LEDVANCE: Understanding Light Beam Angles

    September 3, 2026 Light Beam Angles: How It Affects Different Types of Lighting, Where It Is Applied & What to Consider When Choosing the Right One Beam angle is important in lighting design. It determines how light spreads within a space and influences both functionality and atmosphere. By understanding beam angles, you can achieve both… Read More…

  • ITC 101 Series: Why Certifications (UL, CSA) Matter in Industrial Components

    ITC 101 Series: Why Certifications (UL, CSA) Matter in Industrial Components

    September 2, 2026 By ITC Electrical Components When selecting industrial electrical components, certification is more than a logo on a datasheet. A certification mark indicates that a product or component has been independently evaluated against specified requirements for its intended market. In North America, selecting products with the appropriate certification can affect regulatory acceptance, equipment… Read More…

  • Project Spotlight: Leigh Square Fountain

    Project Spotlight: Leigh Square Fountain

    September 2, 2026 In spring 2025, the City of Port Coquitlam unveiled a transformed Leigh Square, reimagined as a vibrant, accessible, and welcoming gathering place in the heart of downtown. At the heart of the renewed plaza, a Bellagio-style programmable dancing fountain is integrated directly into the paving—three interlocking rings where jets rise, fall, and… Read More…


Changing Scene

  • 2026 Ontario Apprenticeship Awards Call for Nominations

    2026 Ontario Apprenticeship Awards Call for Nominations

    September 3, 2026 Skilled Trades Ontario is proud to open nominations for the 2026 Ontario Apprenticeship Awards, recognizing outstanding apprentices, journeypersons, organizations and skilled trades leaders who are helping strengthen Ontario’s apprenticeship system. Award recipients will be announced at the Ontario Apprenticeship Summit on November 4, 2026, at the Toronto Congress Centre. Nominations must be submitted… Read More…

  • Bartle & Gibson Announces New Partnership with Hubbell Canada

    Bartle & Gibson Announces New Partnership with Hubbell Canada

    September 3, 2026 Bartle & Gibson Co. Ltd., an Alberta-based premier plumbing, heating and electrical distributor and Hubbell Canada have announced a new regional partnership enabling increased access to Hubbell Canada’s end-to-end electrical product portfolio across Western Canada. “With our strong presence in the west through 31 branches and counting located in Alberta, Saskatchewan, British… Read More…

  • Bartle & Gibson Opens Salmon Arm Location

    Bartle & Gibson Opens Salmon Arm Location

    September 3, 2026 Bartle & Gibson opened their new Salmon Arm location on July 20th. The Salmon Arm location features: This site is strategically positioned in the city of Salmon Arm, located near to the busy Picadilly Mall.  Salmon Arm branch is located at: 621- 10 Street SW Salmon ARM, BC V1E 1T1 Photo Source Read More…

  • MacKinnon Magnetics Announces Partnership with Resilient Sales Corporation in Northeastern Ontario

    MacKinnon Magnetics Announces Partnership with Resilient Sales Corporation in Northeastern Ontario

    September 3, 2026 MacKinnon Magnetics is pleased to welcome Resilient Sales Corporation as their newest sales agency partner. Resilient Sales will represent MacKinnon Magnetics across Northeastern Ontario, including the Districts of Muskoka and Parry Sound. Key markets include Sudbury, North Bay, Timmins, Kirkland Lake, Sault Ste. Marie, Huntsville, Bracebridge and Parry Sound. “This partnership expands… Read More…