Guide to the Canadian Electrical Code, Part 1 — Instalment 10

Hazardous Area Project

Feb 25, 2016

Bill Burr

The CE Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the information you need. This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook, but will hopefully provide some help in navigating the code. In this article: Section 18 Hazardous locations, Part 1.

Section 18 covers installation of electrical equipment in hazardous locations as defined in Section 0, such as areas in which there is a potential for the ignition of explosive or combustible gases, dusts, fibres or flyings due to the design, installation or use of electrical equipment.Since the information in this instalment is extensive, it will be presented in two parts. Part B will appear in the March 8 issue.

Rule 18-000 outlines the scope ofthis section, which is a supplementary section of the code and as such outlines additional or supplementary requirements for the selection and installation of electrical equipment in hazardous locations. In addition, Section 18 now uses the international zone system of area classification; however, in cases of addition or renovation to an existing installation classified to the Division system, the electrical equipment may be chosen and installed in accordance with Appendix J of the code. Also note that additional information is available in Appendices B and F.

Rule 18-002 provides special terminology definitions for terms used in this section, which are additional or supplementary to the definitions in Section 0.

Rule 18-004 divides the classifications into explosive gas atmospheres or explosive dust atmospheres. Reference material for area classification can be found in Appendix B. To use Section 18 you must determine the classification of the area in which you are working.

Rule 18-006: locations containing an explosive gas atmosphere are divided into zones 0, 1 or 2 depending on the frequency of occurrence and duration of an explosive gas atmosphere. Appendix B provides typical examples of explosive gas atmosphere classifications.

Rule 18-008: locations containing an explosive dust atmosphere are divided into Zones 20, 21, or 22 depending on the frequency of occurrence and duration of an explosive dust atmosphere. Appendix B provides typical examples of explosive dust atmosphere classifications.

Rule 18-010 specifies that alterations or repairs to equipment must be authorized and not be made to live equipment. In addition this rule specifies that electrical equipment in hazardous locations must be maintained in its original safe condition. Again appendix B provides additional guidance in developing proper maintenance procedures.

Section 18 is divided into three main parts covering
• general requirements
• explosive gas atmospheres
• explosive dust atmospheres

General

This rules in this part apply to all hazardous location installations, both explosive gas and explosive dust atmospheres.

Rule 18-050: the code requires that electrical equipment used in such locations be suitably designed, tested, and certified for the specific explosive atmosphere that will be present. This rule also provides groupings of various explosive gases and combustible dusts and fibres for which electrical equipment must be suitable. It also provides a hierarchy wherein electrical equipment suitable for a preceding group may also be suitable for a latter group.

Rule 18-052 lays out the marking requirements on electrical equipment intended for use in hazardous locations, which includes:
• letters “ex”
• method of protection
• group as per 18-050 above
• temperature rating
• equipment protection level
• for equipment for use in explosive gas atmospheres, the maximum surface temperature as per 18-052 (a),(b) and (3),(4), and (5)

For more specific marking information, please see Appendix B and my previous article – https://electricalindustry.ca/latest-news/1055-equipment-marking-for-hazardous-locations-in-cec-2015-23rd-edition.

Rule 18-054: equipment with an internal or external surface temperature equal to or higher than the ignition temperature of the combustible gas or explosive dust must NOT be installed in that location. This is true even for equipment that is not required to be approved for hazardous locations. While there is no definition of ignition temperature in this section, Appendix B has a chart that shows the ignition temperatures of various gas groups.

Rule 18-056: every separate area, section or room must have its own classification as a hazardous location.

Rule 18-058: if equipment rooms are intended to be hazard free in hazardous locations, they must be constructed of substantial, non-combustible materials and in such a way to ensure they remain hazard free. Where the equipment room communicates with a Zone 2 or an explosive dust atmosphere, it must be separated by close-fitting, self-closing doors. Where the equipment room communicates with a Zone 1 location, it must be considered a Zone 2 location unless ventilation and safeguards are in place as per Rule 18-002 and the definition of Zone 2(b).

Rule 18-060: when using metal-covered cable in hazardous locations, caution must be taken to ensure that
• any lightning related voltage surges on mineral-insulated cable are limited to 5 Kv,or
• circulating currents on single conductor armoured cable are eliminated

For the former, this is accomplished through the use of surge suppressors, For the latter, through bonding the metal sheaths together, at intervals of 1.8 m or less.

Alternatively, insulation jacketed cables can be used but the metal armour must be bonded to ground in the hazardous location and isolated in the non-hazardous location.
Rule 18-062: equipment rooms can be exempted from rules 18-100 to 18-158 if a continuous pressurized protective gas atmosphere is maintained.Appendix B has references to consult in accomplishing this. Note also that procedures must be in place to eliminate any possibility of an ignition source if pressurization fails.

Rule 18-064: there are three levels of energy limitation to provide intrinsically safe installations:
• ia permitted for Zone 0, Zone 1, Zone 2, Zone 20, Zone 21, or Zone 22, whichexempts from rules 18-102 to 18-254
• ib permitted for Zone 1, Zone 2, Zone 21, or Zone 22, which exempts from rules 18-102 to 18-254
• Ic permitted for use in Zone 2 or Zone 22, which exempts from 18-152 to 18-158 and 18-252 to 18-254

Appendix F provides additional information and recommended installation practice for installing intrinsically safe and non-incendive electrical equipment and wiring.

Rule 18-066: to avoid a build-up of dust on cables, cable trays should be open ladder type, covered or installed vertically.

Rule 18-068: in some hazardous locations, non-hazardous, non-arcing, sparking, or heat producingequipmentmaybe installedwhere there is a detection system that continuously monitors the area and activates an alarm, activates ventilation equipment, or de-energizes electrical equipment if a gas concentration reaches a percentage of the explosive limit.The percentage depends on the existence and continued operation of a ventilationsystem.Consult Appendix H for application, installation and maintenance recommendations.

Rule 18-070: where electrical equipment is in contact with flammable fluids, the primary seal must be constructed or installed to prevent any migration of such fluids through the wiring system.If this is accomplished through the use of a secondary seal, an indication or warning marking is required in case the primary seal fails.

Rule 18-072: the rules of Section 10 Grounding and bonding apply to hazardous locations. Additionally, where rigid metal conduit is used, threaded couplings and bosses on enclosures made up tight are required,unless incorporating internal bonding conductors.

Rule 18-074: only intrinsically safe equipment or cranes, hoists and similar equipment installed as per 18-250(2) are permitted to have uninsulated exposed parts in hazardous locations.

In the next instalment we will continue with Part B of Section 18.

* The source for this series of articles is the Canadian Electrical Code, Part I, published by CSA.

Read the rest of the instalments in the series:
Part 1: Guide to the CE Code, Part I – A Roadmap (Installment 1 in a Series)
Part 2:
A Road Map to the CE Code, Part I – Installment 2
Part 3: Guide to the Canadian Electrical Code, Part I – Installment 3
Part 4: A Road Map to the CE Code, Part 1 – Installment 4
Part 5: Guide to the Canadian Electrical Code, Part I — Installment 5
Part 6: Guide to the Canadian Electrical Code, Part I — Installment 6
Part 7:  Guide to the Canadian Electrical Code, Part I — Installment 7
Part 8: Guide to the Canadian Electrical Code, Part I — Installment 8
Part 9: 
Guide to the Canadian Electrical Code, Part I — Installment 9
Part 10: Guide to the Canadian Electrical Code, Part 1 – Installment 10
Part 11: Guide to the Canadian Electrical Code, Part 1 – Installment 11


 

William (Bill) Burr is the former Chair of the Canadian Advisory Council on Electrical Safety (CACES), former Director of Electrical and Elevator Safety for the Province of BC, and former Director of Electrical and Gas Standards Development and former Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting billburr@gmail.com.

 

Related Articles


Latest Articles

  • Ontario Drives Growth in Residential Building Construction in September

    Ontario Drives Growth in Residential Building Construction in September

    November 25, 2024 Investment in building construction rose 2.1% to $21.6 billion in September, following a 0.2% increase in August. The residential sector increased 2.9% to $15.2 billion in September, while the non-residential sector edged up 0.3% to $6.4 billion. Year over year, investment in building construction grew 6.7% in September. On a constant dollar basis (2017=100), investment in building construction increased 1.6% from… Read More…

  • Ontario’s Institutional Construction Intentions Push up the Non-Residential Building Permits in September

    Ontario’s Institutional Construction Intentions Push up the Non-Residential Building Permits in September

    November 25, 2024 The total value of building permits in Canada increased by $1.3 billion (+11.5%) to $13.0 billion in September, reaching the second-highest level since the start of the new series in January 2017. Ontario’s construction intentions grew by $1.2 billion (+25.0%) to $5.9 billion in September 2024, leading gains in both the non-residential and residential sectors. On a constant… Read More…

  • Red Seal Self-Assessment Questions

    Red Seal Self-Assessment Questions

    November 25, 2024 Each trade’s self-assessment tool is available to help you understand your own readiness for challenging the Red Seal exam in that trade. It goes through all topics that are included in the trade’s standard (Red Seal Occupational Standard/National Occupational Analysis) and asks you to reflect on whether you have the experience and knowledge in each… Read More…

  • Halifax Regional Municipality Seeking Deep Energy Retrofit Service Providers

    Halifax Regional Municipality Seeking Deep Energy Retrofit Service Providers

    November 25, 2024 Halifax Regional Municipality (HRM) is seeking qualified deep energy retrofit service providers to be added to its roster of approved contractors. Submit your response to be considered for future deep energy retrofit projects with HRM by the January 6 deadline. Go HERE for more information Read More…


Changing Scene

  • ITC Electrical Components Celebrates 30 Years of Service to the Electrical, Automation and OEM Market in Canada

    ITC Electrical Components Celebrates 30 Years of Service to the Electrical, Automation and OEM Market in Canada

    November 25, 2024 Celebrating its 30th anniversary, ITC Electrical Components has recently launched its new and improved website at www.itcproducts.com. After a successful 15-year career in the electrical components industry Luca Fontana founded ITC Electrical Components in 1994.  Since that time the company has grown from a home-based operation to a successful business with 15 employees and… Read More…

  • Eaton Canada Investing $15m to Expand Manufacturing Capacity

    Eaton Canada Investing $15m to Expand Manufacturing Capacity

    November 25, 2024 Eaton Canada is investing approximately $15 million to expand manufacturing capacity to meet growing demand for its electrical solutions driven by the ongoing electrification of Canada’s economy. These investments will expand the company’s low-voltage manufacturing footprint by 20%, increasing its ability to produce the switchboards, switchgear and panelboards needed to support Canada’s… Read More…

  • Bartle & Gibson Announces Partnership with Electric Avenue

    Bartle & Gibson Announces Partnership with Electric Avenue

    November 25, 2024 Bartle & Gibson Co. Ltd., a Western Canada-based premier plumbing, heating and electrical distributor, proudly announced a new regional partnership to distribute Electric Avenue, providers of convenient, affordable and easy-to-use smart charging solutions for residential and commercial use, across Western Canada. Electric Avenue was founded in 2021 with one simple mission: to… Read More…

  • Federal Investment to Add 989 New Montreal Homes

    Federal Investment to Add 989 New Montreal Homes

    November 18, 2024 The federal government is providing nearly $364 million to help build 989 new homes in Montreal. The announcement took place at 5200 rue de la Savane, in Montreal, which received $100 million dollars through the Apartment Loan Construction Program (ACLP) to build 303 homes and will be operated by Olymbec. This rental building, named Lynk, is designed to… Read More…