The CE Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the information you need. This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook, but will hopefully provide some help in navigating the code. In this article: Section 18 Hazardous locations, Part 2.

Section 18 covers installation of electrical equipment in hazardous locations as defined in Section 0, such as areas in which there is a potential for the ignition of explosive or combustible gases, dusts, fibres or flyings due to the design, installation or use of electrical equipment. Since the information in this instalment is extensive it is presented in two parts. This Instalment is Part 2.

Explosive gas atmospheres

This part contains rules for the installation of electrical equipment in all locations where explosive gas may be present.

Installations in Zone 0 locations

Rule 18-090 — Zone O is the hazardous location where explosive gas atmospheres are present continuously or for long periods and is the most restrictive. No electrical equipment or wiring may be installed in a Zone 0 hazardous location unless it meets the requirements of subrule 18-090 (2). Also note the marking requirements for Zone 0.

Rule 18-092 — seals are required where conduit leaves a Zone 0 location, and at the first point of termination of cables after entry to the Zone 0 location. Unbroken rigid conduit passing through a Zone 0 need not be sealed if the termination points are outside Zone 0. Seals are not required to be explosion-proof or flame-proof but must be identified for minimizing the passage of fluids or dusts and be accessible.

Installations in Zone 1 locations

Rule 18-100 — electrical equipment suitable for Class I Division 1 with protection level Ga or Gb and protection levels as outlined in 18-100(c) may be installed in a Zone 1 location.

Rule 18-102 — rigid metal conduit, hazardous location cables, explosion proof or flame proof “d” boxes, and fittings with threaded connection to conduit and cable glands shall be used for wiring in Zone 1. In addition, threads and joints need to comply with 18-102 (3), (4) and (5), and cables need to be supported to prevent stress at cable glands.

Rule 18-104 provides the rules for sealing conduits and cables entering enclosures in and leaving Zone 1 locations.

Rule 18-106 provides requirements for the installation of motors in Zone 1 locations. Additional guidance is given in Appendix B.

Rule 18-108 provides the rules for installation of Luminaires in Zone 1.

Rule 18-110 — flexible cords are permitted in Zone 1 where flexibility is required but must be installed in accordance with 18-110 (1) and (2).

Installations in Zone 2 locations

Rule 18-150 provides the rules for the installation of equipment in Zone 2. Note that equipment suitable for Class I Division 2 and Zone 0 and Zone 1 are permitted to be installed in Zone 2. Also note that transformers, capacitors, solenoids, and other non-arcing, non-sparking or non-heat-producing devices are permitted in Zone 2 locations.

Rule 18-152 provides rules for wiring methods in Zone 2.

Rule 18-154 provides rules for sealing conduit, cable and equipment in Zone 2.

Rule 18-156 provides rules on installation of luminaires in Zone 2.

Rule 18-158 — flexible cords are permitted in Zone 2 where flexibility is required but must be installed in accordance with 18-158 (1).

Explosive dust atmospheres

This part contains rules for the installation of electrical equipment in all locations where combustible and explosive metal dust may be present.
Installations in Zone 20 locations

Rule 18-190 — like Zone O, Zone 20 is the most restrictive hazardous location where explosive dust atmospheres are present in the form of a cloud of dust in air continuously or for long periods. No electrical equipment or wiring may be installed in a Zone 20 hazardous location unless it meets the requirements of Subrule 18-190.

Rule 18-192 provides requirements for wiring methods in Zone 20.

Rule 18-194 provides requirements for seals for a Zone 20 location.

Rule 18-196 — flexible cords are permitted in Zone 20 where flexible connections are required and shall be extra-hard-usage cord with cable glands.
Installations in Zone 21 locations

Rule 18-200 provides rules for installation of equipment in Zone 21. Equipment suitable for Class II Division 1 is permissible as well as equipment with the noted types of protection in (b) and ©.

Rule 18-202 — rigid metal conduit, hazardous location cables, explosion proof or flame proof “d” boxes, and fittings with threaded connection to conduit and cable glands shall be used for wiring in Zone 21. In addition, threads and joints need to comply with 18-202 (3), (4) and (5), and cables need to be supported to prevent stress at cable glands.

Rule 18-204 provides rules for sealing raceway equipment in Zone 21.

Installations in Zone 22 locations

Rule 18-250 provides rules for installation of equipment in Zone 22. Equipment suitable for Class II Division 2 is permissible as well as equipment with the noted types of protection in (b) and (c). This rule also provides rules for installation of cranes, hoists and other material handling equipment in Zone 22 locations.

Rule 18-252 provides rules for wiring methods in Zone 22.

Rule 18-254 provides the same sealing requirements as Zone 21.

In the next instalment we will discuss Section 20 — Flammable liquid and gasoline dispensing, service stations, garages, bulk storage plants, finishing Processes and aircraft hangars.

* The source for this series of articles is the Canadian Electrical Code, Part I, published by CSA.

Read the rest of the instalments in the series:
Part 1: Guide to the CE Code, Part I – A Roadmap (Installment 1 in a Series)
Part 2:
A Road Map to the CE Code, Part I – Installment 2
Part 3: Guide to the Canadian Electrical Code, Part I – Installment 3
Part 4: A Road Map to the CE Code, Part 1 – Installment 4
Part 5: Guide to the Canadian Electrical Code, Part I — Installment 5
Part 6: Guide to the Canadian Electrical Code, Part I — Installment 6
Part 7: Guide to the Canadian Electrical Code, Part I — Installment 7
Part 8: Guide to the Canadian Electrical Code, Part I — Installment 8
Part 9:
Guide to the Canadian Electrical Code, Part I — Installment 9
Part 10: Guide to the Canadian Electrical Code, Part 1 – Installment 10
Part 11: Guide to the Canadian Electrical Code, Part 1 – Installment 11


 

William (Bill) Burr is the former Chair of the Canadian Advisory Council on Electrical Safety (CACES), former Director of Electrical and Elevator Safety for the Province of BC, and former Director of Electrical and Gas Standards Development and former Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting billburr@gmail.com.

 

Related Articles


Latest Articles

  • EFC Scholarship Program Calls on Communities to Help Students Discover Careers in Canada’s Electrical Industry

    EFC Scholarship Program Calls on Communities to Help Students Discover Careers in Canada’s Electrical Industry

    May 20, 2026 As demand for talent continues to grow across Canada’s electrical and automation sector, Electro-Federation Canada (EFC) is calling on parents, families, educators, and community networks to help connect students with career opportunities through its 2026 Scholarship Program, now open for applications. With more than $160,000 in funding available across 60+ scholarships, the Read More…

  • EHRC Destination Trade Program for Third and Fourth-Year Apprentices

    EHRC Destination Trade Program for Third and Fourth-Year Apprentices

    May 14, 2026 Providing financial incentives of up to $5,000 to employers who create new Work-Integrated Learning (WIL) opportunities for third and fourth-year apprentices. Electricity Human Resources Canada’s (EHRC) Destination Trade program is Canada’s third- or fourth-year apprentice work placement initiative for the electricity industry, providing wage subsidies of up to $5,000 to small to Read More…

  • Record Attendance Marks Strong Return for MEET 2026

    Record Attendance Marks Strong Return for MEET 2026

    May 14, 2026 By Electro Federation Canada The Mechanical Electrical Electronic Technology (MEET) show saw a powerful return to Moncton, NB on May 6-7, setting a new attendance record with 7,532 participants attending the two-day event. The biennial show, now in its 26th edition, is touted as the premier industry trade show in the region Read More…

  • LLM Cybersecurity Is Now a Construction Cybersecurity Problem

    LLM Cybersecurity Is Now a Construction Cybersecurity Problem

    May 14, 2026 By Melvin Newman, PataBid CEO In a previous article, we covered how to write effective AI prompts and the real productivity benefits LLMs (large language models) can bring to construction estimating and operations. If you haven’t read it yet, it’s worth starting there. This article picks up where that one left off, Read More…


Changing Scene

  • Mac’s II Agencies Expands ABB Partnership into UPS Solutions

    Mac’s II Agencies Expands ABB Partnership into UPS Solutions

    May 21, 2026 As demand increases for resilient, always-on power for commercial, industrial, and mission-critical environments, Mac’s II Agencies is strengthening its Power Quality portfolio with ABB systems engineered for diverse conditions. With a broad range of sizes and configurations available, engineers, contractors, and end users can specify power backup and protection solutions with continued confidence, backed Read More…

  • EFC Conference Returns to Halifax with Focus on Industry Disruption and Growth

    EFC Conference Returns to Halifax with Focus on Industry Disruption and Growth

    May 20, 2026 Electro-Federation Canada (EFC) will bring together the electrical industry for its 2026 Annual Industry Conference, taking place June 2-4 at the Halifax Convention Centre. Under the theme “WaveMakers: Where Disruption Meets Direction,” the event will focus on the forces reshaping Canada’s electrical supply chain, including electrification, infrastructure investment, digital transformation, and evolving Read More…

  • STA Boxes Enters a Major New Growth Phase with Expanded Facilities

    STA Boxes Enters a Major New Growth Phase with Expanded Facilities

    In a market where speed, flexibility, and reliability have become essential, STA Boxes is reaching a major milestone in its growth journey. Read More…

  • EECOL Mississauga Branch Now Open

    EECOL Mississauga Branch Now Open

    May 19, 2026 To better support their customers across the Greater Toronto Area, EECOL Electric has opened a new branch in Mississauga. Located on Nashua Drive, this new location brings their trusted electrical products, knowledgeable team, and dependable service closer to your day‑to‑day work. Stop by to connect with the team and see how they Read More…