Guide to the Canadian Electrical Code, Part 1 — Installment 11

March 2 2016

William (Bill) Burr

The CE Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the information you need. This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook, but will hopefully provide some help in navigating the code. In this article: Section 18 Hazardous locations, Part 2.

Section 18 covers installation of electrical equipment in hazardous locations as defined in Section 0, such as areas in which there is a potential for the ignition of explosive or combustible gases, dusts, fibres or flyings due to the design, installation or use of electrical equipment. Since the information in this instalment is extensive it is presented in two parts. This Instalment is Part 2.

Explosive gas atmospheres

This part contains rules for the installation of electrical equipment in all locations where explosive gas may be present.

Installations in Zone 0 locations

Rule 18-090 — Zone O is the hazardous location where explosive gas atmospheres are present continuously or for long periods and is the most restrictive. No electrical equipment or wiring may be installed in a Zone 0 hazardous location unless it meets the requirements of subrule 18-090 (2). Also note the marking requirements for Zone 0.

Rule 18-092 — seals are required where conduit leaves a Zone 0 location, and at the first point of termination of cables after entry to the Zone 0 location. Unbroken rigid conduit passing through a Zone 0 need not be sealed if the termination points are outside Zone 0. Seals are not required to be explosion-proof or flame-proof but must be identified for minimizing the passage of fluids or dusts and be accessible.

Installations in Zone 1 locations

Rule 18-100 — electrical equipment suitable for Class I Division 1 with protection level Ga or Gb and protection levels as outlined in 18-100(c) may be installed in a Zone 1 location.

Rule 18-102 — rigid metal conduit, hazardous location cables, explosion proof or flame proof “d” boxes, and fittings with threaded connection to conduit and cable glands shall be used for wiring in Zone 1. In addition, threads and joints need to comply with 18-102 (3), (4) and (5), and cables need to be supported to prevent stress at cable glands.

Rule 18-104 provides the rules for sealing conduits and cables entering enclosures in and leaving Zone 1 locations.

Rule 18-106 provides requirements for the installation of motors in Zone 1 locations. Additional guidance is given in Appendix B.

Rule 18-108 provides the rules for installation of Luminaires in Zone 1.

Rule 18-110 — flexible cords are permitted in Zone 1 where flexibility is required but must be installed in accordance with 18-110 (1) and (2).

Installations in Zone 2 locations

Rule 18-150 provides the rules for the installation of equipment in Zone 2. Note that equipment suitable for Class I Division 2 and Zone 0 and Zone 1 are permitted to be installed in Zone 2. Also note that transformers, capacitors, solenoids, and other non-arcing, non-sparking or non-heat-producing devices are permitted in Zone 2 locations.

Rule 18-152 provides rules for wiring methods in Zone 2.

Rule 18-154 provides rules for sealing conduit, cable and equipment in Zone 2.

Rule 18-156 provides rules on installation of luminaires in Zone 2.

Rule 18-158 — flexible cords are permitted in Zone 2 where flexibility is required but must be installed in accordance with 18-158 (1).

Explosive dust atmospheres

This part contains rules for the installation of electrical equipment in all locations where combustible and explosive metal dust may be present.
Installations in Zone 20 locations

Rule 18-190 — like Zone O, Zone 20 is the most restrictive hazardous location where explosive dust atmospheres are present in the form of a cloud of dust in air continuously or for long periods. No electrical equipment or wiring may be installed in a Zone 20 hazardous location unless it meets the requirements of Subrule 18-190.

Rule 18-192 provides requirements for wiring methods in Zone 20.

Rule 18-194 provides requirements for seals for a Zone 20 location.

Rule 18-196 — flexible cords are permitted in Zone 20 where flexible connections are required and shall be extra-hard-usage cord with cable glands.
Installations in Zone 21 locations

Rule 18-200 provides rules for installation of equipment in Zone 21. Equipment suitable for Class II Division 1 is permissible as well as equipment with the noted types of protection in (b) and ©.

Rule 18-202 — rigid metal conduit, hazardous location cables, explosion proof or flame proof “d” boxes, and fittings with threaded connection to conduit and cable glands shall be used for wiring in Zone 21. In addition, threads and joints need to comply with 18-202 (3), (4) and (5), and cables need to be supported to prevent stress at cable glands.

Rule 18-204 provides rules for sealing raceway equipment in Zone 21.

Installations in Zone 22 locations

Rule 18-250 provides rules for installation of equipment in Zone 22. Equipment suitable for Class II Division 2 is permissible as well as equipment with the noted types of protection in (b) and (c). This rule also provides rules for installation of cranes, hoists and other material handling equipment in Zone 22 locations.

Rule 18-252 provides rules for wiring methods in Zone 22.

Rule 18-254 provides the same sealing requirements as Zone 21.

In the next instalment we will discuss Section 20 — Flammable liquid and gasoline dispensing, service stations, garages, bulk storage plants, finishing Processes and aircraft hangars.

* The source for this series of articles is the Canadian Electrical Code, Part I, published by CSA.

Read the rest of the instalments in the series:
Part 1: Guide to the CE Code, Part I – A Roadmap (Installment 1 in a Series)
Part 2:
A Road Map to the CE Code, Part I – Installment 2
Part 3: Guide to the Canadian Electrical Code, Part I – Installment 3
Part 4: A Road Map to the CE Code, Part 1 – Installment 4
Part 5: Guide to the Canadian Electrical Code, Part I — Installment 5
Part 6: Guide to the Canadian Electrical Code, Part I — Installment 6
Part 7: Guide to the Canadian Electrical Code, Part I — Installment 7
Part 8: Guide to the Canadian Electrical Code, Part I — Installment 8
Part 9:
Guide to the Canadian Electrical Code, Part I — Installment 9
Part 10: Guide to the Canadian Electrical Code, Part 1 – Installment 10
Part 11: Guide to the Canadian Electrical Code, Part 1 – Installment 11


 

William (Bill) Burr is the former Chair of the Canadian Advisory Council on Electrical Safety (CACES), former Director of Electrical and Elevator Safety for the Province of BC, and former Director of Electrical and Gas Standards Development and former Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting billburr@gmail.com.

 

Related Articles


Latest Articles

  • Investment in Single-Family Homes Continues to Rise for April

    Investment in Single-Family Homes Continues to Rise for April

    June 14, 2024 Month over month, investment in building construction increased 4.5% to $20.4 billion in March. The residential sector was up 5.4% to $14.3 billion, while investment in the non-residential sector increased 2.3% to $6.1 billion. On a constant dollar basis (2017=100), investment in building construction increased 4.1% to $12.5 billion in March. Investment in single-family homes continues to rise Investment in… Read More…

  • Record High Levels in British Columbia’s Multi-Unit Residential Construction Intentions for April

    Record High Levels in British Columbia’s Multi-Unit Residential Construction Intentions for April

    June 14, 2024 Month over month, the total value of building permits in Canada significantly increased 20.5% to $12.8 billion in April. Construction intentions in the residential sector increased 21.0% to $8.0 billion and the non-residential sector rose 19.6% to $4.8 billion, with growth observed in all components. British Columbia posted a record high monthly total value of building permits ($3.1 billion),… Read More…

  • ECAO’s Ontario’s Energy Future Sector Analysis Report

    ECAO’s Ontario’s Energy Future Sector Analysis Report

    June 14, 2024 Driven by economy-wide decarbonization efforts in response to the global climate crisis, Ontario’s electricity sector is rapidly evolving to enable the shift from fossil-based energy sources to clean energy sources. At the same time, with electrification of industry, transportation and more, it is abundantly clear that the demand for electricity supply is… Read More…

  • Planned Shift from Gas to Electric Heat Required to Avoid High Costs and Emissions: Report

    Planned Shift from Gas to Electric Heat Required to Avoid High Costs and Emissions: Report

    June 14, 2024 New research published today by the Canadian Climate Institute finds that a system-wide shift from gas to electric heat is the lowest-cost path through the clean energy transition. The report, Heat Exchange: How today’s policy choices will drive or delay Canada’s transition to clean, reliable heat, concludes that provincial government action will be  necessary to protect reliability and… Read More…


Changing Scene

  • ECAO Recognizes its 2024 R. Hugh Carroll Safety champions

    ECAO Recognizes its 2024 R. Hugh Carroll Safety champions

    June 17, 2024 The Electrical Contractors Association of Ontario’s R. Hugh Carroll Safety Awards demonstrate the ECAO’s commitment “to promoting and fostering a positive, safety-first culture amongst its membership, and the electrical industry”. This year’s honorees were recognized during the association’s 2024 annual general meeting at the Woodbine Trackside Clubhouse. “Every year it gets harder to pick… Read More…

  • Danielle Mayer – 2024 ECAM Award Recipient

    Danielle Mayer – 2024 ECAM Award Recipient

    June 14, 2024 Danielle Mayer’s journey to receiving the 2024 ECAM Award is one of dedication and determination. Danielle’s interest in the electrical trade sparked when she realized its potential as a hands-on career path, prompted by the suggestion from her friends that they needed an electrician among them. Beginning her exploration of the electrical… Read More…

  • CAF-FCA Unveils Trades Talent – An Innovative Speaker Connection Service at 2024 National Apprenticeship Conference

    CAF-FCA Unveils Trades Talent – An Innovative Speaker Connection Service at 2024 National Apprenticeship Conference

    June 14, 2024 The 2024 National Apprenticeship Conference saw an exciting announcement from the Canadian Apprenticeship Forum (CAF-FCA) with the launch of Trades Talent, an innovative online service designed to connect event planners with expert speakers in the skilled trades sector. This ground-breaking platform promises to be a game-changer for those seeking knowledgeable and engaging… Read More…

  • Atkore Announces Environmental Product Declarations for Steel and PVC Conduit Products

    Atkore Announces Environmental Product Declarations for Steel and PVC Conduit Products

    Atkore Inc. announced it has published Environmental Product Declarations (EPDs) for its Galvanized Steel, Stainless Steel, and PVC Conduit & Fittings portfolios. Verified by an independent third party, each EPD contains a product’s life cycle assessment that measures its environmental impact, such as greenhouse gas emissions, energy use, water consumption, waste generation, and other factors…. Read More…