Case Study: Temporary Power for Large Scale Residential Construction

Temporary Power

Ever wonder how large construction projects with sales offices and show suites get power when there is only a generator or temporary power established on the construction site?TheBC Safety Authority (BCSA) pays close attention to these types of installations, since fire alarms, sprinklers, and other building code safety systems are not up and running during the construction phase of the project.

Recently, a BCSA safety officer conducted an assessment of a large multi-family residential site under construction. Working collaboratively with electrical contractors, other trades, safety officials, utilities, and building departments to reach safety solutions is an important part of a BCSA safety officer’s role.

During the inspection, several significant hazards were found.Most notably, townhouses had been energized using the temporary construction service, creating a risk of overload to the service. Had these dwellings become occupied, this could have resulted in a serious fire and shock hazard.

An additional hazard was created by the power cable used to provide power from the temporary distribution system to the townhouses, which was not installed with the necessary mechanical protection.Construction sites typically have heavy machinery operating and it is imperative that the power cables be installed in a manner that protects them from mechanical damage.A break in the armoured cable can result in either a fire (if combustible material is near by) or a shock hazard if the bonding provisions have been compromised.

Addressing the hazards
The safety officer first documented his findings in a certificate of inspection and contacted the electrical contractor to develop a plan to rectify the identified non-compliances.The contractor submitted an application for a variance, as required by the Safety Standards Act, to energize the show rooms and sales offices.The variance included a request to energize a specific portion of the site, and outlined the wiring method used to provide power to this area of the site, and the signage required at strategic locations on the site, including mark ups on the site’s safety plans.The safety officer granted the variance and the electrical contractor completed the installation and the obligations outlined in the variance.

To reduce the safety hazards on the site, branch circuits inside each dwelling had all unnecessary circuit conductors disconnected from circuit breakers. The heavy loads such as space heating, furnaces, dryers, ranges were also disconnected.The safety officer then informed BC Hydro and the electrical contractor that a “hold connection” be placed on the permanent installation permit.This ensures that when the permanent installation is ready for power, the necessary work is completed to transfer and disconnect the temporary power in the showrooms to remove the risk of a possible back feed.

When dealing with sites that have both permanent and temporary electrical systems, closely review your electrical code, specifically the stating that interconnection of temporary power installations and permanent installations shall not be interconnected unless by special permission.

This article was first published online by the BC Safety Authority, http://safetyauthority.ca.

 

Related Articles


Latest Articles


Changing Scene

  • Munden Enterprises Earns Arlington’s Canadian Sales Achievement Award

    Munden Enterprises Earns Arlington’s Canadian Sales Achievement Award

    February 18, 2025 Arlington Industries Inc. is pleased to announce the recipients of its annual representative sales awards – for 2024 sales of Arlington’s MADE IN USA and many patented, innovative and labor-saving products. Presented to firms representing Arlington at the recent 2025 National Electrical Manufacturers Representatives Association (NEMRA) meeting in Orlando, Florida, these awards… Read More…

  • Have your Say on the Proposed Regulations for the NWT Builders’ Lien Act

    Have your Say on the Proposed Regulations for the NWT Builders’ Lien Act

    February 14, 2025 The GNWT is modernizing the legal framework for construction liens. In 2023, the Builders’ Lien Act was enacted to replace the Mechanics Lien Act. The new legislation was put in place to address modern construction practices. It sets out the legal processes, systems, rights, and remedies for parties involved in construction disputes.  The GNWT… Read More…

  • Federal Government Investing in Skilled Trades Training for Atlantic Canada

    Federal Government Investing in Skilled Trades Training for Atlantic Canada

    February 14, 2025 Canada is building more homes, bridges and key infrastructure than at any point in recent history. That requires skilled workers in communities across the country, including in the Atlantic provinces. To encourage more people to join the skilled trades, to build the homes Canadians expect and the resilient economy this moment demands,… Read More…

  • Nova Scotia Power Holding Open Houses to Discuss Modernizing the Electrical Inspections Process

    Nova Scotia Power Holding Open Houses to Discuss Modernizing the Electrical Inspections Process

    February 14, 2025 As Nova Scotia continues to experience unprecedented building growth, it’s the perfect time to review and improve the electrical inspection process—with safety as the top priority. Nova Scotia Power and the Department of Labour, Skills, and Immigration are coming together to explore new opportunities—including risk-based electrical inspections—to ensure the process remains safe,… Read More…