Canadian Buildings Are Safer than Ever!

April 6 2016

Jeff Beare 

Although it often goes unnoticed, emergency lighting has been safeguarding the public in buildings in Canada for several decades. The Canadian building code has been the national reference used to ensure that occupants are protected and have a safe and reliable means of evacuation out of Canadian buildings. Since the introduction of LED exit signs in the early 1990s, product development in this segment has been relatively static until recently. 

Emergency lighting has seen major development over the last decade with significant changes to the 2010 building code, which introduced the green “running man” and photoluminescent technology. In addition, LED chip technology has dramatically changed the performance and life of remote heads and battery units, and the most recent proposed changes to CSA C22.2 141-15 Emergency Lighting Equipment are tightening performance characteristics of a variety of products offered to the emergency lighting electrical industry.

Let’s look at three recent changes in greater detail.

1. Changes to the NBC

In 2010 the National Building Code of Canada (NBC) published a new standard for emergency lighting specifically related to exit signs whereas exit signs now consist of a green pictogram and a white or lightly tinted graphical symbol meeting the colour specifications referred to in ISO 3864 and to the dimensions indicated in ISO 7010.

 

 

 

 

 

 

 

 

 

 

 

 

The 2010 NBC also has provisions for non-electrically lit exit signs that spell out the use of “running man” graphical symbols and stipulates the use of photoluminescents as well as the method in which these signs are tested and applied. Photoluminescence is simply rare earth metals that have a unique characteristic of glowing in the dark when the ambient light that is used to energize the sign extinguishes. 

Photoluminescent exit signs must be ULC 572 compliant for 50, 75 foot and 100 foot visibility, and provide a green substitution for electrically powered signs. Another advantage of photoluminescence when properly used as outlined in the NBC, is that electrical wiring isn’t required and thus no direct electricity expense.

 

 

 

 

 

 

 

 

 

 

 

The changes to the NBC have been slowly implemented by Canadian provinces and territories, with Quebec being the last province to have adopted this new standard, which came into effect in June of 2015 with an 18-month transition period. 

2. The use of LED chip technology in remotes and battery units. 

Battery units and remote heads are the most commonly used, stand-by unit equipment in buildings throughout Canada. 

Battery unit:

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote unit:

 

 

 

 

 

 

 

 

 

 

 

 

Their operation is quite simple. When an emergency lighting unit senses a power failure (Ac fail), the relay on the circuit board which contacts are normally open, close allowing the DC power (from battery) to flow through them and to the remote(s) and exits illuminating them for the prescribed duration identified in the National Building Code. 

In this system, the lamp technology that has been the most commonly used in these applications has been incandescent or halogen with wattages ranging anywhere from 8watts quartz to as high as 70watts quartz. The standard lamp source and wattage commonly used has been the 9watt wedge base. Although the 9watts wedge is the standard lamp, the use of higher wattages and halogen MR16 type lamps are also commonly used when larger spacing’s, higher ceilings or greater light levels are required. 

With the introduction of LED chip technologies we have seen a dramatic change in the type of lamp sources required to achieve the performance criteria mentioned above. As an example, 9 watt tungsten lamps offer anywhere from 80 to 110 lumens , have an average life of 100 hours and achieve a rule of thumb spacing ranging between 15 and 25 foot spacing’s. By using 3 watts LED remotes we are seeing up to 100 000 hours of life, performances of up to 377 lumens and spacings ranging from 44 to 77 feet. The use of LED lamps has also increased the duration of battery units from 1 hour to over 4 hours. 

Example of a spacing comparison between 9 watt tungsten and 3 watt LED

Compare: where the building code requires an average of 1 foot candle and a minimum of 0.1 foot candle at the floor level along the path of egress on a 150’ x 9’ x 9’ corridor with an egress door at one end, a 150’ x 6’ path of egress, and an 8’ unit mounting height. 

Incandescent Lamp: standard wedge-base 9W • PAR18-12V09W • Quantity: 15 • Average: 1.00:

 

 

 

 

 

 

 

 

3W LED Lamp: PAR18-6V3W LED • Quantity: 2 • Average: 1.00:

 

 

 

 

 

 

 

 

The benefits of LED lighting are clear:

  • higher lumens resulting in increased spacings and therefore less remote units to install. In the above example, we have gone from 15x 9w double remotes to 2x 3w double remotes
  • longer life resulting in a more reliable and safe system
  • longer run times allowing the public more time to evacuate
  • economy passed on to the building’s owner — smaller battery sizes and less copper wiring between remotes

3. Changes to CSA141 (-15)

CSA has recently proposed changes to the current standard for emergency lighting CSA C22. 141-15. In these proposed changes, particular attention needs to be given to auto diagnostics/auto test.

An auto test is a means for an emergency lighting system to automatically test itself in order to comply with the National Fire Code of Canada. It states that emergency lighting should be tested for one minute once a month and full discharge once a year and again 24 hours after the yearly discharge. The rationale behind this is that all batteries must be cycled regularly. If not, similarly to the battery in an automobile, they will most likely not work.

The discharge is to simulate an emergency situation whereby NFC law is required to do so. CSA states that all emergency packs should be completely charged within 24hrs. The second discharge 24hrs later is to ensure that the product is ready for another power failure. 

NFC requirements are part of emergency standards and most manufacturers have some version of auto testing. CSA141-15 now has guidelines for auto test, which take into consideration that diagnostic systems should be tested to ensure they do the following:

  • automatic testing every 30 days or less, verify/monitor load transfer, verify/monitor battery charge operation, and have a visual diagnostic with markings adjacent to the status indicators
  • maintain normal intended operation regardless of the functional status of the auto test, meaning if during an auto test if the AC fails the battery unit will default to full emergency mode

This standard also has provisions for optional centralized computerized monitoring systems, enhanced visibility, and exit sign flashing options, and has defined testing criteria for temperature environments. 

To recap, the green running man offers increased brightness and visibility when compared to traditional exit signs, and is understood by all nationalities. Building owners and managers now have the choice to add photoluminescence to signage, stairwell markings and supplemental directional signs, creating a redundant emergency system. The use of LED chip technology allows for increased light levels and over 100 000 hours of life, and increases battery back-up run times. And as prescribed by the NFC and now regulated by CSA141-15, if selected, the auto test/diagnostic option for battery units ensures that battery units will be in proper working order in the advent of a true emergency. We can safely say that Canadian buildings are truly safer than ever!

* CSA C22.2 141-15 Emergency Lighting Equipment applies to exit signs, unit equipment, emergency luminaires, and central power systems intended for connection to circuits with nominal voltages of 600 V and less and providing illumination in the event of a failure of the normal power supply for nonhazardous locations in accordance with the Rules of the Canadian Electrical Code, Part I. 


Jeff Beare is Vice President of Marketing at Stanpro Lighting. He has over 21 years in the lighting industry, has spent the last 10 years at Stanpro Lighting in the capacity of Vice President of Marketing, and is heavily involved in product development. He sits on Electro-Federation Canada’s lighting committee and has chaired the Emergency Lighting subcommittee.

Related Articles


Latest Articles

  • Take the Lesson

    Take the Lesson

    September 2, 2024 By Keith Sones, seasoned utility industry executive “I really don’t want to do this.” “You have to Keith. You have no choice. You can’t leave him hanging” replied my wife. I stared at the phone like a child looks at liver on their plate. They know you have to eat it but also… Read More…

  • Quebec Drives the Growth in Residential Building Construction in June, 2024

    Quebec Drives the Growth in Residential Building Construction in June, 2024

    Investment in building construction grew 2.8% to $21.4 billion in June, after a slight increase of 0.8% in May. These increases partly reflect April’s record high of $13.4 billion in total building permits value, since investment levels for a given period are driven by permits issued in prior months. The June increase in investment in building construction was primarily… Read More…

  • Western Memorial Regional Hospital Sets New Infrastructure Precedent and Receives LEED Silver Certification 

    Western Memorial Regional Hospital Sets New Infrastructure Precedent and Receives LEED Silver Certification 

    August 16, 2024 The new Western Memorial Regional Hospital in Corner Brook is home to Canada’s largest geothermal system, which has set a precedent for modern infrastructure for both Newfoundland and Labrador and North America. The geothermal field is approximately 600 feet below the hospital’s parking lot, and provides 100 per cent of the ground… Read More…

  • Brightening Communities: LED Technology in Action

    Brightening Communities: LED Technology in Action

    August 15, 2024 By Alex Price, Brand & Planning Manager, Current LightingTechnical Contributor: Gary Steinberg, Senior System Manager (Outdoor LED Fixtures), Current Lighting As the landscape of Canadian cities continues to evolve, the importance of outdoor lighting cannot be overstated. From enhancing public safety to promoting economic activity and fostering a sense of community, well-planned… Read More…


Changing Scene

  • Schneider Electric Launches SMART Buildings Division to Drive Sustainable Building Innovation in Canada

    Schneider Electric Launches SMART Buildings Division to Drive Sustainable Building Innovation in Canada

    Schneider Electric is transforming its Digital Buildings business in Canada with the launch of the SMART Buildings Division. This evolution marks a strategic move to deliver comprehensive solutions and services that support building owners and operators in achieving their decarbonization and sustainability goals. The demand for smart buildings is surging, driven by a global shift… Read More…

  • Introducing Alan Bearden as Interim President of Southwire Canada

    Introducing Alan Bearden as Interim President of Southwire Canada

    September 4, 2024 Southwire Canada is pleased to announce that Alan Bearden has been appointed Interim President. In this role, Alan will provide leadership and guidance for Southwire’s Canada-based organization, ensuring continuity and driving growth during this transitional period. Alan Bearden brings a wealth of experience to the position, having joined Southwire in 2008. Over… Read More…

  • A Partnership Between Electromag Graybar Canada and Phoenix Contact

    A Partnership Between Electromag Graybar Canada and Phoenix Contact

    September 3, 2024 Electromag Graybar Canada, a pioneer in industrial automation solutions and pneumatic products, is excited to announce a partnership with Phoenix Contact, a global leader in electrification, networking, and industrial automation. This collaboration, which initially began in the Langley and Ontario branches, is now expanding to Quebec. The alliance aims to provide cutting-edge… Read More…

  • Sonepar Announces the Retirement of William (Bill) C. Smith, Electrozad Director of Transitional Business

    Sonepar Announces the Retirement of William (Bill) C. Smith, Electrozad Director of Transitional Business

    September 2, 2024 William (Bill) C. Smith, Director, Transitional Business of Electrozad Supply Company Limited announced his retirement as of August 30th, 2024 after 49 years of leadership. Bill began his electrical career working part-time at Electrozad Supply while completing a Sales & Marketing Program at St. Clair College.  After his first full-time position in… Read More…