Key Factors to Maintaining Arc Flash Safety, Part 2

Arc Flash Safety - Part 2

 

 

When an arc fault occurs, the result is a massive electrical explosion. The light and heat emitted by the explosion is known as the arc flash, and the pressure wave is known as the arc blast. An arc flash releases hot gases and concentrated radiant energy up to four times the temperature of the sun’s surface, which can melt metal and cause severe radiation burns, damage eyesight, and result in fatalities. The accompanying pressure waves can damage hearing or brain function and send loose equipment, tools, machinery, and debris flying to cause further injuries. Even if an arc blast doesn’t injure a person, it will damage equipment and cause downtime.

Part 1 of this article looked at four of seven arc flash safety measures:
1.    train on safe work practices
2.    de-energize equipment before accessing
3.    perform regular preventive maintenance
4.    wear arc rated PPE within arc flash danger zone

Part 2 continues, with three more arc flash safety measures.

5. Select test tools rated for the environment
Test tools, test probes, flexible clamps, and other accessories are considered part of personal protective equipment (PPE) and must meet safety requirements established by such organizations as ANSI, the Canadian Standards Association (CSA), and the International Electro-Technical Commission (IEC). Make sure your meter and accessories have the appropriate CAT and voltage rating for the electrical environment in which you will use them.

It is important to consider both the CAT and voltage ratings. For example, a CAT III 1000 V meter offers superior protection to a CAT III 600 V rated meter, but a CAT II 1000 V rated meter is not superior to a CAT III 600 V rated meter. That is because in calculating the voltage-withstand ratings, IEC 61010-1 test procedures take into account steady-state voltage, peak impulse transient voltage, and source impedance. The following chart shows those values in context of the top three CAT ratings.

safety Chart

CAT II  208 V/120 V
CAT III  208 V/120 V
CAT III  240 V VFD
CAT III  Fixed mount load
CAT IV  Utility supply

6. Extend your safety zone with non-contact or wireless test tools
Non-contact test tools allow you to take readings on an energized part without making contact. Wireless test tools enable you to attach the probes or clamp to the measurement target and remove yourself from the arc blast zone to read the results. Full PPE is still required whenever making contact with the energized system; however, non-contact tools may allow you to reduce the amount of PPE required while reading the measurement from a distance.

Here are some of the most common non-contact and wireless tools for electrical inspections:
¥    Non-contact voltage detectors allow you to detect voltage during quick power checks without making contact with an energized part. Keep in mind that voltage detectors will only indicate power on the ungrounded side of the circuit; not on the grounded or neutral conductor side.
¥     Infrared thermometers measure temperature from up to several feet away. Just point the tool’s laser beam at the target and read the results on the display. This saves having to climb ladders, reach around hot, rotating equipment or reach into of live panels. Infrared thermometers are available a range of temperatures and accuracy levels.
¥    Visual infrared thermometers combine the convenience of a spot thermometer with the visual benefits of an infrared camera, providing accurate temperature readings at safe distances well beyond shock and arc flash boundaries. In addition to the standard IR thermometer features, visual thermometers provide an infrared heat map that blends with a standard digital image for quick identification of overheated conductors and terminations that could indicate pending equipment failures and possible arc flash issues.
¥    Infrared cameras capture thermal images of electrical components from beyond the arc flash boundary that can be used to readily distinguish temperature differences of components within the image (some degree of PPE is still required, see NFPA 70E). This helps operators quickly determine if corrective action is needed, and even how soon. According to the International Electrical Testing Association (NETA) a temperature difference between similar components under similar load between 4 °C and 15 °C indicates a problem with the higher temperature component, which should be repaired when possible. A temperature difference of greater than 15 °C, indicates the need for immediate repairs.

• Laser distance meters can be used to measure the lengths of conductor runs between equipment when conducting an arc flash study. This allows many distance measurements to be taken safely from the floor by just one person.
• Remote display multimeters allow technicians to attach the meter and probes (or clamp) at the measurement point and remove the display unit to a safe distance—or a better angle—to read the results. This allows you to close the door on a motor control centre or stand at a safe distance as you measure motor inrush current.
• Wireless tools provide the most advanced technology for enhancing safety. With Fluke Connect-enabled test tools you can set up multiple remote modules at the equipment and read the results on a digital multimeter up to 20 meters away or on a smart phone (iOS and Android). With the free Fluke Connect mobile app downloaded to your smart phone you can read results from any of more than 20 different Fluke test tools (up to 10 at a time) and quickly identify and diagnose problems on energized equipment from a safe distance, well outside of electrical shock or arc flash boundaries. This can reduce the need for cumbersome PPE.

7. Install IR windows in panels
Installing properly certified infrared (IR) windows allows technicians to inspect electrical equipment without removing the panel cover. That makes it easier for companies to comply with NFPA 70E when inspecting switchgear and motors. In selecting IR windows, look for
• High visibility for thermal and visual inspections
• Certification for the highest arc blast test ratings—IEEE C37.20.7: 63 kA arc tested at KEMA
• Grounding to the metal enclosure to avoid the release of static electricity
• Easy to open covers that are easy to keep track of and reduce the technician’s time within the hazard area

By installing IR windows that match these requirements you can significantly reduce work permit and NFPA 70E requirements for switchgear inspection.

Conclusion
Arc flash and arc blast are very real dangers in today’s industrial electrical environment. By following best practices, using the proper equipment, and staying as far away from energized components as possible you can reduce your risk of those events and work smarter and safer.

Read Part 1 here.

Source: Fluke Digital Library @ www.fluke.com/library.

Related Articles


Latest Articles

  • Lighting Case Study: Metro Toronto Convention Centre

    Lighting Case Study: Metro Toronto Convention Centre

    September 27, 2024 Goal: Upgrade the outdated 350-450-Watt metal halide lighting technology at the Metro Toronto Convention Centre (MTCC) with high-performing, energy-efficient, long-lasting, and low-maintenance LED fixtures from LEDVANCE Products Installed: 1,431 200-Watt UFO High Bay Fixtures from LEDVANCE, which are ideal replacements for metal halide lighting Benefits: LEDVANCE LEDs slashed the MTCC’s previous lighting… Read More…

  • The Consulting Engineer’s Guide to Advanced Electric Boiler Technology

    The Consulting Engineer’s Guide to Advanced Electric Boiler Technology

    September 27, 2024 An international boiler expert helps industry professionals take advantage of high voltage electrode boilers’ virtually 100% efficient, zero-emission capabilities, providing guidance on selection and installation For consulting engineers tasked with planning, designing, and supervising construction projects for a wide range of industries, advanced electric boilers – particularly high voltage electrode boilers –… Read More…

  • Just Getting Started – Discussing Milwaukee’s 100 Year Anniversary with President of Milwaukee Tool Canada, John Myers

    Just Getting Started – Discussing Milwaukee’s 100 Year Anniversary with President of Milwaukee Tool Canada, John Myers

    September 23, 2024 By Blake Marchand It goes without saying that the Milwaukee brand is historic. Their longevity is a testament to company culture and innovation. As this year marks Milwaukee’s 100th anniversary, the company held a tree planting ceremony earlier in the year to mark the milestone, planting 100 trees in partnership with Tree… Read More…

  • ECABC Provides Platform Recommendations to BC Political Parties

    ECABC Provides Platform Recommendations to BC Political Parties

    September 23, 2024 The Electrical Contractors Association of British Columbia has provided three platform policy recommendations to each of BC’s major political parties in advance of the October 19, 2024 provincial election: implementing prompt payment legislation, increasing capital and operating funding to support electrical apprentices, and naming a Minister responsible for construction in their Cabinet…. Read More…


Changing Scene

  • NOARK Partners With Innovelec, to Power the Electrical Industry in Western Canada

    NOARK Partners With Innovelec, to Power the Electrical Industry in Western Canada

    September 26, 2024 INNOVELEC, a supplier of products and services for the electrical industry in Western Canada for over 25 years,  and NOARK Electric, global manufacturer of low-voltage electrical components for industrial applications, have partnered to electrify Western Canada. Specializing in motor controls and protection for Original Equipment Manufacturers, System Integrators and Panel Builders, Noark Electric… Read More…

  • Mitsubishi Electric Sales Canada Inc. and Efficiency Capital Partner to Cross Promote Low-Carbon Building Solutions in Canada

    Mitsubishi Electric Sales Canada Inc. and Efficiency Capital Partner to Cross Promote Low-Carbon Building Solutions in Canada

    September 23, 2024 Efficiency Capital (EC), Canada’s first Energy-as-a-Service (EaaS) company, and Mitsubishi Electric Sales Canada Inc. (MESCA) announced a strategic cross promotional partnership to make low-carbon building solutions more accessible to building owners and operators across Canada. Energy efficiency in buildings, despite being one of the critical pathways to meet Canada’s climate goals, faces… Read More…

  • Siemens to Carve out Electric Vehicle Charging Business to Enable next Level of Growth

    Siemens to Carve out Electric Vehicle Charging Business to Enable next Level of Growth

    September 23, 2024 Siemens has announced the intention to carve out its eMobility business. The company bundled its eMobility charging activities in 2018 and subsequently organized it into a separate business unit in 2022.  The carve out of Siemens eMobility, which has a strong technological core and portfolio, will give the business entrepreneurial freedom to… Read More…

  • FLO Confirms FLO Station Eligibility for ZEVIP Funding

    FLO Confirms FLO Station Eligibility for ZEVIP Funding

    September 24, 2024 Canada recently announced trade measures impacting vehicles from China and limiting eligibility under the Natural Resources Canada (NRCan) Zero Emission Vehicle Infrastructure Program (ZEVIP) to electric vehicle (EV) charging products manufactured in countries that have negotiated free trade agreements with Canada. Effective October 1, 2024, this directive is expected to have an impact on… Read More…