The Importance of Trip-Free Operation and Its Characteristics

Trip-free circuit breakers

 

Anthony T. Ricciuti

One of the many often desirable characteristics in the specifications and marketing literature for medium voltage circuit breakers is “trip-free.” Unfortunately, there are many misconceptions about this characteristic.
Definitions

For IEEET rated products, there are several related definitions of “trip-free”:

•    In the most general definition of “trip-free,” the contacts of the circuit breaker must return tothe open position and remain there when an opening operation follows a closing operation,regardless of whether the closing signal, force,or action is maintained.

•    A common variant is called “electrically trip-free.” For a medium voltage circuit breaker tobe considered electrically trip-free, the circuit breaker must be able to receive and respond to an electrical opening signal regardless of whether an electrical closing signal is energized.

•    “Mechanically trip-free” operations refer to a mechanical release mechanism that can open the medium voltage circuit breaker regardless of whether any closing release device operated by any means is activated or maintained.Medium voltage circuit breakers can also be hydraulically trip-free or pneumatically trip-free if they contain a hydraulic or pneumatic opening release device, respectively,that are capable of opening the circuit breaker regardless of whether any closing release device operated by any means is activated or maintained.

Any of these variants of trip-free operation may include a trip-free relay, in which its operation alters a closing release circuit, permitting an opening release to operate unimpeded by a closing release operation in any state. For IEC rated products, although the standard recommends that the suitability for trip-free operations should be provided to customers that are specifying medium voltage circuit breakers,no specific definition is provided for this function.

Physical requirements

For IEEE rated products, if a mechanical opening release operation is maintained on a medium voltage circuit breaker, then any closing release operation signal must not result in contact movement that reduces the open gap between the contacts by more than 10%. This characteristic is often confused with the definition of trip-free.However, if any opening release operation isinitiated simultaneously with any closing release operation signal, contact movement up to and including a momentary touching of the main circuit breaker contacts is acceptable before the circuit breaker completes the opening operation.

Additionally, because electrical opening release operation circuits typically employ auxiliary switch contacts internal to the circuit breaker, and therefore the electrical release operation circuit remains open until the main contacts of the circuit breaker have closed, when an electrical opening release operation circuit is maintained, the momentary touching of the main contacts is acceptable before the circuit breaker completes the opening operation.

Figure 1: Eaton medium voltage circuit breaker operation

Eaton Circuit breaker


Anthony T. Ricciuti is a Specialist Engineer at Eaton, a power management company with 2014 sales of US$22.6 billion. Anthony has a Bachelor’s degree in Mechanical Engineering and more than 20 years of experience in the design, testing, and analysis of circuit breakers. This article first appeared as an Eaton white paper, www.eaton.com/Eaton/OurCompany/WhitePapers/FeaturedWhitePapers/index.htm.

Related Articles


Latest Articles

  • Clarification from ESA on Labour Mobility Updates Between Provinces

    Clarification from ESA on Labour Mobility Updates Between Provinces

    July 14, 2025 Effective July 1st, 2025, ESA implemented changes required under the Bill 2Protect Ontario Through Free Trade within Canada Act, 2025 and the Ontario Labour Mobility Act, introduced by the Government of Ontario. These legislative updates aim to reduce interprovincial barriers and support the mobility of qualified tradespeople across Canada. Out of Province Master Electrician… Read More…

  • Peerless Electric’s Journey: 86 Years of Canadian Manufacturing

    Peerless Electric’s Journey: 86 Years of Canadian Manufacturing

    July 4, 2025 The story of Peerless Electric begins in 1939, at the heart of Montreal, in a time of great global uncertainty. As the world edged toward war and economies struggled to recover from the Great Depression, a small group of innovators dared to dream big: to create lighting solutions that would stand the… Read More…

  • 2025 Industry Research Reveals How to Thrive in a Shifting Electrical and Automation Landscape

    2025 Industry Research Reveals How to Thrive in a Shifting Electrical and Automation Landscape

    July 4, 2025 EFC is proud to share its 2025 Industry Research report — a comprehensive look into the changing dynamics of the Canadian electrical and automation markets. This year’s report dives deep into the evolving expectations of customers as our industry navigates supply chain pressures, digital transformation, and sustainability demands. Based on input from… Read More…

  • The Growing Presence of Women in Quebec Construction Industry

    The Growing Presence of Women in Quebec Construction Industry

    July 4. 2025 The presence of women in the construction industry continues to grow in Quebec. In 2024, there were 7,885 women working in various trades. 3,589 Quebec contractors hired at least one woman on their construction sites, an all-time high. Of this number, nearly 480 companies operate in the electrical sector. The CMEQ salutes… Read More…


Changing Scene