Guide to the Canadian Electrical Code, Part 1[i] – A Road Map: Section 42 — Electric Welders

September 15, 2025

by William (Bill) Burr[i]


The Code is a comprehensive document. Sometimes it can seem quite daunting to quickly find the information you need. This series of articles provides a guide to help users find their way through this critical document. This is not intended to replace the notes in Appendix B or the explanations of individual requirements contained in the CEC Handbook but will hopefully provide some help in navigating the Code. These notes are based on the 26th edition.

Section 42 — Electric Welders

Rule 42-000 Scopestates that Section 42 is a supplementary or amendatory section of the code and applies to the installation of electric welders. There are two main types of welders – arc and resistance welders. Arc welders use a sacrificial rod to weld the metal target material together. Resistance welders fuse the metal target material together. Arc welders are divided further into transformer and motor-generator types.

Rule 42-002 Special terminologycontains definitions for special terms that apply to Section 42 that are not defined in Section 0 such as: actual primary current, duty cycle, and rated primary current. These terms will be important when calculating the ampacity of the supply conductors for welders.

Rule 42-004 Receptacles and attachment plugs – along with Appendix B notes, outlines that

  • where receptacles are installed for the plug and cord-connection of a portable welder, the ampacity rating of the overcurrent protection for the circuit can be more than the rating of the receptacle, but the receptacle must have a rating equal to or greater than the ampacity of the supply cable required for the primary current of the cord-connected welder. This is important because the high instantaneous inrush start-up current of the welder will exceed the branch circuit conductor ampacity. This prevents nuisance tripping.
  • where a welder receptacle is installed, it must be labeled to indicate:
    • the receptacle is for a welder connection only,
    • the AWG size of the insulated conductors,
    • whether the insulated supply conductor is Cu/Al,
    • the conductor insulation designation and temperature rating, and
    • the ampere rating of the overcurrent device protecting the receptacle insulated supply conductors based on the duty rating (80% or 100%)
Transformer arc welders and inverter welders

Rule 42-006 Supply conductorsprovides the factors in determining the ampacity of insulated supply conductors for transformer type arc or inverter welders. The ampacity depends on the duty cycle of a single welder, as in sub-rule (1) and the demand factors where a group of welders are supplied by one circuit as in sub-rule (2).  Table 42A shows the correlation between duty cycle and demand factor and determination of the demand factor for multiple welder installations.

Rule 42-006: Supply Conductors
  • Individual Welders – For each transformer arc welder or inverter welder installed individually, the ampacity of the insulated supply conductors must be at least equal to the rated primary current of the welder (in amperes) multiplied by the corresponding factor listed in Table 42A.
  • Groups of Welders -When supplying a group of transformer arc welders or inverter welders from a single circuit, the ampacity of the supply conductors must be at least the sum of the current values determined for each welder using the method above, with the following demand factors applied:
    • 100% of the two largest calculated currents
    • 85% of the third largest calculated current
    • 70% of the fourth largest calculated current
    • 60% of the calculated currents for all remaining welders in the group
  • Reduced Values for Low Duty Cycles -Lower ampacity values than those specified above are allowed if the nature of the work makes a high operating duty cycle for individual welders impossible.

Rule 42-008: Overcurrent Protection for Transformer Arc Welders and Inverter Welders – specifies the factors to be used in calculating the rating of circuit overcurrent protection:

  • Overcurrent protection for each transformer arc welder and inverter welder must be rated or set at no more than 200% of the welder’s rated primary current, unless the overcurrent device protecting the insulated supply conductors meets this requirement.
  • Every ungrounded conductor supplying a transformer arc welder or inverter welder must be protected by an overcurrent device rated or set at no more than 200% of the ampacity of the insulated conductor, as specified in Table 1, 2, 3, or 4. The next higher rating or setting may be used if:
    • The nearest standard rating of the overcurrent device is less than the required rating or setting, or
  • The required rating or setting would cause the overcurrent device to open too frequently.
  • For feeders supplying a group of transformer arc welders or inverter welders, the maximum rating or setting of the overcurrent protection must not exceed a value determined by:
    • Calculating the maximum rating or setting permitted for the welder with the highest overcurrent protection, and
    • Adding the sum of ampacities (as calculated by Rule 42-006 (1)) for all other welders in the group.

Rule 42-010 Disconnecting meansrequires that where there is no integral disconnect on the welder, a switch or disconnect must be provided to disconnect the supply conductors and must have sufficient current rating capacity to accommodate the overcurrent protection as specified in Rule 42-008.

Motor-generator arc welders

Rule 42-012 Conductors, protection, and control of motor-generator arc welders – specifies that the requirements for insulated conductors, protection, and control of motor-generator arc welders are primarily governed by Sections 4 and 28. However, there are a few notable exceptions:

  • Motors must be marked in amperes only.
    • If a controller is built-in as an integral part of the motor-generator set, it does not need to be separately marked, if all necessary data are included on the motor nameplate.
  • For an individual motor-generator arc welder, the ampacity of its insulated supply conductors must be at least the rated primary current (in amperes) of the welder multiplied by the applicable factor found in Table 42B.
  • When supplying a group of motor-generator arc welders, the ampacity of the insulated supply conductors must be not less than the sum of the calculated currents for each welder (using the method above), multiplied by the following demand factors:
    • 100% of the two highest calculated currents in the group
    • 85% of the third largest calculated current
    • 70% of the fourth largest calculated current
    • 60% of the calculated currents for all remaining welders in the group
  • In situations where it is impossible for individual welders to operate at a high duty cycle due to the nature of the work, lower values than those specified above may be used.
Resistance welders

Rule 42-014 Supply conductors for resistance weldersprovidesthe factors in determining the ampacity of insulated supply conductors serving resistance welders according to the various operating conditions of the equipment:

  • Individual seam or automatically fed resistance welders – the insulated supply conductors must have an ampacity of at least 70% of the welder’s rated primary current when operated at varying values of primary current or duty cycle.
  • Manually operated, non-automatic resistance welders – for welders operated at different times with different primary current or duty cycle values, supply conductors must have an ampacity of at least 50% of the rated primary current.
  • Welders with known and constant primary current and duty cycle – the ampacity of supply conductors should not be less than the value obtained by multiplying the actual primary current by the appropriate factor found in Table 42C.
  • Conductors supplying multiple resistance welders – the ampacity required is at least the sum of the following:
    • The ampacity for the welder with the largest calculated supply conductor requirement (using the factors described above).
    • 60% of the conductor ampacities calculated for all other welders in the group.

42-016 Overcurrent Protectionspecifies the factors in determining the rating of the overcurrent protection:

  • Each resistance welder must have overcurrent protection rated or set at no more than 300% of its rated primary current, unless the device protecting supply conductors offers equivalent protection.
  • Each ungrounded conductor of a resistance welder must have overcurrent protection rated or set at no more than 300% of the conductor’s ampacity (as per Tables 1–4). The next higher standard rating is allowed if:
    • the nearest standard rating is less than required; or
    • the required rating causes nuisance tripping.
  • For feeders supplying multiple welders, the maximum overcurrent device rating is the highest permitted for any single welder plus the total ampacities calculated for the rest as per Rule 42-014.

Rule 42-018 Control of resistance welders – requires that a resistance welder have a disconnecting switch or circuit breaker rated at not less than the capacity of the insulated supply conductors, as per Rule 42-014 to isolate the welder from the supply circuit.

Rule 42-020 Nameplate data for resistance welders – requires data specific to the resistance welder to be provided on the nameplate including rated KVA at 50% duty cycle, maximum and minimum open-circuit secondary voltage, short circuit current and the throat and gap setting.

In the next installment, we will be discussing Section 44 — Theatre installations


[i] Source: CSA C22.1:24, Canadian Electrical Code, Part 1 – Safety Standard for Electrical Installations. © 2024 Canadian Standards Association. Please visit store.csagroup.org. With the permission of CSA Group, material is reproduced from CSA Group standard CSA C22.1:24, Canadian Electrical Code, Part 1 – Safety Standard for Electrical Installations. This material is not the complete and official position of CSA Group on the referenced subject, which is represented solely by the Standard in its entirety. While use of the material has been authorized, CSA Group is not responsible for the manner in which the data are presented, nor for any representations and interpretations. No further reproduction is permitted. For more information or to purchase standard(s) from CSA Group, please visit store.csagroup.org or call 1-800-463-6727.

[i] William (Bill) Burr is an associate member of the Canadian Electrical Code, Part 1, Technical Committee and formerly Chair of the Canadian Advisory Council on Electrical Safety (CACES), Chief Electrical and Elevator Inspector for the Province of BC & the Northwest Territories, Director of Electrical and Gas Standards Development and Director of Conformity Assessment at CSA Group. Bill can be reached at Burr and Associates Consulting billburr@gmail.com.

Related Articles


Latest Articles

  • EHRC Destination Trade Program for Third and Fourth-Year Apprentices

    EHRC Destination Trade Program for Third and Fourth-Year Apprentices

    May 14, 2026 Providing financial incentives of up to $5,000 to employers who create new Work-Integrated Learning (WIL) opportunities for third and fourth-year apprentices. Electricity Human Resources Canada’s (EHRC) Destination Trade program is Canada’s third- or fourth-year apprentice work placement initiative for the electricity industry, providing wage subsidies of up to $5,000 to small to Read More…

  • Record Attendance Marks Strong Return for MEET 2026

    Record Attendance Marks Strong Return for MEET 2026

    May 14, 2026 By Electro Federation Canada The Mechanical Electrical Electronic Technology (MEET) show saw a powerful return to Moncton, NB on May 6-7, setting a new attendance record with 7,532 participants attending the two-day event. The biennial show, now in its 26th edition, is touted as the premier industry trade show in the region Read More…

  • LLM Cybersecurity Is Now a Construction Cybersecurity Problem

    LLM Cybersecurity Is Now a Construction Cybersecurity Problem

    May 14, 2026 By Melvin Newman, PataBid CEO In a previous article, we covered how to write effective AI prompts and the real productivity benefits LLMs (large language models) can bring to construction estimating and operations. If you haven’t read it yet, it’s worth starting there. This article picks up where that one left off, Read More…

  • Smart Planning and Innovation Drive Success in Winnipeg Retrofit

    Smart Planning and Innovation Drive Success in Winnipeg Retrofit

    May 14, 2026 The Darling Ingredients retrofit project recently wrapped in Winnipeg—and it’s already being hailed as a model for future upgrades across the company’s North American facilities. Black & McDonald’s electrical division was tasked with replacing the motor control centres (MCCs) at the rendering plant, a high-stakes environment where downtime simply isn’t an option. Read More…


Changing Scene

  • Luminis Wins Red Dot Award for Ellington

    Luminis Wins Red Dot Award for Ellington

    May 14, 2026 Luminis, an established innovator and manufacturer of specification-grade, interior and exterior lighting solutions, today announced its Ellington and Trilo families have each received a Red Dot Design Award for Product Design. Dating back to 1955, the Red Dot Design Award is one of the world’s largest design competitions. Every year, the Red Read More…

  • Quarter Century Platinum Status for PCL Construction

    Quarter Century Platinum Status for PCL Construction

    May 14, 2026 PCL Construction is proud to announce it has once again been recognized as a Platinum Club member of Canada’s Best Managed Companies, earning the distinction for 2026 and reaffirming its place among the country’s most respected and well-managed private enterprises. The recognition extends PCL’s long-standing record of excellence, marking 25 consecutive years as Read More…

  • Landscape Ontario, Electrical Safety Authority Partner to Promote Electrical Safety in Landscape Trades

    Landscape Ontario, Electrical Safety Authority Partner to Promote Electrical Safety in Landscape Trades

    May 14, 2026 Landscape Ontario Horticultural Trades Association (Landscape Ontario) and the Electrical Safety Authority (ESA) have partnered to improve electrical safety awareness and compliance across Ontario’s landscape and horticultural industry. The partnership focuses on supporting safe work around electrical infrastructure, including overhead powerlines and underground systems, and providing clarity and guidance on the application of the Ontario Read More…

  • Register Now for EFC’s Annual Conference: June 2-4, 2026

    Register Now for EFC’s Annual Conference: June 2-4, 2026

    May 14, 2026 Bringing together professionals from across Canada’s electrical industry, EFC’s annual conference offers a dynamic platform for learning, networking, and business growth. Attendees will gain valuable insights from expert speakers in the business program while also being able to take advantage of dedicated B2B Head Office meeting spaces and the ever popular Electro-Lounge Read More…